eGauge PEK-277V is an advanced metering device designed to monitor and measure 277/480VAC electrical systems. It provides real-time data on voltage, current, power consumption, and energy usage. With its built-in Ethernet connectivity, the eGauge PEK-277V can be easily integrated into existing networks for remote monitoring and data analysis. Additionally, it can generate detailed reports, helping users to identify areas for energy savings and improve overall efficiency.

eGauge PEK-277V is an advanced metering device designed to monitor and measure 277/480VAC electrical systems. It provides real-time data on voltage, current, power consumption, and energy usage. With its built-in Ethernet connectivity, the eGauge PEK-277V can be easily integrated into existing networks for remote monitoring and data analysis. Additionally, it can generate detailed reports, helping users to identify areas for energy savings and improve overall efficiency.

277V PEK Setup Guide
is guide describes one way to connect the components of the 277V PEK. e parts in this kit
can be used in many dierent ways to meet the requirements of an installation.
We recommend drilling holes for conduit, wires, and other external pieces prior to installing
components within the enclosure.
For an example line diagram, see last page.
1) Check that you have received all of the
correct parts:
2) e two 13” pieces of DIN rail should already
be mounted in the enclosure. With a Phillips
head screwdriver, check to make sure they are
tightly screwed in place.
1x Integra Enclosure
2x DIN Rails (pre-attached)
1x 120V DIN Rail Receptacle
5x Terminal Blocks
1x Cover Plate
2x Terminal End Stop
1x eGauge Mounting Kit (steel)
1x 15’ Yellow, Orange, White, Brown Wire
4x DIN Rail Mounting Screws and Washers
1x
Potential Transformer with DIN rail
mounting clip and Mounting plate for
transformer
eGauge.net
3) Take the 5 gray terminal block pieces and
connect them to the DIN rail. Use the gray
end plate to cover the exposed end. Connect
a terminal end stopper to each side of the
terminal block. Wait to use the screws to secure
the block as you may need to adjust it later.
4) Connect the 50VA Potential Transformer to
the same DIN rail as the terminal block. Orient
the primary side (colored wires) toward the
terminal block. e black wire on the primary
side of the transformer is the neutral line.
Important: Ensure that the neutral line of the
transformer connects to the same block as the
neutral line of the incoming distribution panel!
5) Insert the black and brown wires on the
primary side of the transformer into the
terminal block as shown in the photo. Use
wire nuts or electrical tape to cover all exposed
ends of unused wire on the primary side of the
transformer.
eGauge.net
6) Connect the 120VAC receptacle to the
opposing DIN Rail
7) Insert the white and white/black wires from
the secondary side of the potential transformer
into the 120VAC receptacle. e black and
white striped connects to the “+” or “HOT
position and the plain white connects to the “-”
or “NEU” (neutral) position.
8) Attach the cell router or other accessory. Cell
modems use a DIN clip to attach to the rail.
9) Attach the eGauge using the included DIN
mounting kit. e mounting kit can be used to
orient the eGauge in many ways. e image to
the le shows a “at” mount.
eGauge.net
10) Connect the power adapter for the cell
router or other accessory to the 120VAC
receptacle and the Ethernet cable to the eGauge
11) Cut lengths (about 7” long) from each of
the 15’ colored cable, strip about 1/4” from each
end, and use each to connect the eGauge voltage
block to the power distribution block.
Important: Ensure that the neutral line of the
eGauge connects to the same block as the
neutral line of the incoming distribution panel!
12) Wire the power distribution block to a
breaker or fuse block of the distribution panel
being measured.
eGauge.net
Gauge Systems
EG4xxx Meter, Data Logger, Server
L3
---
L2
N
L1
Ethernet
+
GND
x x x
NEU HOT
Cell Modem
12V DC
Ethernet
2x Antennas
White
Black/White
277/480VAC Distribution Panel
L3 L2 N L1
L3 L2 N L1
Example Line Diagram
eGauge.net
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6

eGauge PEK-277V User guide

Type
User guide

eGauge PEK-277V is an advanced metering device designed to monitor and measure 277/480VAC electrical systems. It provides real-time data on voltage, current, power consumption, and energy usage. With its built-in Ethernet connectivity, the eGauge PEK-277V can be easily integrated into existing networks for remote monitoring and data analysis. Additionally, it can generate detailed reports, helping users to identify areas for energy savings and improve overall efficiency.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI