220Vac
Technician Settings:
IR (Option)
Date:
Title:
No. Revision Date File name: FMH-220-FC-SUPER3.VSD
Print name:
Checksum:
Software name:
Drawn: P.Rechtman
Checked: S.Lukin
Approved: E.Roy
FMH/220/FC/SUPER3
Apr 23, 2007
Ert300/IR
OUT-ERT300/TR5
1. Set temperature to 10oC.
2. Press and hold the MODE button (7 sec.) until the display flashes.
Using the (+) or (-) buttons adjust the High Temperature Limit (HEAT) (range 10...30oC).
3. Press the MODE button again.
Using the (+) or (-) buttons adjust the Low Temperature Limit (COOL) (range 10...30oC).
4. Press the MODE button again and choose the State of Security:
- OP = OPEN (enable all buttons).
- LO (aux) = Lock buttons except set buttons, aux will appear in display.
Remark: If no button is pressed for 20 seconds the thermostat will automatically return to normal
display.
5. Press the MODE button again - a digit between -6 and +6 will appear on display.
Using the (+) or (-) buttons adjust the OFFSET for Temperature Reading (range -6…+6oC).
6. Press the MODE button again and choose between activating the Input (T2-0)- (option for
Auto-Change Over Sensor or Contact Input), or not.
- bF = Input (T2-0) is not active- thermostat works normally.
- bO = Auto-Change Over sensor logic (available for 2-pipe system only) or Contact Input logic.
Follow steps below to configure the output application:
- Auto-Change Over Sensor (Cool/Heat Logic)
When Auto-Change Over sensor is selected, the system mode (Cool/Heat) is
automatically selected according to the temperature. The MODE button is not active.
- Move DIP switch S1.1 to "ON" position
- Press the MODE button and select the "EF" option.
- Contact input (remote switch)
The Contact Input can be set to work in three different modes:
- Move DIP switch S1.1 to "OFF" position
- Press the MODE button and select one of the following options:
- EF = Mode Selection (via the remote switch)
Change the system mode through one remote switch, attached to one or
more thermostats. It is suitable for hotel rooms and offices, when the system
mode cannot be defined differently for each thermostat.
- Remote switch close – HEAT
- Remote switch open – COOL
- E1 = Turn system On/Off (via the remote switch)
- Remote switch close - Thermostat work normally (ON)
- Remote switch open - Thermostat OFF and "EC" appears on the display.
- E2 = Activate Economy mode (via the remote switch)
- Remote switch close - Thermostat work normally (ON)
- Remote switch open - Thermostat works according to economy set-points).
- Thermostat in cool mode - economy set-point for cooling.
- Thermostat in heat mode - economy set-point for heating.
7. Press the MODE button again - "AUX" and "Cool" will appear on the display.
Using the (+) or (-) buttons adjust the Temperature Set-Point for Cooling in Economy Mode.
Press the MODE button again - "AUX" and "Heat" will appear on the display.
Using the (+) or (-) buttons adjust the Temperature Set-Point for Heating in Economy Mode.
8. Press the MODE button to return to normal display.
88
Cool
Heat
Fan
Hi
Med
Low
On
Off
Aux
oC
Set
On/Off
Mode
Fan
Rear side of thermostat
S1.1 ON – Auto-Change Over Sensor
OFF – Contact Input
S1.2 ON – External Sensor
OFF – Internal Sensor
S1.3 ON – Internal Sensor
OFF – External Sensor
S1.4 ON – With auto change over mode
OFF – Without auto change over mode
S1.5 ON – Display - user can switch
between Toamb and Toset using the mode button.
OFF – Display - Tset only
S1.6 ON – Auto fan all the time
OFF – Auto fan or Fan ON - selectable using the
FAN button
DIP Switch Configuration
2-Pipe Systems
System Configuration
HE
RE Cool
Heat
4-Pipe Systems
HE
RE
Cool valve
Heat valve
Cool
Heat
One valve
No Valve Systems – Only FAN
HE
RE Cool
Heat
Not connected
Not connected
In order to set the thermostat to work ONLY on the fan
(fan will work or not depending on demand for heating or cooling) -
move switch 6 to ON position.
For applications with 2 & 4 pipes move Switch 6 to OFF position -
Fan ON or AUTO FAN selected by button.
External Sensor
0T1 T2
2x0.5
Contact input (remote switch)
or Auto-change over sensor
2x0.5