FMH/220/HC11/3S/IR
HE
Date:
Title:
No.Revision Date File name: FMH-220-HC11-3S-IR-rev1.vsd
Print name:
Checksum: 446D
Software name: FMH1104
Drawn: P.Rechtman
Checked: S.Lukin
Approved: E.Roy
FMH/220/HC11/3S/IR
Feb 22, 2005
Ert300/IR
OUT-ERT300/TR5
meitav-tec
Tel: +972-3-9626462
Fax: +972-3-9626620
e-mail: support@meitavtec.com
RE
3
2
1
N
L
cool
heat
medium
low
high
230Vac
fan speeds
88
Cool
Heat
Fan
Hi
Med
Low
On
Off
Aux
oC
Set
On/Off
Mode
Fan
Enter technician Settings:
Use the "+"and "-" buttons to adjust set-point temperature to 10oC.
Press and hold the MODE button until "EO" appears on display.
Setting Heat Element type
When “EO” appears on display, use the "+" and "-" buttons to select between:
oElectric heat ("E" flashing)
oOil heat ("O" flashing)
Setting compressor delay
Press the MODE button again - "30" will appear on display.
Using the "+" and "-" buttons to select between:
oWith 3 minutes delay for compressor ("3" flashing)
oWithout delay ("0" flashing)
Setting Offset to calibrate room temperature readings (if needed)
Press the MODE button again - a number will appear on display.
Using the "+"and "-" buttons adjust the offset (Range -6°C...+6°C.).
Press the MODE button again to return to normal display.
Fan on/Auto fan setting:
Press and hold (3 sec.) the FAN button to switch between “fan on” and “auto fan”.
In “fan on” mode the word “FAN” will appear on display.
In “auto fan” mode the word “FAN” will not appear on display.
Timer indication:
If daily timer active – the word "Aux" will appear on display. .
After break of power, “AUX” will flash and the timer will not work.
Technician Settings:
IR (Option)