Toshiba RAS-10SKX User manual

Category
Split-system air conditioners
Type
User manual

This manual is also suitable for

SERVICE M ANUAL
SPLIT W A LL TY PE
TO SH IB A
P R IN TE D IN JA P A N , D ec.,1996 ToM o
FIL E N O . A 00-9625
AIR-CONDITIONER
RAS-10SK-E
RAS-10SA-E
RAS-10SKX
RAS-10SAX
– 2 –
CONTENTS
1. SPECIFICATIONS ........................................................................................................... 4
2. CONSTRUCTION VIEWS............................................................................................... 6
2-1. Indoor Unit .................................................................................................................................. 6
2-2. Outdoor Unit ............................................................................................................................... 7
3. WIRING DIAGRAM.......................................................................................................... 8
4. SPECIFICATIONS OF ELECTRICAL PARTS................................................................. 9
4-1. Indoor Unit .................................................................................................................................. 9
4-2. Outdoor Unit ............................................................................................................................... 9
5. REFRIGERANT CYCLE DIAGRAM .............................................................................. 10
6. MICRO-COMPUTER BLOCK DIAGRAM.......................................................................11
7. OPERATION DESCRIPTIONS ...................................................................................... 12
7-1. FAN ONLY Operation ............................................................................................................... 12
7-2. COOL Operation....................................................................................................................... 12
7-2-1. Louver Control ......................................................................................................................................13
7-3. DRY Operation.......................................................................................................................... 13
7-4. AUTO Operation ....................................................................................................................... 14
7-4-1. Temporary Auto .....................................................................................................................................14
7-5. ECONO. Mode........................................................................................................................... 15
7-5-1. Cooling...................................................................................................................................................15
7-6. Low-Temperature Limit Control (Cooling Operation) .......................................................... 15
7-7. Auto Restart Function ............................................................................................................. 16
7-7-1. How to Set the Auto Restart.................................................................................................................16
7-7-2. How to Cancel the Auto Restart ..........................................................................................................17
7-7-3. In Case of Power Failure during the Timer Operation.......................................................................17
8. INSTALLATION PROCEDURE...................................................................................... 18
8-1. Safety Cautions ........................................................................................................................ 18
8-2. Installation Diagram of Indoor and Outdoor Units............................................................... 20
8-3. Installation ................................................................................................................................ 21
8-3-1. Optional Parts........................................................................................................................................21
8-3-2. Installation Parts ...................................................................................................................................21
8-4. Indoor Unit ................................................................................................................................ 22
8-4-1. Cutting a Hole and Mounting Installation Plate .................................................................................22
8-4-2. Electrical Work ......................................................................................................................................23
8-4-3. Wiring Connection ................................................................................................................................24
8-4-4. Piping and Drain Hose Installation......................................................................................................26
8-4-5. Indoor Unit Installation .........................................................................................................................27
8-4-6. Drainage.................................................................................................................................................27
8-5. Outdoor Unit ............................................................................................................................. 28
8-5-1. Refrigerant Piping Connection ............................................................................................................29
8-5-2. Vacuum Pumping ..................................................................................................................................29
8-5-3. Wiring Connection ................................................................................................................................30
8-6. Others........................................................................................................................................ 31
8-6-1. Gas Leak Test ........................................................................................................................................31
8-6-2. Test Operation .......................................................................................................................................31
8-6-3. Auto Restart Setting .............................................................................................................................31
– 3 –
9. TROUBLESHOOTING CHART ..................................................................................... 32
9-1. What to be Prechecked First .................................................................................................. 32
9-1-1. Power Supply Voltage...........................................................................................................................32
9-1-2. Incorrect Cable Connection between Indoor and Outdoor Units.....................................................32
9-1-3. Misleading but Good Operations.........................................................................................................33
9-2. Primary Judgement of Trouble Sources ............................................................................... 34
9-2-1. Role of Indoor Unit Controller..............................................................................................................34
9-2-2. Display of Abnormalities and Judgement of the Abnormal Spots...................................................34
9-3. Troubleshooting Flowcharts................................................................................................... 38
9-3-1. Power can not be Turned on ................................................................................................................38
9-3-2. Power can not be Turned on after Replacing Indoor PC Board .......................................................39
9-3-3. Outdoor Unit does not Operate ...........................................................................................................39
9-3-4. Only Compressor does not Operate ...................................................................................................40
9-3-5. Only Outdoor Fan does not Operate ...................................................................................................41
9-3-6. Only the Indoor Fan does not Operate................................................................................................42
9-4. How to Check the Remote Control (Including the Indoor PC Board) ................................ 43
9-4-1. How to Check the PC Board.................................................................................................................44
9-4-2. PC Board Layout ...................................................................................................................................46
9-4-3. How to Reduce the Operation Time of the Anti-Restart Timer .........................................................47
10. PART REPLACEMENT ................................................................................................. 48
10-1. Indoor Unit ................................................................................................................................ 48
10-2. Microcomputer ......................................................................................................................... 50
10-3. Outdoor Unit ............................................................................................................................. 51
11. CAUTIONS ON REPLACEMENT OF PC BOARD ASSEMBLY.................................... 52
12. EXPLODED VIEWS AND PARTS LIST........................................................................ 53
12-1. Indoor Unit (1)........................................................................................................................... 53
Indoor Unit (2)........................................................................................................................... 54
12-2. Outdoor Unit ............................................................................................................................. 55
– 4 –
COOLING
Single
220/230/240
50
0.83/0.85/0.88
95/92/90
16
1.2
44/36/31
44/45/45
R-22
0.73
Capillary tube
9.52
Flare connection
6.35
Flare connection
10
5
16
RAS-10SK-E/RAS-10SKX
265
790
174
8
Finned tube
Cross flow fan
650
510
430
19
Polypropylene net filter (Washable)
RAS-10SA-E/RAS-10SAX
530
770
200
29
Finned tube
Propeller
1600
18
PH102T1-4C
750
Fuse, Overload relay
Ye s
21 ~ 43
1. SPECIFICATIONS
Specifications are subject to change without notice.
Model
kW
Phase
V
Hz
kW
%
A
Indoor/Outdoor
A
lit/h
dB
dB
kg
mm
mm
m *2
m
mm
mm
mm
mm
kg
m
3
/h
m
3
/h
m
3
/h
W
mm
mm
mm
kg
m
3
/h
W
W
°C
Item
Capacity
Power source
Power consumption
Power factor
Running current
Starting current
Moisture removal
Noise
Refrigerant
Refrigerant control
Interconnection pipe
Condensate drain pipe
INDOOR UNIT
Dimensions
Net weight
Evaporator type
Indoor fan type
Air volume
Fan motor output
Air filter
OUTDOOR UNIT
Dimensions
Net weight
Condenser type
Outdoor fan type
Airflow volume
Fan motor output
Compressor
Safety device
Auto louver
Usable outdoor temperature range
*1
Indoor (H/M/L)
Outdoor (220/230/240V)
Name of refrigerant
Rated volume
Gas side size
Connection type
Liquid side size
Connection type
Maximum length (of one way)
Maximum height difference
Indoor unit
Outdoor unit
Outer diameter
Height
Width
Depth
High fan
Medium fan
Low fan
Height
Width
Depth
Model
Output
220V
2.65
240V
2.70
230V
2.70
220V
2.70
240V
2.70
230V
2.65
220V
0.15/3.82
230V
0.15/3.87
240V
0.15/3.92
RAS-10SK-E/10SA-E
RAS-10SKX/10SAX
– 5 –
Note : *1
Capacity is based on the following temperature conditions.
JIS C9612-1994
Cooling
27°C
19°C
35°C
24°C
Condition
(DB)
(WB)
(DB)
(WB)
Temperature
Indoor unit inlet air temperature
Outdoor unit inlet air temperature
Notes : *2 CHARGELESS
No additional refrigerant required.
This air conditioner accepts a connection piping length of up to 10m and a head of up to 5m.
There is no need to add the refrigerant as long as the total length of the connection piping is up to 10m.
– 6 –
2. CONSTRUCTION VIEWS
2-1. Indoor Unit
RAS-10SK-E
RAS-10SKX
Air filter
790
Heat exchanger
Air inlet
265
Air outlet
47
10
50
174
47
10
50
Wireless
remote
control
55
16
559.6
Remote
control
holder
112.8
136
Knock out system
790
232 326 232
Hanger
321
Drain hose (0.54m)
Connecting pipe (0.39m)
(Flare ø6.35)
(Flare ø9.52)
Hanger
65965.5
326
450
65.5
For stud bolt
(ø8~ø10)
For stud bolt
(ø6)
Hanger
Minimum
distance to wall
Minimum
distance
to ceiling
265
Knock out system
Front panel
Back body
20 2037
40.5
60.5
790
12626931976
Center line
Installation
plate outline
HangerHanger
40.5
3.5
Hanger
Minimum
distance
to wall
17 20
46
120 or more 120 or more
66 or more
2.5
Connecting pipe (0.49m)
1800
10SK-E : Without power cord
10SKX : With power cord
– 7 –
2-2. Outdoor Unit
RAS-10SA-E
RAS-10SAX
600 85
36
111
ø25 Drain hole
50
30
216
230
8-ø6 Holes
(For fixing the outdoor unit)
4-ø11x14 Long holes
(For anchor bolt ø8-ø10)
Gas side (flare ø9.52)
Liquid side (flare ø6.35)
111
A
600
R10
50
36
25
216
230
ø11x14 Hole
ø6 Hole
Handle
11
525
530
5
268
Fan guard
ø420
TOSHIBA
770 59
89
200
11
12
Electric
parts cover
Z
54 62
Access for
charging
250
Z
View
600
45 or more
Inlet port
600 or more
(Minimum distance
of the wall)
4-ø11x14 Long holes
(For anchor bolt ø8-ø10)
200 or more
Outlet
port
Center
port
230
100 or more
Inlet port
Visible outline
of the product
A
Detail Drawing
Mounting dimension of anchor bolt
268
770
59
89
– 8 –
3. WIRING DIAGRAM
1
2
3
4
5
6
789
1
2
3
4
5
6
789
1
23
4
5
6
789
1
2
1
2
1
2
1
2
L
N
1
2
3
4
6
5
IC
FAN MOTOR
WHI
WHI
PNK
BLK
BLK
BLK
RED
RED
RED
RUNNING
CAPACITOR
RUNNING
CAPACITOR
OVER LOAD
RELAY
GRN & YEL
CHASSIS
INDOOR
OUTDOOR
BLK
WHI
GRN&YEL
GRN&YEL
P04
BLK
BRW
BLU
PNK
YEL
ORN
RED
BRW
GRY
GRY
BLU
CN04
CN07
CN10
BLU
CN03 CN01
CN13
CN25
BLK
BLK
BLK
BLK
IC01
IC02
C06
DC 35V
DC 12V
DC 7V
DC 0V
T01
MAIN P.C. BOARD
MCC-713
C02
DB01
R01
C01
L01
C15
IC04
R109
F01 FUSE
T3.15A
250V
R21
RY01
RY02
WHI
BLK
3
4
3
4
POWER
TERMINAL
BLOCK
INDOOR
TERMINAL
BLOCK
INFRARED RAYS RECEIVE
AND INDICATION PARTS
THERMO
SENSOR
(TA)
HEAT
EXCHANGER
SENSOR
(TC)
LOUVER
MOTOR
FAN MOTOR
:
:
:
:
:
:
:
:
:
:
BROWN
RED
WHITE
YELLOW
BLUE
BLACK
GRAY
PINK
ORANGE
GREEN &
YELLOW
BRW
RED
WHI
YEL
BLU
BLK
GRY
PNK
ORN
GRN&YEL
COLOR IDENTIFICATION
THERMAL FUSE
77˚C x 2
VARISTOR
3
1
1
2
3
4
6
5
1
2
3
4
5
1
2
3
4
5
3
1
DC
MOTOR
SG01
DSA
BLU
BLU
BLU
BLU
BLU
PNK
BLK
WHI
R116
RAS-10SK-E/SA-E
220/230/240V ~
50Hz
RAS-10SKX/SAX
220/230/240V ~
50Hz
L
N
L
N
Model Section A
Section A
1
2
1
2
COMPRESSOR
BLU
YEL
BLK
RED
WHI
OUTDOOR
TERMINAL
BLOCK
DSA : Surge absorber
– 9 –
Parts name
Fan motor (for indoor)
Thermo sensor
(TA-sensor)
DC-DC transformer (T01)
Microcomputer
Power relay (RY01), Com-
mon relay (RY02)
Heat exchanger sensor
(TC-sensor)
Line filter (L01)
Diode (DB01)
Capacitor (C02)
Fuse (F01)
Power supply IC (IC01)
Varistor (R21, R109)
Resistor (R01)
Louver motor
Specifications
DC 35V, 19W
10k at 25°C
DC390V, Secondary DC35V, 12V, 7V
Coil : DC12V 75mA, Rated AC250V 20A
10k at 25°C
10mH, AC 0.6A
4A, 600V
100µF, 450V
T3.15A, 250V
4A, 600V
560V
5.6 , 5W
Output (Rated) 2W, 10poles, 1phase DC 12V
4. SPECIFICATIONS OF ELECTRICAL PARTS
4-1. Indoor Unit
RAS-10SK-E
RAS-10SKX
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Type
ICF-35-19-3
or
TICF-35-19-3
(microprocessor)
SWT-34
TMP87CK40F
DI1U
(microprocessor)
RF-103YOR6
RBV-406
CEAUF2W101M20
MT3
MA2830-FJ
15G561K
ERF-5TK5R6
MP35EA7
Specifications
Output (Rated) 750W, 2pole, 1phase, 220/230/240V, 50Hz
Winding resistance ()
(at 20°C)
Output (Rated) 18W, 6pole, 1phase, 220/230/240V, 50Hz
Winding resistance ()
(at 20°C)
500V AC, 1.5µF
400V AC, 25µF
U/T 6.1A (80°C), OPEN 135±5°C, CLOSE 78±11°C
No.
1
2
3
4
5
Type
PH102T1-4C
UE6-21SJ5P
SK-50FMP
SK-40CMP25U1
J-MRA99285-9201
Parts name
Compressor
Fan motor (for outdoor)
Running capacitor
(for fan motor)
Running capacitor
(for compressor)
Overload relay
Red-Black
3.88
White-Black
5.06
White-Black
370
Red-Black
370
4-2. Outdoor Unit
RAS-10SA-E
RAS-10SAX
– 10 –
5. REFRIGERANT CYCLE DIAGRAM
RAS-10SK-E / RAS-10SA-E
RAS-10SKX / RAS-10SAX
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
10SK-E
10SKX
13.0
18.0
2.0
Standard pressure
P
(kg/cm²G)
10SK-E
10SKX
5.0
6.5
4.0
Outdoor
35/24
43/26
21/15
Cooling
50Hz
Standard
High temperature
Low temperature
Ambient temp.
conditions DB/WB
(°C)
Fan speed
(indoor)
High
High
Low
Indoor
27/19
32/23
21/15
Fig. 5-1
Table 5-1
Evaporator
Indoor unit
Cross flow fan
Optional piping kits
RB-P31BFH1 (3m)
RB-P51BFH1 (5m)
RB-P71BFH1 (7m)
Compressor
Accumulator
Condenser
Propeller fan
Outdoor unit
Dryer
Capillary tube
ø1.5x1200
PH102T1-4C
Mark ( ) means check points of Gas Leak
O.D.:9.52mm O.D.:6.35mm
Cooling
Packed valve
(ø9.52)
Packed valve
(ø6.35)
0.39m
(Connecting pipe)
ø9.52
0.49m
(Connecting pipe)
ø6.35
T1
P
Refrigerant
R-22 0.73kg
– 11 –
6. MICRO-COMPUTER BLOCK DIAGRAM
Infrared Rays Signal Receiver
Functions
ECONO.
Louver Direction Setting
Louver AUTO Swing
OFF TIMER Setting
ON TIMER Setting
Fan Speed Selection
Thermo Setting
Operation Mode Selection
AUTO, COOL, DRY, FAN ONLY
Operation (START/STOP)
Relay Driver, Louver Driver
Clock Frequency
Oscillator Circuit
Heat Exchanger Sensor
Infrared
Rays
Initializing Circuit
C. P. U
Main Unit Control Panel
AC 220/230/240V~
50Hz
Remote Control
Operation
Display
Timer
Display
ECONO.
Sign Display
FAN-ONLY
Sign Display
Indoor
Fan Motor
Louver
ON/OFF Signal
Compressor, Outdoor Fan
ON/OFF Signal
Louver
Motor
Compressor
RY02
RY01
Noise Filter
Power Supply
Circuit
Outdoor Fan Motor
Relay
Thermo Sensor
• Louver Control
• 3-minute Delay at Restart for Compressor
• Motor Revolution Control
• Processing
(Temperature Processing)
• Timer
Relay
– 12 –
7. OPERATION DESCRIPTIONS
7-1. FAN ONLY Operation
(MODE of the remote control : FAN ONLY)
(1) During this mode, the relay RY01 is always turned
off so that only the indoor fan is operated. RY02
is always turnd on. FAN-ONLY display is lit.
1) When the FAN is set to AUTO, the indoor fan
motor operates as shown in Fig 7-1-1.
2) When the FAN is set to LOW, MED, or HIGH,
the indoor fan motor operates with a constant
in volume as listed in Table 7-1-1.
7-2. COOL Operation
(MODE of the remote control : COOL)
(1) Compressor, outdoor fan and operation display
are controlled as shown in Fig. 7-2-1.
Fig. 7-2-2
(3) Once the setting is made, the operation mode is
memorized in the microcomputer so that the same
operation can be effected thereafter simply by
pushing the START/STOP button.
Fig. 7-1-1 Auto setting of air volume
Table 7-1-1 Manual setting of FAN SPEED
Indication of
FAN SPEED
LOW
MED
HIGH
HIGH Air volume
(m
3
/h)
430
510
650
(2) Once the setting is made, the operation mode is
memorized in the microcomputer so that the same
operation can be effected thereafter simply by
pushing the START/STOP button.
Fig. 7-2-1
(2) Relays RY01 and RY02 are turned on to energize
the outdoor unit, and a cool operation is carried
out.
1) When the FAN is set to AUTO, the indoor fan
motor operates as shown in Fig 7-2-2.
2) When the FAN is set to LOW, MED, or HIGH,
the indoor fan motor operates with a constant
in volume as listed in Table 7-1-1.
(Room temp. – Set temp.)
MED
LOW(+)
LOW
LOW
(continuous)
+4
+3
+2
+1
0
RY01
OFF
Set
temp.
Manual
FAN
According
to the set
position
HIGH
AUTO
(Room temp. – Set temp.)
+1
0
Set
temp.
ON
OFF
OPERATION
display
ON ON
Compressor
Outdoor fan
(RY01)
Common relay
(RY02)
HIGH
MED
LOW(+)
LOW
LOW
28
27
26
25
24
Room temp.
– 13 –
7-2-1. Louver Control
(1) By pushing the SET button of the remote control
during the operation, the louver can be set to the
desired position.
And the louver position is stored in the microcom-
puter, the louvers will be set to the position au-
tomatically at the next operation.
(2) When the AUTO button is pushed, the louver ver-
tically swings within range of 25deg.
7-3. DRY Operation
(MODE of the remote control : DRY)
(1) Compressor, outdoor fan and operation display
are controlled as shown in Fig. 7-3-1.
Fig. 7-3-2
Fig. 7-3-1
The microprocessor turns the compressor on
and off at regular intervals (4 to 6 minutes on
and/or off). During the compressor off, the
indoor fan will operate in the super low position.
The indoor fan will operate in the AUTO
position.
(2) The pattern of operation depending on the relation
between room temperature and set temperature
is shown below:
Room temp.
Set temp.+1
Set temp.
Compressor
Outdoor fan
Indoor fan
L.
*
S.L. S.L.L. L. S.L. L.
ON ON ON ON
OFF OFF OFF
*
Super Low
(Room temp. – Set temp.)
Set
temp.
ON
+3
+2
+1
0
OFF
OPERATION
display
Compressor
Outdoor fan
(RY01)
Common relay
(RY02)
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
ON
– 14 –
7-4. AUTO Operation
(MODE of the remote control : AUTO)
(1) One of the 2 modes, Cooling or Dry is selected
according to room temperature at which operation
is to start, as shown in Fig. 7-4-1. The Fan mode
will continue until room temperature reaches a
level at which another mode is selected.
7-4-1. Temporary Auto
When the TEMPORARY button is pushed, the set
temperature is fixed at 24°C and controlled in accor-
dance with the chart shown in Fig. 7-4-1.
Fig. 7-4-1
Cooling mode
Cooling mode
Dry mode
+4
+1
(The same cooling mode as the room temperature control is set at set temp. –1˚C)
The Louver moved downward.
(The same cooling mode as the room temperature control is set at set temp. –1˚C)
(The same dry operation as the room temperature control is set at set temp. –1˚C)
(Room temp. – Set temp.)
– 15 –
7-5. ECONO. Mode
When the ECONO. button is pushed, during COOL
and AUTO operation, the OPERATION display is
turned off and the ECONO. display is lit and the indoor
unit operates quietly and mildly with controlling airflow.
7-5-1. Cooling
(1) In the ECONO. mode, the set temp. by the remote
control is changed automatically as shown in Fig.
7-5-1.
(2) Fan speed LOW
+2
+1
Set temp.
1H 2H TIME0H
(˚C)
ECONO. button
is pushed
Set temp.
is changed
Set temp.
is changed
7-6. Low-Temperature Limit Control
(Cooling Operation)
The microprocessor detects the indoor heat exchanger
temperature so as to prevent freezing up the indoor
heat exchanger.
Control is performed as shown in Fig. 7-6-1.
Fig. 7-5-1
Compressor
Less than 5˚C continues
for 5 minutes
OFF
ON
Outdoor fan
7
Heat exchanger
temperature
5
(˚C)
Fig. 7-6-1
– 16 –
7-7. Auto Restart Function
This unit is equipped with an Automatic restarting
facility which allows the unit to restart and resume the
set operating conditions in the event of a power supply
shutdown without the use of the hand control.
The operation will resume without warning three
minutes after the power is restored.
The Auto Restart function is set not to work on
shipment from the factory, and so it is necessary to
set it to function as required.
7-7-1. How to Set the Auto Restart
To set the Auto Restart function, proceed as follows:
Access the TEMPORARY button located in the lower
right hand corner beneath the hinged front panel of
the indoor unit (please refer to section on PARTS
NAME). The power supply to the unit must be on -
the function will not be set if the power is off.
To enable the Auto Restart function, press the
TEMPORARY button continuously for three seconds.
The unit will acknowledge the setting and beep three
times. The system will now restart automatically.
The above Auto Restart settings can be carried out:
During subsequent operation, the orange light is lit.
The Auto Restart function will not accept an
instruction if timer operation with the remote control
is selected.
(Please refer to the section on setting the timer or
setting the louver.)
When the system is stand-by (not running)
During louver swing (AUTO) operation, after restart
by the Auto Restart function the louver swing stops.
When the system is operating
OPERATION
Press the TEMPORARY button
continuously more than three
seconds.
MOTION
Stand-by
The system starts to operate. The green light will be lit.
about three seconds after
The unit beeps three times. The orange light will be lit.
The system is operating. The orange light is lighting.
If the system is not required to run at this time, press the TEMPORARY
button once more or use the remote control and the unit will stop.
OPERATION
Press the TEMPORARY button
continuously more than three
seconds.
MOTION
Operating The green light is lit.
The system stops to operate. The green light is turned off.
about three seconds after
The unit beeps three times.
The system stops.
If the system is not required to stop at this time, use the remote control
and to restart.
TEMPORARY
0
3S
TEMPORARY
0
3S
– 17 –
7-7-2. How to Cancel the Auto Restart
To cancel the Auto Restart function, proceed as
follows:
Repeat the setting procedure: the unit will
acknowledge the instruction and bleep three times.
The system will now be required to manually restart
with the remote control after the main supply is turned
off.
Cancellation is carried out:
When the system is stand-by (not running)
OPERATION
Press the TEMPORARY button
continuously more than three
seconds.
MOTION
Stand-by
The system starts to operate. The orange light will be lit.
about three seconds after
The unit beeps three times. The green light will be lit.
The system is operating.
If the system is not required to run at this time, press the TEMPORARY
button once more or use the remote control and the unit will stop.
When the system is operating
OPERATION
Press the TEMPORARY button
continuously more than three
seconds.
MOTION
Operating The orange light is lit.
The system stops to operate. The orange light is turned off.
about three seconds after
The unit beeps three times.
The system stops.
If the system is not required to stop at this time, use the remote control
and to restart.
During subsequent operation, the green light is light-
ing.
7-7-3. In Case of Power Failure during the
Timer Operation
(1) If ON-TIMER operation is reserved with setting of
Auto Restart operation, it is cancelled with power
failure. (The OPERATION lamp on the main unit
goes on and off to inform of power failure.) In that
case, try to reserve ON-TIMER operation once
again.
TEMPORARY
0
3S
TEMPORARY
0
3S
(2) If OFF-TIMER operation is reserved without
setting of Auto Restart operation, the reservation
is cancelled with power failure. (The OPERATION
lamp on the main unit goes on and off to inform of
power failure.) In that case, try to reserve OFF-
TIMER operation. When Auto Restart operation
is set, OFF-TIMER reservation is also cancelled
with power failure.
– 18 –
8. INSTALLATION PROCEDURE
8-1. Safety Cautions
For general public use
Power supply cord of parts of appliance for Outdoor use shall be more than polychloroprene sheathed flexible
cord (design H05 RN-F), or cord designation 245 IEC 57.
CAUTION
TO DISCONNECT THE APPLIANCE FROM THE MAINS SUPPLY.
This appliance must be connected to the mains by means of a circuit breaker or a switch with a contact
separation of at least 3 mm.
If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after
installation. The plug must be disconnected from the power supply socket in order to disconnect the appliance
completely from the mains.
DANGER
` FOR USE BY QUALIFIED PERSONS ONLY.
` TURN OFF MAIN POWER SUPPLY AND BREAKER BEFORE ATTEMPTING ANY ELECTRICAL WORK.
MAKE SURE ALL POWER SWITCHES AND BREAKER TURN OFF. FAILURE TO DO SO MAY CAUSE
ELECTRICAL SHOCK.
` CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED BY
WRONG WAY, ELECTRIC PARTS MAY BE DAMAGED.
` CHECK THE EARTH WIRE IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
` DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OF GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
` TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT
WELL AWAY (MORE THAN 2M.) FROM HEAT SOURCES SUCH AS RADIATORS, HEAT RESISTORS,
FURNACE, STOVES, ETC..
` WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY
CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R-22) WITH ANY OTHER GASEOUS BODY
INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT,
THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT
RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
` IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE INSTALLATION
WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED BY
FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
Never modify this unit by removing any of the safety guards or by by-passing any of the safety interlock
switches.
Do not install in a place which cannot bear the weight of the unit.
Personal injury and property damage can result if the unit falls.
Before doing the electrical work, attach an approved plug to the power supply cord.
And make sure the equipment to be earthed.
Appliance shall be installed in accordance with national wiring requlations.
If you detect any damage, do not install the unit. Contact your Toshiba dealer immediately.
– 19 –
CAUTION
Exposure of unit or water or other moisture before installation will result in an electrical short.
Do not store in a wet basement or expose to rain or water.
After unpacking the unit, examine it carefully for possible damage.
Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise and discharged air might disturb user’s neighbors.
To avoid personal injury, be careful when handling parts with sharp edges.
Please read the installation manual carefully before installing the unit. It contains further important
instructions for proper installation.
UK Plugs and Sockets etc (Safety) Regulations 1994
SI Number 1768
With regard to Schedule 3, Item 7 of the above UK Regulations, this appliance must be permanently connected to
the fixed wiring of the main electrical supply by means other than the use of an approved 13 Amp plug-top
as outlined in the Regulations.
Electrical work must be carried by suitably qualified persons and in accordance with all relevant safety standards
and codes of practice.
We recommend that the power supply for this appliance is derived from a suitably protected dedicated circuit.
(for U.K. only)
– 20 –
8-2. Installation Diagram of Indoor and Outdoor Units
For installation of the indoor unit, use the paper pattern on the back.
3 Clip anchorClip anchor
Hook
66 mm or more
Hook
1 Installation
plate
8 Mounting screw
Hook
120 mm or more
Front cabinet
Front panel
Air filter
(Attach to the back side.)
(Attach to the back side.)
5 Shield pipe
6 Pan head
wood screw
4 Remote control
holder
2 Wireless
remote
control
9 Deodorizing
filter
10 Purifying
filter
11
Filter
frame
100 mm or more
400 mm or more
Loop the connective cable
(about 100 mm in diameter
and 300~350 mm long).
600 mm or more
Electric parts
cover
45 mm or more
600 mm or more
2
Wireless remote control
7
Batteries
Cover
6 mm thick heat resisting
polyethylene foam
Bottom
Rear
Right
Rear left
Left
Cut the piping hole
sloped slightly
Wall
120 mm
or more
For the rear and left piping
Insert the remote control holder
cushion between the indoor
unit and wall, and lift indoor
unit to make work easier.
Do not allow the drain hose to
get slack.
Make sure to run the drain
hose sloped downward.
The auxiliary piping can be
connected the left, rear left,
rear, right or bottom.
Insulation of refrigerant pipes
insulates the pipes separately,
not together.
Before install the wireless
remote control
• With the remote control cover
open, load the batteries
supplied correctly, observing
their polarity.
Extension
drain hose
(Option:
RB-821SW)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56

Toshiba RAS-10SKX User manual

Category
Split-system air conditioners
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI