  • Hello! I am an AI chatbot trained to assist you with the Viessmann VITODENS 200 Installation Instructions Manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Installation instructions
VIESMANN
for heating engineers
Vitodens 200
Type WB2A, 8.8 to 26.0 kW
Gas fired wa ll mounted con densing boi ler
Natural gas and LPG version
VITODENS 200
5862 559 GB 2/2004 Dispose after installation
Please follow these safety instructions closely to prevent accidents and
material losses.
Safety instructions explained
!
Important information
This symbol warns against the
risk of material losses and
environmental pollution.
Safety regulations
Installation, initial start-up, inspection,
maintenanc e and re pairs must be car-
ried out by a competent person (heat-
ing engineer/installation contractor).
Observe all current sa fety regulations
as defined by DIN, EN, DVGW, TRGI,
TRF, VDE or all locally applicable
standards.
See a lso the "safety instructions" in
the "Vitotec Technical Guide" folder.
Before working on the equipment/
heating sy stem, isolate the m ains
electrical supply (e.g. by removing a
separate mai ns f use or by means of a
mains electrical isolator) and safe-
guard against unauthorised reconnec-
tion.
Close the main gas shut-off valve and
safeguard against unauthorised
reopening .
Electric al assemblies p rovided on site
must be type-a pproved.
Work on gas equipment
This must only be carried out by an
approved gas fitter.
Observe all commissioning work spe-
cified for gas installations to TRGI or
TRF and all local regulations.
Safety instructions
2
5862 559 GB
Preparing for installation
Product information ................... ................................................................. 4
Preparations for boiler installation............................................................... 5
Installation
Installing the boiler and making all connections ........................................... 7
Flue gas connection .................................................................................... 8
Condensate connection .............................................................................. 8
Gas c onnection ................................................................. ......................... 8
Opening the control unit housing.................... ............................................. 10
Electrical connections............................................................................ ..... 11
&
Routing connecting cables ...... ................................................................. 13
Closing control unit housing and in serting user interface .... ......................... 14
Front panel installation............... ................................................................. 15
Commissioning and adjustments ................................................................. 15
Index
3
5862 559 GB
Vitodens 200, Type WB2A
Set up for operatio n with natural g as E .
The natural gas E version can be converted to natural gas LL or LPG P using a
conversi on kit.
Product information
4
5862 559 GB
For on-site preparation of gas, water and electrical connections, see
installation instructions, installation template or mounting frame.
A Heating flow Rp¾"
B DHW Rp½" (gas fired combination
boiler)
DHW flow G¾" (gas fired boiler)
C Gas connection
D Cold wate r Rp ½" (gas fired com bi-
nation boiler)
DHW return G¾" (gas fired boiler)
E Heating return R p¾"
F Fill & drain valve
G Cable arrang ement area
H Dimension for installation with
DHW cylinder below t he boiler.
K Condensate dr ain
Preparations for boiler installation
5
5862 559 GB
1. Prepare t he water conne ctions.
Thoroughly flush the heating sys-
tem.
2. Prepare the gas con nection
accordingtoTRGIorTRForall
local r egulation s.
3. Prepare t he electrical co nnections.
&
Mainscable:NYM-J3x1.5mm
2
,
fuse max. 16 A, 230 V~, 50 Hz.
&
Accessory cables: NYM with the
required number of conductors
for the external connections.
&
Allcablesinarea"G" shoul d
protrude 1200 mm from the wall.
Preparations for boiler installation (cont.)
6
5862 559 GB
A Heating flow
B DHW (gas fired combination boi-
ler)
DHW flow (gas fired boiler)
C Gas connection
D Cold wa ter (gas fir ed c ombinati on
boiler)
DHW return (gas fired boiler)
E Heating return
F Fill & drain valve
Installing the boiler and making all connections
7
5862 559 GB
Connect the balanc ed fl ue pipe. Flue gas system installation
instructions.
Condensate connection
Connect the condensate drain with a
pipe air vent valve sloping to the pub-
lic sewer.
Gas connection
A Gas connection
Conversion to other gas
types:
Conversion kit installation
instructions
Information regarding operation
with LPG
We recommend the installation of an
external safety solenoid valve when
installing the boiler in rooms below
ground l evel.
Flue gas connection
8
5862 559 GB
1. Carry out a leak test.
!
Important information
Excessive test pressure
leadstodamageonboiler
and gas train.
Max. test pressure
150 mbar. If a higher pres-
sure is requi red fo r l eak
tests, separate the boiler
and the gas train from the
mains gas supply (undo fit-
tings).
2. Purge th e ga s s upply pipe.
Gas connection (cont.)
9
5862 559 GB
Opening the control unit housing
10
5862 559 GB
Notes regarding the connection o f accessories
For details o f acce ssories also obs erve the separate i nstallation ins truc-
tions provided.
A Radio clock co nnection B Vitotrol 100 UTD (only for c ontrol
units operating with a constant
temperatu re)
C Vitotrol 100 UTA (only for control
units operating with a constant
temperatu re)
Electrical connections
11
5862 559 GB
Plug 230 V~
Power supply
&
Never interchange cores "L1"
and "N".
&
Install an isolator in the mains
supply line which simulta-
neously separates all non-
earthed conductors from the
mains with at least 3 mm contact
separation.
&
Max. fuse rating 16 A.
lH
&
Mains s upply - acces sories
(230 V ~ 50 Hz). Where the boi-
ler is installed in a bathroom or
shower room, the mains supply
of access ories outsi de the wet
area must not be connected to
the control unit. The p ower sup-
ply connection for accessories
canbemadeimmediatelyatthe
control unit, if the boiler is
installed outside damp areas.
This connection is directly con-
trolled with the system ON/OFF
switch (max. 3A).
&
Vitotrol 100 UTA
&
Vitotrol 100 UTD
Low voltage plug
! Outside temperature sensor
(only for weather -compensated
mode)
Installation
&
North or n orthwestern wall, 2
to2.5mabovegroundlevel.In
multi-storey buildings, in the
upper half of the second floor
&
Not above windows, d oors or
ventilation outlets
&
Not immediately below balcony
or gutter
&
Do not render over
&
Twocorecablewithamaxi-
mum length of 35 m and a
cross-section of 1.5 mm
2
? Flow temperatu re s ensor for low
loss header (accessories)
% Cylinder temperature sensor
(part of the DHW cyli nder con-
nection set)
aVG KM BUS user (accessory)
&
Vitotrol 200 or 300 rem ote c on-
trol
&
Vit oco m 1 00
&
Extension kit for one heating
circuit with mixer
&
Vitosolic
&
External extension H 1 or H2
Electrical connections (cont.)
12
5862 559 GB
Routing connecting cables
!
Important information
Connecting cables are damaged if they touch hot components.
When routi ng a nd securing co nnecting cable s on site, ensur e that the
maximum permissible cable temperatures are not exceeded.
A Low voltage connections
B 230 V connections
C Internal extension
D Main PCB
E Communication s modu le
Electrical connections (cont.)
13
5862 559 GB
Closing control unit housing and inserting user interface
14
5862 559 GB
Commissioning and adjustments
For commissioning and adjustment, see service instructions.
Front panel installation
15
5862 559 GB
16
Printed on environmentally-friendly,
chlorine-free bleached paper
5862 559 GB Subject to technical modifications
Viessmann Limited
Hortonwood 30, Tel ford, TF1 7Y P, GB
Telephone: +44 1952 675000
Fax: +44 195 2 6 75040
www.viessmann.co.uk
VIESMANN
Service instructions
for heating engineers
Vitodens 200
Type WB2A, 8.8 to 26.0 kW
Gas fired wa ll mounted con densing boi ler
natural gas and LPG version
See applicability on the last page
VITODENS 200
5692 573 GB 6/2004 Please k eep safe
Please follow these safety instructions closely to prevent accidents and
material losses.
Safety instructions explained
Danger
This symbol warns against the
risk of injury.
!
Important information
This symbol warns against the
risk of material losses and
environmental pollution.
Note
Details identified by the words "Note"
contain addit ional information .
Wa rranty
All warranty rights are void if these
service instructions are not observed.
Target group
These service instructions are exclu-
sively designed for qualified person-
nel.
Work on gas equ ipment must on ly b e
carried out by a registered gas fitter.
Only approved contractors may mod-
ify this equipment for countries other
than those designated o n the type
plate. That contractor will then
arrange for the relevant approval in
that country.
Electric al work must on ly be carrie d
out by a qualified electrician.
The system must be commissioned by
the system installer or a qualified per-
son authorised by the installer.
Regulations
Observe the following during service
work:
&
all legal instructions regarding the
prevention of accidents,
&
the TRGI, TRF and special regula-
tions, e.g. those of the BDH,
a ÖVGW-TR Gas, ÖVGW-TRF,
c SVGW,
&
all legal instructio ns re garding
environmental protection,
&
the Code of P ractice by rel evant
trade assoc iations and all local reg-
ulations.
If you notice a smell of gas
Danger
Escapin g ga s can cause exp lo-
sionswhichmayleadtoser-
ious injury.
&
Do not smoke. P revent
naked flames and sparks.
Never switch electrical lights
or equipm ent.
&
Open windows and doors.
&
Close the gas s hut-off valve.
&
Remove all per sonnel from
the danger zone.
&
Observe the safety regula-
tions of your local gas sup-
plier which can b e f ound on
the gas meter.
&
Notify your he ating contrac-
tor from outs ide th e bui lding.
Safety instructions
2
Safety instructions
5692 573 GB
If you smell flue gas
Danger
Flue gas may lead to life-threa-
tening po isoning.
&
Shut down the heating sys-
tem.
&
Ventilate the boiler room.
&
Close all doors leading to liv-
ing areas.
Repair work
It is not permitted to carry out repairs
on parts that fulfil a safety function.
Use only ori ginal Viessmann spare
parts, or equivalent parts that have
been appr oved by Viessman n.
Service work on the heating system
&
Isolate the sy stem from mains sup -
ply and check that it is no longer
"live", e.g . by re moving a separat e
fuse or by means of a mains electri-
cal isolator.
&
Safeguard the system against
unauthorised reconnection.
&
When usin g g as as fuel, also c lose
the main gas shut-off valve and
safeguard against unauthorised
reopening.
Ancillary components, spare and
wearing parts
!
Important information
Components which are not
tested with the heating system,
the installation of non-
approved spare parts and
unauthor ised conver sion may
lead to damage to the heating
system, which may affect their
function and limi t our wa rranty.
For conversions or replace-
ments, use onl y or iginal parts
from Viessmann or those spare
parts which are approved by
Viessmann.
Safety instructions (cont.)
3
Safety instructions
5692 573 GB
Initial s tart-up, inspection, maintenance
Steps - initial start -up, inspection and maintenance ..................................... 5
Further details regarding the individual steps . ............................................. 7
Coding
Code 1............................................................................... ......................... 39
Code 2............................................................................... ......................... 42
Resetting the coding to the as delivered condition .................................. ..... 62
Service scans
Service level summary........................................................................... ..... 63
Temperatures, boiler c oding card and brief scans........................................ 64
Checking outputs (relay test) ................................................................. ..... 68
Scanning operating condit ions and sensors ... ............................................. 69
Troubleshooting
Downloading fault codes history ......................................... ......................... 72
Call up current fault codes ............................. ............................................. 72
Checking and acknowledging faults ............................................................ 74
Repairs ......................................................... ............................................. 84
Function description
Constant temperature control unit ...................................... ......................... 96
Weather-compensated control unit ..................................... ......................... 98
Extensions for e xternal conne ctions (accessory)......................................... 100
Control functions ... ..................................................................................... 104
Designs
Connection and wiring diagrams internal connections...... ......................... 109
Connection and wiring diagrams external connections.............................. 111
Parts lists ......................................................................... ......................... 113
Commissioning/service reports............................................................... 120
Specification............................ ................................................................. 126