Carrier 48SX024-060 User manual

Category
Split-system air conditioners
Type
User manual
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS .................1-9
General ......................................1
RECEIVING AND INSTALLATION ...........10-22
Step 1 Check Equipment ..................10
IDENTIFY UNIT
INSPECT SHIPMENT
Step 2 Provide Unit Support ..............10
ROOF CURB
SLAB MOUNT
FLUSH MOUNT
Step 3 Field Fabricate Ductwork ...........10
Step 4 Provide Clearances ................10
Step 5 Rig and Place Unit .................10
UNITS WITHOUT BASE RAIL
UNITS WITH OPTIONAL BASE RAIL
Step 6 Connect Condensate Drain .........13
Step 7 Install Flue Hood ..................13
Step 8 Install Gas Piping ..................13
Step 9 Install Duct Connections ...........16
CONFIGURING UNITS FOR DOWNFLOW
(VERTICAL) DISCHARGE
Step 10 Install Electrical Connections .....18
HIGH-VOLTAGE CONNECTIONS
SPECIAL PROCEDURES FOR 208-V
OPERATION
CONTROL VOLTAGE CONNECTIONS;
NON-INTEGRATED CONTROL MOTOR
(NON-ICM) UNITS
CONTROL VOLTAGE CONNECTIONS;
INTEGRATED CONTROL MOTOR (ICM)
UNITS
HEAT ANTICIPATOR SETTING
TRANSFORMER PROTECTION
PRE-START-UP ............................22,23
START-UP ................................23-44
MAINTENANCE ............................44-47
TROUBLESHOOTING ......................48-50
START-UP CHECKLIST .....................CL-1
NOTE TO INSTALLER Before the installation, READ
THESE INSTRUCTIONS CAREFULLY AND COM-
PLETELY.Also, make sure the Users Manual and Replace-
ment Guide are left with the unit after installation. The fur-
nace is NOT to be used for temporary heating of buildings
or structures under construction.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical com-
ponents. Only trained and qualified personnel should install,
repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters.All other operations should
be performed by trained service personnel. When working
on air-conditioning equipment, observe precautions in the
literature, tags and labels attached to the unit, and other safety
precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire ex-
tinguisher available for all brazing operations.
Improper installation, adjustment, alteration, service, main-
tenance, or use can cause carbon monoxide poisoning,
fire, or an explosion which can result in personal injury
or unit damage. Consult a qualified installer, service agency,
or gas supplier for information or assistance. The quali-
fied installer or agency must use only factory-authorized
kits or accessories when modifying this product.
Before performing service or maintenance operations on
unit, turn off gas supply then unit main power switch.
Electrical shock could cause personal injury.
General The 48SS,SX units (see Fig. 1) are fully self-
contained, combination Category I gas heating/electric cool-
ing units designed for outdoor installation. See Fig. 2-9
(pages 2-9) for unit dimensions. All unit sizes have dis-
charge openings for both horizontal and downflow configu-
rations, and are factory shipped with all 4 duct openings covered.
Units may be installed either on a rooftop or a ground-level
cement slab. See Fig. 10 for roof curb dimensions.
Fig. 1 Unit 48SX Shown With Optional Base Rail
48SS018-060
48SX024-060
Single Package Gas Heating/
Electric Cooling Units
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 1a 6a
PC 111 Catalog No. 534-721 Printed in U.S.A. Form 48SS,SX-12SI Pg 1 9-98 Replaces: 48SS,SX-11SI
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel .............................0
Unit top ...........................36(914)
Side opposite ducts .....................36(914)
Compressor access .....................36(914)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum extension of overhangs ...............48(1219)
Unit top ...........................14(356)
Duct side of unit ........................2(51)
Side opposite ducts .....................14(356)
Bottom of unit ...........................0
Flue panel .........................36(914)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side ................42(1067)
Unit and ungrounded surfaces, control box side .........36(914)
Unit and block or concrete walls and other grounded
surfaces, control box side ..................42(1067)
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
UNIT HEIGHT
(in./mm)
lbkgABCD E
48SS180040 208/230-1-60 272 123 81/37 62/28 76/35 53/24 24.1/613
48SS024040 208/230-1-60 303 138 97/44 43/20 123/56 40/18 24.1/613
48SS024060 208/230-1-60 315 143 100/45 46/21 126/57 43/20 24.1/613
48SS030040 208/230-1-60, 208/230-3-60 320 145 100/45 47/21 126/57 47/21 24.1/613
48SS030060/080 208/230-1-60, 208/230-3-60 332 149 103/46 50/22 129/58 50/23 24.1/613
48SS036060/080 208/230-1-60, 208/230-3-60, 460-3-60 336 153 86/39 76/35 111/50 63/29 24.1/613
48SS036100/120 208/230-1-60, 208/230-3-60, 460-3-60 348 158 89/40 79/36 114/52 66/30 24.1/613
48SS042060/080 208/230-1-60, 208/230-3-60, 460-3-60 375 170 95/43 86/39 119/54 75/34 28.1/714
48SS042100/120 208/230-1-60, 208/230-3-60, 460-3-60 387 176 98/45 89/40 122/55 78/35 28.1/714
UNIT
F
in./mm
G
in./mm
CENTER OF GRAVITY in./mm
XYZ
48SS018040
16
9
16
/420.7 18
15
16
/481.0
25.07/637 20.59/523
10.85/276
48SS024040 27.07/688 23.35/593
48SS024060 26.98/685 23.27/591
48SS030040 26.71/678 23.46/596
48SS030060/080 27.15/689 22.36/568
48SS036060/080 27.50/698 22.48/571
48SS036100/120 27.40/696 22.44/570
48SS042060/080
20
9
16
/522.3 22
15
16
/582.6
27.01/686 22.44/570
12.7/321
48SS042100/120 26.94/684 22.44/570
LEGEND
CG Center of Gravity
COND Condenser
LV Low Voltage
MAT’L Material
NEC National Electrical Code
REQ’D Required
NOTES:
1. Clearances mustbemaintained topreventrecirculation ofairfrom outdoor-
fan discharge.
2. Adequate clearance around airopenings into combustionchamber must
be provided.
Fig. 2 48SS018-042 Without Base Rail, Unit Dimensions
2
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel .............................0
Unit top ...........................36(914)
Side opposite ducts .....................36(914)
Compressor access .....................36(914)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum extension of overhangs ...............48(1219)
Unit top ...........................14(356)
Duct side of unit ........................2(51)
Side opposite ducts .....................14(356)
Bottom of unit ...........................0
Flue panel .........................36(914)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side ................42(1067)
Unit and ungrounded surfaces, control box side .........36(914)
Unit and block or concrete walls and other grounded
surfaces, control box side ..................42(1067)
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
UNIT HEIGHT
(in./mm)
lbkgABCD E
48SS018040 208/230-1-60 296 135 87/40 68/31 82/37 59/27 27.4/697
48SS024040 208/230-1-60 327 149 103/47 49/22 129/59 46/21 27.4/697
48SS024060 208/230-1-60 339 155 106/48 52/24 132/60 49/22 27.4/697
48SS030040 208/230-1-60, 208/230-3-60 344 157 106/48 53/24 132/60 53/24 27.4/697
48SS030060/080 208/230-1-60, 208/230-3-60 356 162 102/46 71/32 123/56 60/27 27.4/697
48SS036060/080 208/230-1-60, 208/230-3-60, 460-3-60 360 164 92/42 82/37 117/53 69/31 27.4/697
48SS036100/120 208/230-1-60, 208/230-3-60, 460-3-60 372 169 95/43 85/39 120/55 72/33 27.4/697
48SS042060/080 208/230-1-60, 208/230-3-60, 460-3-60 399 181 101/46 92/42 125/57 81/37 31.4/798
48SS042100/120 208/230-1-60, 208/230-3-60, 460-3-60 411 187 104/47 95/43 128/58 84/38 31.4/798
UNIT
F
in./mm
G
in./mm
CENTER OF GRAVITY in./mm
XYZ
48SS018040
19
7
8
/504.8 22
1
4
/565.4
25.04/636 22.72/577
13.16/334.3
48SS024040 26.90/683.3 20.17/512.3
48SS024060 26.82/681.2 20.22/513.6
48SS030040 26.57/674.9 20.1 /509.3
48SS030060/080 26.93/684 21.1 /535.4
48SS036060/080 27.31/693.7 21.0 /532.6
48SS036100/120 27.23/691.6 21.0 /533.1
48SS042060/080
23
7
8
/606.4 26
1
4
/666.8
26.87/682.5 21.0 /533.1
14.96/380
48SS042100/120 26.81/681 21.0 /533.7
LEGEND
CG Center of Gravity
COND Condenser
LV Low Voltage
MAT’L Material
NEC National Electrical Code
REQ’D Required
NOTES:
1. Clearances mustbemaintained topreventrecirculation ofairfrom outdoor-
fan discharge.
2. Adequate clearance around airopenings into combustionchamber must
be provided.
Fig. 3 48SS018-042 With Optional Base Rail, Unit Dimensions
3
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel .............................0
Unit top ...........................36(914)
Side opposite ducts .....................36(914)
Compressor access .....................36(914)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum extension of overhangs ...............48(1219)
Unit top ...........................14(356)
Duct side of unit ........................2(51)
Side opposite ducts .....................14(356)
Bottom of unit ...........................0
Flue panel .........................36(914)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side ................42(1067)
Unit and ungrounded surfaces, control box side .........36(914)
Unit and block or concrete walls and other grounded
surfaces, control box side ..................42(1067)
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
lb kg A B C D
48SS048080 208/230-1-60, 208/230-3-60, 460-3-60 414 188 107/49 83/38 158/72 66/30
48SS048100/120/140 208/230-1-60, 208/230-3-60, 460-3-60 426 193 110/50 86/39 159/72 71/32
48SS060080 208/230-1-60, 208/230-3-60, 460-3-60 453 206 117/53 93/42 167/76 76/35
48SS060100/120/140 208/230-1-60, 208/230-3-60, 460-3-60 465 211 120/55 96/44 167/76 82/37
UNIT
CENTER OF GRAVITY (in./mm)
XYZ
48SS048080 28.76/731 23.46/596 15.35/390
48SS048100/120/140 28.42/722 23.42/595 15.35/390
48SS060080 28.36/720 23.27/591 15.35/390
48SS060100/120/140 27.95/710 23.23/590 15.35/390
LEGEND
CG Center of Gravity
COND Condenser
LV Low Voltage
MAT’L Material
NEC National Electrical Code
REQ’D Required
NOTES:
1. Clearances mustbemaintained topreventrecirculation ofairfrom outdoor-
fan discharge.
2. Adequate clearance around airopenings into combustionchamber must
be provided.
Fig. 4 48SS048,060 Without Base Rail, Unit Dimensions
4
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel .............................0
Unit top ...........................36(914)
Side opposite ducts .....................36(914)
Compressor access .....................36(914)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum extension of overhangs ...............48(1219)
Unit top ...........................14(356)
Duct side of unit ........................2(51)
Side opposite ducts .....................14(356)
Bottom of unit ...........................0
Flue panel .........................36(914)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side ................42(1067)
Unit and ungrounded surfaces, control box side .........36(914)
Unit and block or concrete walls and other grounded
surfaces, control box side ..................42(1067)
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
lb kg A B C D
48SS048080 208/230-1-60, 208/230-3-60, 460-3-60 438 199 113/51 89/40 164/75 72/33
48SS048100/120/140 208/230-1-60, 208/230-3-60, 460-3-60 450 205 116/53 92/42 165/75 77/35
48SS060080 208/230-1-60, 208/230-3-60, 460-3-60 477 217 123/56 99/45 173/79 82/37
48SS060100/120/140 208/230-1-60, 208/230-3-60, 460-3-60 489 222 126/57 102/46 173/79 88/40
UNIT
CENTER OF GRAVITY (in./mm)
XYZ
48SS048080 28.54/724.9 20.00/508 17.66/448.6
48SS048100/120/140 28.22/716.8 20.05/509.3 17.66/448.6
48SS060080 28.18/715.6 20.19/512.8 17.66/448.6
48SS060100/120/140 27.79/705.9 20.23/513.8 17.66/448.6
LEGEND
CG Center of Gravity
COND Condenser
LV Low Voltage
MAT’L Material
NEC National Electrical Code
REQ’D Required
NOTES:
1. Clearances mustbemaintained topreventrecirculation ofairfrom outdoor-
fan discharge.
2. Adequate clearance around airopenings into combustionchamber must
be provided.
Fig. 5 48SS048,060 With Optional Base Rail, Unit Dimensions
5
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel .............................0
Unit top ...........................36(914)
Side opposite ducts .....................36(914)
Compressor access .....................36(914)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum extension of overhangs ...............48(1219)
Unit top ...........................14(356)
Duct side of unit ........................2(51)
Side opposite ducts .....................14(356)
Bottom of unit ...........................0
Flue panel .........................36(914)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side ................42(1067)
Unit and ungrounded surfaces, control box side .........36(914)
Unit and block or concrete walls and other grounded
surfaces, control box side ..................42(1067)
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
lbkgABCD
48SX024040 208/230-1-60 333 151 104/47 50/23 130/59 49/22
48SX024060 208/230-1-60 345 157 107/49 53/24 133/60 52/24
48SX030040 208/230-1-60 336 153 97/44 66/30 118/54 55/25
48SX030060/080 208/230-1-60 348 158 100/45 69/31 121/55 58/26
48SX036060/080 208/230-1-60, 208/230-3-60, 460-3-60 366 166 94/43 84/38 117/53 71/32
48SX036100/120 208/230-1-60, 208/230-3-60, 460-3-60 378 172 97/44 87/40 120/55 74/34
UNIT
CENTER OF GRAVITY (in./mm)
XYZ
48SX024040 26.71/678 20.06/510 12.65/321
48SX024060 26.64/677 20.12/511 12.65/321
48SX030040 27.06/687 21.05/535 12.65/321
48SX030060/080 26.98/685 21.07/535 12.65/321
48SX036060/080 27.14/689 21.10/536 12.65/321
48SX036100/120 27.06/687 21.12/536 12.65/321
LEGEND
CG Center of Gravity
COND Condenser
LV Low Voltage
MAT’L Material
NEC National Electrical Code
REQ’D Required
NOTES:
1. Clearances mustbemaintained topreventrecirculation ofairfrom outdoor-
fan discharge.
2. Adequate clearance around airopenings into combustionchamber must
be provided.
Fig. 6 48SX024-036 Without Base Rail, Unit Dimensions
6
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel ...........................0
Unit top .........................36(914)
Side opposite ducts ....................36(914)
Compressor access ....................36(914)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum extension of overhangs .............48(1219)
Unit top .........................14(356)
Duct side of unit ......................2(51)
Side opposite ducts ....................14(356)
Bottom of unit .........................0
Flue panel ........................36(914)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side ..............42(1067)
Unit and ungrounded surfaces, control box side .......36(914)
Unit and block or concrete walls and other grounded
surfaces, control box side ................42(1067)
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
lb kg A B C D
48SX024040 208/230-1-60 357 163 110/50 56/25 136/62 55/25
48SX024060 208/230-1-60 369 168 113/51 59/27 139/63 58/26
48SX030040 208/230-1-60 360 164 103/47 72/33 124/56 61/28
48SX030060/080 208/230-1-60 372 169 106/48 75/34 127/58 64/29
48SX036060/080 208/230-1-60, 208/230-3-60, 460-3-60 390 177 100/45 90/41 123/56 77/35
48SX036100/120 208/230-1-60, 208/230-3-60, 460-3-60 402 183 103/47 93/42 127/57 80/36
UNIT
CENTER OF GRAVITY (in./mm)
XYZ
48SX024040 26.57/674.9 20.17/512.3 14.96/380.0
48SX024060 26.51/673.3 20.22/513.6 14.96/380.0
48SX030040 26.90/683.3 21.09/535.7 14.96/380.0
48SX030060/080 26.83/681.5 21.11/536.2 14.96/380.0
48SX036060/080 26.99/685.5 21.14/537.0 14.96/380.0
48SX036100/120 26.92/683.8 21.14/537.0 14.96/380.0
LEGEND
CG Center of Gravity
COND Condenser
LV Low Voltage
MAT’L Material
NEC National Electrical Code
REQ’D Required
NOTES:
1. Clearances mustbemaintained topreventrecirculation ofairfrom outdoor-
fan discharge.
2. Adequate clearance around airopenings into combustionchamber must
be provided.
Fig. 7 48SX024-036 With Optional Base Rail, Unit Dimensions
7
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel .............................0
Unit top ...........................36(914)
Side opposite ducts .....................36(914)
Compressor access .....................36(914)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum extension of overhangs ...............48(1219)
Unit top ...........................14(356)
Duct side of unit ........................2(51)
Side opposite ducts .....................14(356)
Bottom of unit ...........................0
Flue panel .........................36(914)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side ................42(1067)
Unit and ungrounded surfaces, control box side .........36(914)
Unit and block or concrete walls and other grounded
surfaces, control box side ..................42(1067)
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
lbkgABCD
48SX042060/080 208/230-1-60, 208/230-3-60, 460-3-60 391 178 100/45 91/41 120/55 80/36
48SX042100/120 208/230-1-60, 208/230-3-60, 460-3-60 403 183 103/47 94/43 123/56 83/38
48SX048080 208/230-1-60, 208/230-3-60, 460-3-60 422 192 109/50 85/39 158/72 70/32
48SX048100/120/140 208/230-1-60, 208/230-3-60, 460-3-60 434 197 112/51 88/40 161/73 73/33
48SX060080 208/230-1-60, 208/230-3-60 453 206 117/53 93/42 167/76 76/35
48SX060100/120/140 208/230-1-60, 208/230-3-60 465 211 120/55 96/44 167/76 82/37
UNIT
CENTER OF GRAVITY (in./mm)
XYZ
48SX042060/080 26.66/677 21.19/538 15.35/390
48SX042100/120 26.61/676 21.21/539 15.35/390
48SX048080 28.45/723 19.95/507 15.35/390
48SX048100/120/140 28.35/720 19.99/508 15.35/390
48SX060080 28.36/720 23.27/591 15.35/390
48SX060100/120/140 27.95/710 23.23/590 15.35/390
LEGEND
CG Center of Gravity
COND Condenser
LV Low Voltage
MAT’L Material
NEC National Electrical Code
REQ’D Required
NOTES:
1. Clearances mustbemaintained topreventrecirculation ofairfrom outdoor-
fan discharge.
2. Adequate clearance around airopenings into combustionchamber must
be provided.
Fig. 8 48SX042-060 Without Base Rail, Unit Dimensions
8
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel .............................0
Unit top ...........................36(914)
Side opposite ducts .....................36(914)
Compressor access .....................36(914)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum extension of overhangs ...............48(1219)
Unit top ...........................14(356)
Duct side of unit ........................2(51)
Side opposite ducts .....................14(356)
Bottom of unit ...........................0
Flue panel .........................36(914)
LEGEND
CG Center of Gravity
COND Condenser
LV Low Voltage
MAT’L Material
NEC National Electrical Code
REQ’D Required
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
lb kg A B C D
48SX042060,080 208/230-1-60, 208/230-3-60, 460-3-60 415 189 106/48 97/44 126/57 86/39
48SX042100,120 208/230-1-60, 208/230-3-60, 460-3-60 427 194 109/50 100/45 129/59 89/40
48SX048080 208/230-1-60, 208/230-3-60, 460-3-60 446 293 115/52 91/41 164/75 76/35
48SX048100/120/140 208/230-1-60, 208/230-3-60, 460-3-60 458 208 118/54 94/43 167/76 79/36
48SX060080 208/230-1-60, 208/230-3-60 477 217 123/56 99/45 173/79 82/37
48SX060100/120/140 208/230-1-60, 208/230-3-60 489 222 126/57 102/46 173/79 88/40
UNIT
CENTER OF GRAVITY (in./mm)
XYZ
48SX042060,080 26.55/674.4 21.22/539.0 17.66/448.6
48SX042100,120 26.50/673.0 21.24/539.6 17.66/448.6
48SX048080 28.25/717.6 20.04/509.0 17.66/448.6
48SX048100/120/140 28.16/715.3 20.08/510.0 17.66/448.6
48SX060080 28.18/715.6 20.19/512.8 17.66/448.6
48SX060100/120/140 27.79/705.9 20.23/513.8 17.66/448.6
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge.
2. Adequate clearance around air openings into combustion chamber must be
provided.
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side ................42(1067)
Unit and ungrounded surfaces, control box side .........36(914)
Unit and block or concrete walls and other grounded
surfaces, control box side ..................42(1067)
Fig. 9 48SX042-060 With Optional Base Rail, Unit Dimensions
9
RECEIVING AND INSTALLATION
Step 1 Check Equipment
IDENTIFYUNIT The unit model number and serial num-
ber are stamped on unit identification plate. Check this
information against shipping papers and job data.
INSPECT SHIPMENT Inspect for shipping damage while
unit is still on shipping pallet. If unit appears to be damaged
or is torn loose from its anchorage, have it examined by trans-
portation inspectors before removal. Forward claim papers
directly to transportation company. Manufacturer is not re-
sponsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify
the nearest Carrier Air Conditioning office if any item is
missing.
To prevent loss or damage, leave all parts in original pack-
ages until installation.
Step 2 Provide Unit Support
ROOF CURB Install accessory roof curb in accordance
with instructions shipped with curb. See Fig. 10 for roof curb
dimensions. Install insulation, cant strips, roofing, and flash-
ing. Ductwork must be attached to curb.
IMPORTANT: The gasketing of the unit to the roof
curb is critical for a watertight seal. Install gasketing
material supplied with the roof curb. Improperly ap-
plied gasketing can also result in air leaks and poor
unit performance.
Curb should be level to within
1
4
inch. This is necessary
for unit drain to function properly. Refer to accessory roof
curb installation instructions for additional information as
required.
SLAB MOUNT Place the unit on a solid, level concrete
pad that is a minimum of 4 in. thick with 2 in. above grade.
The slab should be flush on the front of the unit (to allow
condensate drain installation) and should extend 2 in. on the
three remaining sides of the unit. See Fig. 11. Install a 6-in.
gravel apron in front of condenser-air inlets to prevent ob-
struction of airflow by grass or shrubs. Do not secure the
unit to the slab except when required by local codes.
FLUSH MOUNT Place side of unit with duct panel flush
against transition. On units with optional base rails, the skirt
on duct-panel side of unit can be removed to allow unit to
be mounted flush against transitions that extend below base-
pan of unit. To remove skirt, remove 4 screws holding skirt
to base rail. Then, remove skirt.
To remove wood support under unit (with base rail only),
loosen 4 screws above rigging holes and slide assembly out
through rectangular hole.
Step 3 Field Fabricate Ductwork Secure all
ducts to roof curb and building structure on vertical dis-
charge units. Do not connect ductwork to unit. For horizon-
tal applications, unit is provided with flanges on the horizontal
openings. All ductwork should be secured to the flanges. In-
sulate and weatherproof all external ductwork, joints, and
roof openings with counter flashing and mastic in accor-
dance with applicable codes.
Ducts passing through an unconditioned space must be
insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with ap-
plicable fire codes.
A minimum clearance is not required around ductwork.
Cabinet return-air static shall not exceed −.25 in. wg.
Step 4 Provide Clearances The required mini-
mum operating and service clearances are shown in
Fig. 2-9. Adequate combustion, ventilation, and condenser
air must be provided, in accordance with section 5.3,Air for
Combustion and Ventilation, of the National Fuel Gas Code
ANSI (American National Standards Institute) Z223.1 (in
Canada, sections 7.2, 7.3 or 7.4 or Can/CGA [Canadian Gas
Association] B149 Installation Codes), or applicable provi-
sions of local building code.
Do not restrict condenser airflow. An air restriction at
either the outdoor-air inlet or the fan discharge can be
detrimental to compressor life.
The condenser fan pushes air through the condenser coil
and discharges it through the bank of louvers in the top cover,
the decorative grille on the right side of the unit, and the
compressor access panel. Be sure that the fan discharge does
not recirculate to the condenser coil. Do not locate the unit
in either a corner or under an overhead obstruction. The mini-
mum clearance under a partial overhang (such as a normal
house overhang) is 48-in. above the unit top. The maximum
horizontal extension of a partial overhang must not exceed
48 inches.
Do not place the unit where water, ice, or snow from an
overhang or roof will damage or flood the unit. Do not in-
stall the unit on carpeting, tile, or other combustible mate-
rials. The unit may be installed on wood flooring or on
Class A, B, or C roof covering materials.
Step 5 Rig and Place Unit
When installing the unit on a rooftop, be sure the roof
will support the additional weight. Refer to Fig. 2-9 for
corner weight information.
Use spreader bars or crate top when rigging the unit. The
units must be rigged for lifting as shown in Fig. 12 and 13.
Refer to Tables 1 and 2 for operating weight and to Fig. 2-9
for corner weights. Use extreme caution to prevent damage
when moving the unit. Unit must remain in an upright po-
sition during all rigging and moving operations. The unit
must be level for proper condensate drainage; therefore, the
ground-level pad or accessory roof curb must be level be-
fore setting the unit in place. When a field-fabricated sup-
port is used, be sure that the support is level and properly
supports the unit.
10
PART NUMBER ‘A’’
FLAT
CURB
CPRFCURB001A00 89 [203]
CPRFCURB002A00 119 [279]
CPRFCURB003A00 149 [356]
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied as required for unit being installed.
3. Dimensions in [ ] are in millimeters.
4. Roof curb is made of 16 gage steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance 4 ft on each side.
7. Direction of airflow.
8. Insulated panels: 1-in. thick fiberglass 1 lb density.
Fig. 10 Roof Curb Dimensions
11
UNITS WITHOUT BASE RAIL If accessory rigging
brackets are to be used for rigging, install them as follows:
Secure screws and paint protectors solidly against unit
basepan to hold lifting brackets in position.
Never use lifting brackets when the temperature is be-
low −10 F.
Never exceed 200 lbs per bracket of lifting force.
Never use lifting brackets for lifting other models of air-
conditioning units.
Lifting point should be directly over the unit center of
gravity.
1. Position brackets as close to the corners of unit as pos-
sible. Be sure brackets are well outside of center of grav-
ity. (See Fig. 2, 4, 6, 8, and 12.).
2. Position paint protectors and foam strips between screws
and painted surface of unit.Tightenscrews until they make
contact with the paint protectors.
3. Secure device or hook of sufficient strength to hole in bracket
as shown in detail ‘A of Fig. 12.
4. If wood top is available, use it for a spreader bar to pre-
vent straps from damaging unit. If wood top is not avail-
able, use spreader bars of sufficient length.
Fig. 11 Slab Mounting Details
NOTICE TO RIGGERS
Hook rigging shackles through holes in lifting brackets, as shown in
Detail ‘‘A.’ Lifting brackets to be centered around the unit center of
gravity. Use wooden top skid when rigging, to prevent rigging straps
from damaging unit.
All panels must be in place when rigging.
UNIT
48SS
MAX
WEIGHT
ABC
Size lb kg in. mm in. mm in. mm
018 332 150
49.4 1255
24.3 618 24.85 631
024 375 170 22.4 570 24.85 631
030 384 174 22.3 565 24.85 631
036 408 185 22.0 559 24.85 631
042 447 203 22.5 571 28.85 733
048 486 220 21.0 533 34.85 885
060 525 238 21.5 545 34.85 885
UNIT
48SX
024 405 184
49.4 1255
22.8 579 28.9 733
030 408 185 22.4 569 28.9 733
036 438 199 22.4 569 28.9 733
042 463 210 22.8 579 34.9 885
048 494 224 21.1 536 34.9 885
060 525 238 21.5 545 34.9 885
Fig. 12 Suggested Rigging for Units Without
Base Rail
NOTICE TO RIGGERS
Hook rigging shackles through holes in lifting brackets, as shown in
Detail ‘‘A.’ Lifting brackets to be centered around the unit center of
gravity. Use wood top skid when rigging, to prevent rigging straps
from damaging unit. Remove 4 screws to slide wood support through
rectangular hole in rail.
All panels must be in place when rigging.
UNIT
48SS
MAX
WEIGHT
ABC
Size lb kg in. mm in. mm in. mm
018 320 145
49.4 1255
24.4 619 28.2 715
024 363 165 22.6 574 28.2 715
030 380 172 22.5 571 28.2 715
036 396 180 22.2 563 28.2 715
042 435 197 22.6 574 32.2 816
048 474 215 21.2 538 38.2 969
060 513 233 21.6 549 38.2 969
UNIT
48SX
024 393 178
49.4 1255
22.9 582 32.2 816
030 396 180 22.6 574 32.2 816
036 426 193 22.5 571 32.2 816
042 451 205 22.9 582 38.2 969
048 482 219 21.3 540 38.2 969
060 513 233 21.6 549 38.2 969
Fig. 13 Suggested Rigging for Units With
Optional Base Rail
12
UNITS WITH OPTIONAL BASE RAIL Lifting holes
are provided in optional base rail as shown in Fig. 13. Op-
erating weights are shown in Tables 1 and 2. Refer to rig-
ging instructions on unit.
Protective wood support must be removed from unit be-
fore unit is mounted to curb. Remove 4 screws that secure
support above rigging holes in rails. Slide support out through
rectangular hole in rail. See Fig. 13.
Step 6 Connect Condensate Drain
NOTE: When installing condensate drain connection be sure
to comply with local codes and restrictions.
Model 48SS,SX disposes of condensate water through a
3
4
in. NPT fitting which exits through the compressor access
panel. See Fig. 2-9 for location.
Condensate water can be drained directly onto the roof in
rooftop installations (where permitted) or onto a gravel apron
in ground-level installations. Install a field-supplied conden-
sate trap at end of condensate connection to ensure proper
drainage. Make sure that the outlet of the trap is at least
1 in. lower than the drain-pan condensate connection to pre-
vent the pan from overflowing. See Fig. 14. Prime the trap
with water. When using a gravel apron, make sure it slopes
away from the unit.
If the installation requires draining the condensate water
away from the unit, install a 2-in. trap at the condensate con-
nection to ensure proper drainage. See Fig. 14. Make sure
that the outlet of the trap is at least 1 in. lower than the drain-
pan condensate connection to prevent the pan from over-
flowing. Prime the trap with water. Connect a drain tube us-
ing a minimum of
3
4
-in. PVC or
3
4
-in. copper pipe (all field-
supplied) at the outlet end of the 2-in. trap. Do not undersize
the tube. Pitch the drain tube downward at a slope of at least
one in. for every 10 ft of horizontal run. Be sure to check the
drain tube for leaks.
Step 7 Install Flue Hood The flue hood as-
sembly is shipped screwed to the control box in the burner
compartment. Remove the burner access panel to locate the
assembly.
For units being installed in California Air Quality Man-
agement Districts which require NO
x
emissions of
40 nanograms/joule or less, kit CRLOWNOX001A00 must
be installed.
The venting system is designed to ensure proper vent-
ing. The flue hood assembly must be installed as indi-
cated in this section of the unit installation instructions.
Install the flue hood as follows:
1. This installation must conform with local building codes
and with the National Fuel Gas Code (NFGC),ANSIZ223.1
(in Canada, CAN/CGAB149.1, and B149.2) or NFPA(Na-
tional Fire Protection Association) latest revision. Refer
to Provincial and local plumbing or wastewater codes and
other applicable local codes.
2. Remove from shipping location. Place vent cap assembly
over flue panel. Orient screw holes in vent cap with holes
in the flue panel.
3. Secure flue hood to flue panel by inserting a single screw
on the right side, the left side, and the top of the hood.
Step 8 Install Gas Piping The gas supply pipe
enters the unit through the access hole provided. The gas
connection to the unit is made to the
1
2
-in. FPT gas inlet on
the manual shutoff or gas valve.
Install a gas supply line that runs to the heating section.
Refer to Table 3 and the NFGC for gas pipe sizing. Do not
use cast-iron pipe. It is recommended that a black iron pipe
is used. Check the local utility for recommendations con-
cerning existing lines. Size gas supply piping for 0.5 in. wg
maximum pressure drop. Never use pipe smaller than the
1
2
-in. FPT gas inlet on the unit gas valve.
For natural gas applications, the gas pressure at unit gas
connection must not be less than 4.0 in. wg or greater than
13 in. wg while the unit is operating. For propane applica-
tions, the gas pressure must not be less than 4.0 in. wg or
greater than 13 in. wg at the unit connection.
An
1
8
-in. NPT plugged tapping accessible for test gage
connection must be installed immediately upstream of the
gas supply connection to the furnace.
When installing the gas supply line, observe local codes
pertaining to gas pipe installations. Refer to the NFGC ANSI
Z223.1-1988 NFPA latest edition (in Canada, CAN/CGA
B149.1, (2)-M86). In the absence of local building codes,
adhere to the following pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe
1
4
inch in every 15 ft to prevent traps. Grade all hori-
zontal runs downward to risers. Use risers to connect to
heating section and to meter.
2. Protect all segments of piping system against physical and
thermal damage. Support all piping with appropriate straps,
hangers, etc. Use a minimum of one hanger every 6 ft.
For pipe sizes larger than
1
2
in., follow recommendations
of national codes.
3. Apply joint compound (pipe dope) sparingly and only to
male threads of joint when making pipe connections. Use
only pipe dope that is resistant to action of liquefied
petroleum gases as specified by local and/or national codes.
Never use Teflon tape.
4. Install sediment trap in riser leading to heating section
per Fig. 15. This drip leg functions as a trap for dirt and
condensate.
5. Install an accessible, external, manual main shutoff valve
in gas supply pipe within 6 ft of heating section.
6. Install ground-joint union close to heating section be-
tween unit manual shutoff and external manual main shut-
off valve.
7. Pressure-test all gas piping in accordance with local and
national plumbing and gas codes before connecting pip-
ing to unit.
NOTE: Pressure test the gas supply system after the gas
supply piping is connected to the gas valve. The supply
piping must be disconnected from the gas valve during
the testing of the piping systems when test pressure is in
excess of 0.5 psig. Pressure test the gas supply piping
system at pressures equal to or less than 0.5 psig. The
unit heating section must be isolated from the gas piping
system by closing the external main manual shutoff valve
and slightly opening the ground-joint union.
Fig. 14 Condensate Trap
13
Table 1 Physical Data Unit 48SS
UNIT SIZE 48SS 018040 024040 024060 030040 030060 030080 036060 036080 036100 036120
NOMINAL CAPACITY (ton) 1
1
2
222
1
2
2
1
2
2
1
2
3333
OPERATING WEIGHT (lb)
Without Base Rail 272 303 315 320 332 332 336 336 348 348
With Optional Base Rail 296 327 339 344 356 356 360 360 372 372
COMPRESSORS Rotary Reciprocating
Quantity 11
REFRIGERANT (R-22)
Charge (lb) 2.60 2.75 2.75 3.40 3.40 3.40 4.30 4.30 4.30 4.30
REFRIGERANT METERING DEVICE Acutrol™ Device
Orifice ID (in.) .030 .030 .030 .030 .030 .030 .032 .032 .032 .032
CONDENSER COIL
Rows...Fins/in. 1...17 1...17 1...17 2...17 2...17 2...17 2...17 2...17 2...17 2...17
Face Area (sq ft) 5.95 5.95 5.95 5.95 5.95 5.95 5.95 5.95 5.95 5.95
CONDENSER FAN
Nominal Cfm 1700 1700 1700 1900 1900 1900 1900 1900 1900 1900
Diameter (in.) 18 18 18 18 18 18 18 18 18 18
Motor Hp (Rpm)
1
8
(850)
1
8
(850)
1
8
(850)
1
8
(850)
1
8
(850)
1
8
(850)
1
4
(1050)
1
4
(1050)
1
4
(1050)
1
4
(1050)
EVAPORATOR COIL
Rows Fins/in.
3...15 3...15 3...15 3...15 3...15 3...15 3...15 3...15 3...15 3...15
Face Area (sq ft) 1.83 2.29 2.29 2.29 2.29 2.29 3.06 3.06 3.06 3.06
EVAPORATOR FAN Direct Drive
Nominal Airflow (Cfm) 600 800 800 1000 1000 1000 1200 1200 1200 1200
Size (in.) 10x10 10x10 10x10 10x10 10x10 10x10 10x10 10x10 10x10 10x10
Motor Hp
1
4
1
4
1
4
1
4
1
4
1
4
1
2
1
2
1
2
1
2
FURNACE SECTION*
Burner Orifice (Qty...drill size)
Natural Gas
1...32 1...32 2...40 1...32 2...40 2...32 2...40 2...32 2...30 3...32
Burner Orifice (Qty...drill size)
Propane Gas
1...41 1...41 2...47 1...41 2...47 2...42 2...47 2...42 2...40 3...42
RETURN-AIR FILTERS (in.)†
Throwaway 20x20 20x20 20x20 20x24 20x24 20x24 20x24 20x24 20x24 20x24
UNIT SIZE 48SS 042060 042080 042100 042120 048080 048100 048120 048140 060080 060100 060120 060140
NOMINAL CAPACITY (ton) 3
1
2
3
1
2
3
1
2
3
1
2
44445555
OPERATING WEIGHT (lb)
Without Base Rail 375 375 387 387 414 426 426 426 453 465 465 465
With Optional Base Rail 399 399 411 411 438 450 450 450 477 489 489 489
COMPRESSORS Reciprocating Hermetic Scroll
Quantity 11
REFRIGERANT (R-22)
Charge (lb) 5.20 5.20 5.20 5.20 6.50 6.50 6.50 6.50 7.00 7.00 7.00 7.00
REFRIGERANT METERING Acutrol Device
DEVICE
Orifice ID (in.) .034 .034 .034 .034 .030 .030 .030 .030 .030 .030 .030 .030
CONDENSER COIL
Rows...Fins/in. 2...17 2...17 2...17 2...17 2...17 2...17 2...17 2...17 2...17 2...17 2...17 2...17
Face Area (sq ft) 7.04 7.04 7.04 7.04 8.67 8.67 8.67 8.67 8.67 8.67 8.67 8.67
CONDENSER FAN
Nominal Cfm 1900 1900 1900 1900 2400 2400 2400 2400 2400 2400 2400 2400
Diameter (in.) 18 18 18 18 20 20 20 20 20 20 20 20
Motor Hp (Rpm)
1
4
(1050)
1
4
(1050)
1
4
(1050)
1
4
(1050)
1
3
(1050)
1
3
(1050)
1
3
(1050)
1
3
(1050)
1
3
(1050)
1
3
(1050)
1
3
(1050)
1
3
(1050)
EVAPORATOR COIL
Rows Fins/in. 3...15 3...15 3...15 3...15 3...15 3...15 3...15 3...15 4...15 4...15 4...15 4...15
Face Area (sq ft) 3.33 3.33 3.33 3.33 4.44 4.44 4.44 4.44 4.44 4.44 4.44 4.44
EVAPORATOR FAN Direct Drive
Nominal Airflow (Cfm) 1400 1400 1400 1400 1600 1600 1600 1600 1995 1995 1995 1995
Size (in.) 10x10 10x10 10x10 10x10 10x10 10x10 10x10 10x10 10x11 10x11 10x11 10x11
Motor Hp
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
1111
FURNACE SECTION*
Burner Orifice (Qty...drill size)
Natural Gas
2...40 2...32 2...30 3...32 2...32 2...30 3...32 3...31 2...32 2...30 3...32 3...31
Burner Orifice (Qty...drill size)
Propane Gas
2...47 2...42 2...40 3...42 2...42 2...40 3...42 3...40 3...42 2...40 3...42 3...40
RETURN-AIR FILTERS (in.)†
Throwaway 24x24 24x24 24x24 24x24 24x30 24x30 24x30 24x30 24x30 24x30 24x30 24x30
*Based on altitude of 0-2000 feet.
†Required filter sizes shown are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated cool-
ing airflow or the heating airflow at a velocity of 300 ft/min for throwaway type or 450 ft/min for high-capacity type.
For non-standard air filters, air filter pressure drop must not exceed 0.08 in. wg.
14
Table 2 Physical Data Unit 48SX
UNIT SIZE 48SX 024040 024060 030040 030060 030080 036060 036080 036100 036120
NOMINAL CAPACITY (ton) 222
1
2
2
1
2
2
1
2
3333
OPERATING WEIGHT (lb)
Without Base Rail 333 345 336 348 348 366 366 378 378
With Optional Base Rail 357 369 360 372 372 390 390 402 402
COMPRESSORS Scroll
Quantity 1
REFRIGERANT (R-22)
Charge (lb) 3.9 3.9 4.5 4.5 4.5 5.4 5.4 5.4 5.4
REFRIGERANT METERING DEVICE Acutrol™ Device
Orifice ID (in.) .034 .034 .030 .030 .030 .032 .032 .032 .032
CONDENSER COIL
Rows...Fins/in. 2...17 2...17 2...17 2...17 2...17 2...17 2...17 2...17 2...17
Face Area (sq ft) 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0
CONDENSER FAN
Nominal Cfm 2200 2200 2200 2200 2200 2200 2200 2200 2200
Diameter (in.) 20 20 20 20 20 20 20 20 20
Motor Hp (Rpm)
1
4
(1100)
1
4
(1100)
1
4
(1100)
1
4
(1100)
1
4
(1100)
1
4
(1100)
1
4
(1100)
1
4
(1100)
1
4
(1100)
EVAPORATOR COIL
Rows Fins/in.
2...15 2...15 3...15 3...15 3...15 4...15 4...15 4...15 4...15
Face Area (sq ft) 3.6 3.6 2.7 2.7 2.7 3.6 3.6 3.6 3.6
EVAPORATOR FAN* Direct Drive
Nominal Airflow (Cfm) 800 800 1000 1000 1000 1200 1200 1200 1200
Size (in.) 10x10 10x10 10x10 10x10 10x10 10x10 10x10 10x10 10x10
Motor Hp
1
4
1
4
1
4
1
4
1
4
1
2
1
2
1
2
1
2
FURNACE SECTION†
Burner Orifice (Qty...drill size)
Natural Gas
1...32 2...40 1...32 2...40 2...32 2...40 2...32 2...30 3...32
Burner Orifice (Qty...drill size)
Propane Gas
1...41 2...47 1...41 2...47 2...42 2...47 2...42 2...40 3...42
RETURN-AIR FILTERS (in.)**
Disposable 24x24 24x24 24x24 24x24 24x24 24x24 24x24 24x24 24x24
UNIT SIZE 48SX 042060 042080 042100 042120 048080 048100 048120 048140 060080 060100 060120 060140
NOMINAL CAPACITY (ton) 3
1
2
3
1
2
3
1
2
3
1
2
44445555
OPERATING WEIGHT (lb)
Without Base Rail 391 391 403 403 422 434 434 434 453 465 465 465
With Optional Base Rail 415 415 427 427 446 458 458 458 477 489 489 489
COMPRESSORS Scroll
Quantity 1
REFRIGERANT (R-22)
Charge (lb) 5.7 5.7 5.7 5.7 5.8 5.8 5.8 5.8 7.00 7.00 7.00 7.00
REFRIGERANT METERING Acutrol Device
DEVICE
Orifice ID (in.) .034 .034 .034 .034 .034 .034 .034 .034 .030 .030 .030 .030
CONDENSER COIL
Rows...Fins/in. 2...17 2...17 2...17 2...17 2...17 2...17 2...17 2...17 2...17 2...17 2...17 2...17
Face Area (sq ft) 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.67 8.67 8.67 8.67
CONDENSER FAN
Nominal Cfm 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400
Diameter (in.) 20 20 20 20 20 20 20 20 20 20 20 20
Motor Hp (Rpm)
1
4
(1100)
1
4
(1100)
1
4
(1100)
1
4
(1100)
1
4
(1100)
1
4
(1100)
1
4
(1100)
1
4
(1100)
1
3
(1050)
1
3
(1050)
1
3
(1050)
1
3
(1050)
EVAPORATOR COIL
Rows Fins/in. 3...15 3...15 3...15 3...15 4...15 4...15 4...15 4...15 4...15 4...15 4...15 4...15
Face Area (sq ft) 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.44 4.44 4.44 4.44
EVAPORATOR FAN* Direct Drive
Nominal Airflow (Cfm) 1400 1400 1400 1400 1600 1600 1600 1600 1995 1995 1995 1995
Size (in.) 10x10 10x10 10x10 10x10 10x10 10x10 10x10 10x10 10x11 10x11 10x11 10x11
Motor Hp
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
1111
FURNACE SECTION†
Burner Orifice (Qty...drill size)
Natural Gas
2...40 2...32 2...30 3...32 2...32 2...30 3...32 3...31 2...32 2...30 3...32 3...31
Burner Orifice (Qty...drill size)
Propane Gas
2...47 2...42 2...40 3...42 2...42 2...40 3...42 3...40 3...42 2...40 3...42 3...40
RETURN-AIR FILTERS (in.)**
Disposable 24x30 24x30 24x30 24x30 24x30 24x30 24x30 24x30 24x30 24x30 24x30 24x30
*Size 048 evaporator fan is equipped with a 460-v or integrated control motor (ICM). Size 060 evaporator fan is
equipped with an ICM only. The ICM provides variable speed.
†Based on an altitude of 0-2000 feet.
**Required filter sizes shown are based on the ARI (Air Conditioning & Refrigeration Institute) rated heating airflow
at a velocity of 300 ft/min for throwaway type or 450 ft/min for high-capacity type. For non-standard air filters, air
filter pressure drop must not exceed 0.08 in. wg.
15
(Text continued from page 13)
Unstable operation may occur when the gas valve
and manifold assembly are forced out of position while
connecting improperly-routed rigid gas piping to the
gas valve. Use a backup wrench when making con-
nection to avoid strain on, or distortion of, the gas
control piping.
If a flexible conductor is required or allowed by the
authority having jurisdiction, black iron pipe shall
be installed at the gas valve and shall extend a mini-
mum of 2 in. outside the unit casing.
Never use a match or other open flame when check-
ing for gas leaks. Never purge gas line into com-
bustion chamber. Failure to follow this warning could
result in an explosion causing personal injury or death.
8. Check for gas leaks at the field-installed and factory-
installed gas lines after all piping connections have been
completed. Use soap-and-water solution (or method speci-
fied by local codes and/or regulations).
Step 9 Install Duct Connections The unit
has duct flanges on the supply- and return-air openings on
the side and bottom of the unit. See Fig. 2-9 for connection
sizes and locations.
CONFIGURING UNITS FOR DOWNFLOW (VERTICAL)
DISCHARGE
Before performing service or maintenance operations on
the system, turn off main power to unit or electrical shock
could result.
1. Open all electrical disconnects before starting any serv-
ice work.
2. Remove return duct cover located on duct panel.
Figure 16 shows duct cover removed. Save duct cover
and screws.
3. Locate lances in basepan insulation that are placed over
the perimeter of the vertical duct opening cover
(Fig. 17).
4. Using a straight edge and sharp knife, cut and remove
the insulation around the perimeter of the cover. Re-
move and save 5 screws securing the cover to the base-
pan and slide out the cover. Discard the cover (Fig. 18).
5. Remove supply duct cover located on duct panel.
Figure 16 shows duct cover removed. Save duct cover
and screws.
6. Remove and discard 2 screws which secure vertical dis-
charge opening cover to basepan (Fig. 19). Slide cover
forward to disengage, then tilt and remove cover through
vertical discharge opening in bottom of unit. Discard duct
cover (Fig. 20).
Collect ALL screws that were removed. Do not leave
screws on rooftop as permanent damage to the roof
may occur.
7. If unit ductwork is to be attached to vertical opening
flanges on the unit basepan (jackstand applications only),
do so at this time.
8. It is recommended that the basepan insulation around
the perimeter of the vertical return-air opening be se-
cured to the basepan with aluminum tape. Applicable
local codes may require aluminum tape to prevent ex-
posed fiberglass.
9. Cover both horizontal duct openings with the duct cov-
ers from Steps 2 and 5. Make sure opening is air- and
watertight.
10. After completing unit conversion, perform all safety checks
and power up unit.
NOTE: The design and installation of the duct system must
be in accordance with the standards of the NFPA for instal-
lation of nonresidence-type air conditioning and ventilating
systems, NFPA 90A or residence-type, NFPA 90B; and/or
local codes and residence-type, NFPA90B; and/or local codes
and ordinances.
Fig. 15 Sediment Trap
16
Table 3 Maximum Gas Flow Capacity*
NOMINAL
IRON PIPE,
SIZE
(in.)
INTERNAL
DIAMETER
(in.)
LENGTH OF PIPE, FT†
10 20 30 40 50 60 70 80 90 100 125 150 175 200
1
2
.622 175 120 97 82 73 66 61 57 53 50 44 40
3
4
.824 360 250 200 170 151 138 125 118 110 103 93 84 77 72
1 1.049 680 465 375 320 285 260 240 220 205 195 175 160 145 135
1
1
4
1.380 1400 950 770 600 580 530 490 460 430 400 360 325 300 280
1
1
2
1.610 2100 1460 1180 990 900 810 750 690 650 620 550 500 460 430
*Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5-in. wg (based on
a 0.60 specific gravity gas). Refer to Table C-4, National Fire Protection Association NFPA 54.
†This length includes an ordinary number of fittings.
SUPPLY DUCT OPENING RETURN DUCT OPENING
Fig. 16 Supply and Return Duct Openings
Fig. 17 Lance Location for Vertical Duct
Opening Cover
Fig. 18 Vertical Duct Cover Removed
Fig. 19 Removal of Vertical Discharge
Opening Cover
17
Adhere to the following criteria when selecting, sizing,
and installing the duct system:
1. Units are shipped with all 4 duct openings covered. Re-
move appropriate panels for intended installation.
2. Select and size ductwork, supply-air registers, and
return-air grilles according to American Society of
Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE) recommendations.
3. Use flexible transition between rigid ductwork and unit
to prevent transmission of vibration. The transition may
be screwed or bolted to duct flanges. Use suitable gaskets
to ensure weathertight and airtight seal.
4. All units must have field-supplied filters or accessory fil-
ter rack installed in the return-air side of the unit. Rec-
ommended sizes for filters are shown in Tables 1 and 2.
5. Size all ductwork for maximum required airflow (either
heating or cooling) for unit being installed. Avoid abrupt
duct size increases or decreases or performance may be
affected.
6. Adequately insulate and weatherproof all ductwork
located outdoors. Insulate ducts passing through uncon-
ditioned space, and use vapor barrier in accordance with
latest issue of Sheet Metal and Air Conditioning
Contractors NationalAssociation (SMACNA) andAirCon-
ditioning Contractors of America (ACCA) minimum in-
stallation standards for heating and air-conditioning sys-
tems. Secure all ducts to building structure.
7. Flash, weatherproof, and vibration-isolate all openings in
building structure in accordance with local codes and good
building practices.
Step 10 Install Electrical Connections
The unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground
may consist of an electrical wire connected to the unit
ground lug in the control compartment, or conduit ap-
proved for electrical ground when installed in accor-
dance with NEC (National Electrical Code) ANSI/
NFPA (latest edition) (in Canada, Canadian Electrical
Code CSA [Canadian Standards Association] C22.1) and
local electrical codes. Do not use gas piping as an elec-
trical ground. Failure to adhere to this warning could
result in personal injury or death.
Failure to follow these precautions could result in dam-
age to the unit being installed:
1. Make all electrical connections in accordance with NEC
ANSI/NFPA(latest edition) and local electrical codes gov-
erning such wiring. In Canada, all electrical connections
must be in accordance with CSA standard C22.1 Cana-
dian Electrical Code Part 1 and applicable local codes.
Refer to unit wiring diagram.
2. Use only copper conductor for connections between field-
supplied electrical disconnect switch and unit. DO NOT
USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within oper-
ating voltage range indicated on unit rating plate.
4. Do not damage internal components when drilling through
any panel to mount electrical hardware, conduit, etc. On
3-phase units, ensure phases are balanced within 2%. Con-
sult local power company for correction of improper volt-
age and/or phase imbalance.
HIGH-VOLTAGE CONNECTIONS The unit must have
a separate electrical service with a field-supplied, water-
proof, disconnect switch mounted at, or within sight from,
the unit. Refer to the unit rating plate for maximum fuse/
circuit breaker size and minimum circuit amps (ampacity)
for wire sizing. See Tables 4A and 4B for electrical data.
The field-supplied disconnect switch box may be mounted
on the unit over the high-voltage inlet hole when the
standard power and low-voltage entry points are used. See
Fig. 2-9 for acceptable location.
Standard Power Entry Proceed as follows to complete the
high-voltage connections to the unit:
1. Connect ground lead to chassis ground connection when
using separate ground wire.
2. Run high-voltage leads into unit control box.
3. Locate black and yellow wires connected to line side of
contactor.
4. Cut wires at partition where they exit control box.
5. Strip back leads and connect to high voltage leads. On
3-phase units, blue wire is provided stripped back and
ready to connect to high voltage lead. See unit wiring la-
bel and Fig. 21.
Fig. 20 Vertical Discharge Cover Removed
18
Table 4A Electrical Data Unit 48SS
UNIT
SIZE
48SS
V-PH-Hz
VOLTAGE
RANGE
COMPRESSOR
OUTDOOR-FAN
MOTOR
INDOOR-FAN
MOTOR
POWER SUPPLY
AWG60C
MIN WIRE
SIZE
MAX WIRE
LENGTH (ft)
Min Max RLA LRA FLA FLA MCA MOCP*
018 208/230-1-60 187 253 8.3 45.0 0.7 1.8 12.9 15 14 75
024 208/230-1-60 187 253 12.4 61.0 0.7 2.0 18.2 30 12 80
030
208/230-1-60 187 253 14.4 82.0 1.4 2.3 21.4 30 10 100
208/230-3-60 187 253 9.4 66.0 1.4 2.0 15.1 25 12 80
036
208/230-1-60 187 253 18.0 96.0 1.4 2.8 26.7 40 10 90
208/230-3-60 187 253 11.7 75.0 1.4 2.8 18.8 30 12 65
460-3-60 414 506 5.6 40.0 0.8 1.4 9.2 10 14 100
042
208/230-1-60 187 253 20.4 104.0 1.4 4.0 30.9 50 8 100
208/230-3-60 187 253 14.0 91.0 1.4 4.0 22.9 35 10 85
460-3-60 414 506 6.4 42.0 0.8 2.0 10.8 15 14 100
048
208/230-1-60† 187 253 21.8 124.0 2.1 5.0 40.1 60 8 100
208/230-1-60** 187 253 26.4 129.0 2.1 5.0 40.1 60 6 100
208/230-3-60† 187 253 12.8 93.0 2.1 5.0 25.9 40 10 75
208/230-3-60** 187 253 15.0 99.0 2.1 5.0 25.9 40 10 75
460-3-60† 414 506 6.4 46.5 1.1 2.3 13.7 20 14 100
460-3-60** 414 506 8.2 50.0 1.1 2.3 13.7 20 14 100
060
208/230-1-60 187 253 32.1 169.0 2.1 6.8 49.0 60 6 100
208/230-3-60 187 253 19.3 123.0 2.1 6.8 33.0 50 8 90
460-3-60 414 506 10.0 62.0 1.1 3.2 16.8 25 12 100
LEGEND
AWG American Wire Gage
FLA Full Load Amps
HACR Heating, Air Conditioning and
Refrigeration
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
RLA Rated Load Amps
*Fuse or HACR Breaker.
Carrier Scroll Compressor.
**Copeland Scroll Compressor.
NOTES:
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker. The CGA (Canadian Gas As-
sociation) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table, de-
termine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%.
Use the following formula to determine
the percentage of voltage imbalance.
% Voltage imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 1 464 1 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 452=5v
(BC) 464 457=7v
(AC) 457 455=2v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
19
Table 4B Electrical Data Unit 48SX
UNIT
SIZE
48SX
V-PH-Hz
VOLTAGE
RANGE
COMPRESSOR
OUTDOOR-FAN
MOTOR
INDOOR-FAN
MOTOR
POWER SUPPLY
AWG60C
MIN WIRE
SIZE
MAX WIRE
LENGTH (ft)
Min Max RLA LRA FLA FLA MCA MOCP*
024 208/230-1-60 187 253 12.9 62.5 1.4 2.0 19.5 30 12 75
030 208/230-1-60 187 253 15.0 76.0 1.4 2.6 22.8 30 10 100
036
208/230-1-60 187 253 16.7 95.0 1.4 2.8 25.1 30 10 95
208/230-3-60 187 253 10.9 75.0 1.4 2.8 17.8 25 12 70
460-3-60 414 506 5.4 40.0 0.8 1.4 9.0 10 14 100
042
208/230-1-60 187 253 20.0 104.0 1.4 3.1 29.5 45 10 80
208/230-3-60 187 253 13.9 88.0 1.4 3.1 21.9 30 10 60
460-3-60 414 506 6.8 44.0 0.8 1.6 10.9 15 14 100
048
208/230-1-60 187 253 26.4 129.0 1.4 7.2 41.6 60 6 100
208/230-3-60 187 253 15.0 99.0 1.4 7.2 27.4 40 10 70
460-3-60 414 506 8.2 49.5 0.8 2.3 13.4 20 14 100
060
208/230-1-60 187 253 32.1 169.0 2.1 7.2 49.4 60 6 100
208/230-3-60 187 253 19.3 123.0 2.1 7.2 33.4 50 8 90
LEGEND
AWG American Wire Gage
FLA Full Load Amps
HACR Heating, Air Conditioning and
Refrigeration
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
RLA Rated Load Amps
*Fuse or HACR Breaker.
Carrier Scroll Compressor.
**Copeland Scroll Compressor.
NOTES:
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker. The CGA (Canadian Gas As-
sociation) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table, de-
termine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%.
Use the following formula to determine
the percentage of voltage imbalance.
% Voltage imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 1 464 1 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 452=5v
(BC) 464 457=7v
(AC) 457 455=2v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52

Carrier 48SX024-060 User manual

Category
Split-system air conditioners
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI