9
CONTROL FUNCTION
(SINGLE OUTPUT)
_________________________________________________________
Control action PID control with auto-tuning
Fuzzy control with auto-tuning
_________________________________________________________
Proportional band (P) 0-999.9% of full scale (FS), setting in 0.1% steps
_________________________________________________________
Integral time (I) 0-3200 sec, setting in 1 sec steps
_________________________________________________________
Differential time (D) 0-999.9 sec, setting in 0.1 sec steps
_________________________________________________________
P,I,D = 0: On/off action
I,D = 0: Proportional action
_________________________________________________________
Proportional cycle 1-150 sec, setting in 1 sec steps, for relay contact
output and DC SSR driver output only
_________________________________________________________
Hysteresis width 0-50% FS, setting in 1 E.U.(Engineering Units) steps
On/Off action only
_________________________________________________________
Anti-reset wind up 0-100% FS, setting in 1 E.U. steps, auto-setting
with auto-tuning
_________________________________________________________
Input sampling cycle 0.5 sec
_________________________________________________________
CONTROL FUNCTION
(DUAL OUTPUT) (Heat/Cool Type) CN4522, CN4622, CN4722 only
_________________________________________________________
Heating Proportional band P x 1/2 (P= 0-999.9%)
_________________________________________________________
Cooling Proportional band Heating proportional band x Cooling proportional
band coefficient
Cooling proportional band coefficient= 0-100
0: On/Off action
_________________________________________________________
Integral time 0-3200 sec for heating and cooling
_________________________________________________________
Differential time 0-999.9 sec for heating and cooling
_________________________________________________________