Xtreme TX91 User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual
TX91 & TX91L
Isolated Online UPS
3.8kVA, 5kVA, 6kVA, 10kVA Models
User & Installaon Manual
www.xpcc.com | © 2020 Xtreme Power Conversion Corporaon. All rights reserved. (Rev 12/22/20)
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 2
Uninterrupble Power Supply
Table of Contents
1 Safety and EMC Instrucons.......................................................................4
1.1 Transportaon and Storage...................................................................................................... 4
1.2 Preparaon............................................................................................................................... 4
1.3 Installaon................................................................................................................................ 4
1.4 Connecon .............................................................................................................................. 4
1.5 Maintenance............................................................................................................................ 5
1.6 Operaon................................................................................................................................. 5
1.7 Recycling................................................................................................................................... 6
1.8 Standards..................................................................................................................................6
2 Installaon ...............................................................................................7
2.1 Unpacking and inspecon..........................................................................................................7
2.2 Rear Panel View.........................................................................................................................8
2.3 Baery Pack Rear Panel View....................................................................................................9
2.4 UPS Electrical Conntecons/Installaon.................................................................................10
2.5 Connecng UPS with Baery Packs..........................................................................................12
2.6 Baery Wiring Diagram...........................................................................................................12
2.7 Storage and Maintenance........................................................................................................13
3 Operaons..............................................................................................14
3.1 User Interface.........................................................................................................................14
3.1.1 Buon Operaon......................................................................................................14
3.1.2 LED Indicators...........................................................................................................14
3.1.3 LCD Panel................................................................................................................. 14
3.1.5 Operang Mode/ Descripons................................................................................ 17
3.2 UPS Operaon.........................................................................................................................19
4 Trouble Shoong......................................................................................29
4.1 Audible Alarm..........................................................................................................................29
4.2 Warning Indicator....................................................................................................................29
4.3 Warning Code Descripons.....................................................................................................30
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 3
Uninterrupble Power Supply
4.4 Trouble Shoong Chart...........................................................................................................31
5 Specicaons..........................................................................................32
5.1 TX91 Specicaons..................................................................................................................32
5.2 TX91L Specicaons.................................................................................................................33
6 Obtaining Service....................................................................................34
7 Xtreme Power Conversion Limited Warranty.............................................35
8 Xtreme Power Load Protecon Policy......................................................36
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 4
Uninterrupble Power Supply
1 Safety and EMC Instrucons
Safety Instrucons
Please read carefully the following user manual and the safety instrucons before installing the UPS or using the
UPS! Please comply with all warnings and operang instrucons in this manual. Save this manual and read care-
fully the following instrucons before installing the unit. Do not operate this unit before reading through all safety
informaon and operang instrucons carefully.
1.1 Transportaon and Storage
• Please transport the UPS system only in the original packaging to protect against shock and impact.
• The UPS must be stored in a room where it is venlated and dry.
1.2 Preparaon
• Condensaon may occur if the UPS system is moved directly from cold to warm environments. The UPS
system must be absolutely dry before being installed. Please allow at least two hours for the UPS system
to acclimate to the environment.
• Do not install the UPS system near water or in moist environments.
• Do not install the UPS system where it would be exposed
1.3 Installaon
Do not connect appliances or devices which would overload the UPS (e.g. motor-type equipment) to the
UPS output receptacles or terminal.
• Place cables in such a way that no one can step on or trip over them.
• Do not block air vents in the housing of the system components. The UPS system must be installed in a
locaon with good venlaon. Ensure enough space on each side for venlaon.
UPS has provided a ground terminal for equipotenal earth bonding to the external UPS baery cabinets
in the nal installed system conguraon.
• The UPS can be installed only by qualied maintenance personnel.
• An appropriate disconnect device for short-circuit backup protecon should be provided in the building
wiring installaon, upstream of the UPS.
An integral single emergency switching device which prevents further supply to the load by the UPS in
any mode of operaon should be provided in the building wiring installaon.
• Connect the ground before connecng to the building wiring terminal.
• Installaon and wiring must be performed in accordance with the local electrical laws and regulaons.
1.4 Connecon
• This UPS must be installed and grounded in accordance with local and naonal electrical code.
The power supply for this unit must be single-phase rated in accordance with the equipment nameplate.
It also must be suitably grounded.
There can be no derivaon in the line that goes from the Backfeed Protecon to the UPS, as the standard
safety would be infringed.
The power supply for this unit must be single-phase rated in accordance with the equipment nameplate.
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
BEFORE CONNECTING SUPPLY
• Use of this equipment in life support applicaons where failure of this equipment can reasonably be
expected to cause the failure of the life support equipment or to signicantly aect its safety or eecve-
ness is not recommended. Do not use this equipment in the presence of a ammable anesthec mixture
with air, oxygen or nitrous oxide.
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 5
Uninterrupble Power Supply
• Connect your UPS power module’s grounding terminal to a grounding electrode conductor.
• The UPS is connected to a DC energy source (baery). The output terminals may be live when the UPS
is not connected to an AC supply.
• Warning labels should be placed on all primary power switches installed in places away from the
device to alert the electrical maintenance personnel of the presence of a UPS in the circuit. The label will
bear the following or an equivalent text:
Before working on this circuit
Isolate Uninterrupble Power Supply (UPS)
Then check for Hazardous Voltage between
all terminals including the protected ground
Risk of Voltage Backfeed
1.5 Maintenance
• Even aer the UPS is disconnected from the mains, the components inside are sll connected to the
baery packs which may be potenally dangerous.
• Before carrying out any kind of service or maintenance, disconnect the baeries and verify that no
current is present and no hazardous voltage exists in the terminals of high capability capacitor such as
BUS-capacitors.
• Verify that no between the baery terminals and the ground is present before maintenance or repair.
In this product, the baery circuit is not isolated from the input voltage. Hazardous voltages may occur
between the baery terminals and the ground.
• Baeries may cause electric shock and have a high short-circuit current. Please remove all wristwatch-
es, rings and other metal personal objects before maintenance or repair, and only use tools with insu-
lated grips and handles for maintaining or repairing.
• When replacing the baeries, install the same number and same type of baeries.
• Do not aempt to dispose of baeries by burning them. This could cause baery explosion. The baer-
ies must be rightly deposed according to local regulaon.
• Do not open or destroy baeries. Escaping electrolyte can cause injury to the skin and eyes. It may be
toxic.
• Please replace the fuse only with the same type and amperage in order to avoid re hazards.
• Do not disassemble the UPS system.
TX91 3.8 -10kVA & TX91L 3.8 10kVA Users Manual Uninterrupble Power Supply
Xtreme Power Conversion Corporaon Page 3
• When replacing baeries, it is necessary to replace ALL baeries with the same quanty, type & capac-
ity.
• Do not plug or unplug the baery connector if UPS is working in baery mode.
• This unit is not designed for outdoor use.
1.6 Operaon
• Do not disconnect the ground conductor cable on the UPS or the building wiring terminals in any me
since this would cancel the protecve ground of the UPS system and of all connected loads.
• The UPS system features its own, internal current source (baeries). The UPS output receptacles or
output terminal blocks may be electrically live even if the UPS system is not connected to the building
wiring system.
• In order to fully disconnect the UPS system, rst press the “OFF” buon and then disconnect the
mains.
• Ensure that no liquid or other foreign objects can enter into the UPS system.
• The UPS can be operated by any individuals with no previous experience.
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 6
Uninterrupble Power Supply
• Use of this equipment in life support applicaons where failure of this equipment can reasonably be expected
to cause the failure of the life support equipment or to signicantly aect its safety or eecveness is not rec-
ommended. Do not use this equipment in the presence of a ammable anesthec mixture with air, oxygen or
nitrous oxide.
• Connect your UPS power module’s grounding terminal to a grounding electrode conductor.
• The UPS is connected to a DC energy source (baery). The output terminals may be live when the UPS is not
connected to an AC supply.
1.7 Recycling the Used Baery
• Do not dispose of the baery in a re. Baery may explode. Proper disposal of baery is re-
quired. Refer to your local codes for disposal requirements. For more informaon, contact your
local recycling/reuse or hazardous waste center.
• Do not open or mulate the baery. Released electrolyte is harmful to the skin and eyes. It
may be toxic.
1.8 Standards
* Safety
Safety Conformance: IEC/EN 62040-1,UL1778 (5th Edion)
Safety Markings : cTUVus, CE
* EMI
Conducted Emission..............................:IEC/EN 62040-2,FCC PART15 CLASS A
Radiated Emission.................................:IEC/EN 62040-2,FCC PART15 CLASS A
*EMS
ESD.........................................................:IEC/EN 61000-4-2 Level 4
RS........................................................ ...:IEC/EN 61000-4-3 Level 3
EFT......................................................... :IEC/EN 61000-4-4 Level 4
SURGE................................................... :IEC/EN 61000-4-5 Level 4
CS........................................................... :IEC/EN 61000-4-6 Level 3
Power-frequency Magnec eld.............. :IEC/EN 61000-4-8 Level 4
Low Frequency Signals............................:IEC/EN 61000-2-2
Warning: This is a product for commercial and industrial applicaon in the second environment-installaon re-
stricons or addional measures may be needed to prevent disturbances.
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 7
Uninterrupble Power Supply
2 Installaon
2.1 Unpacking and Inspecon
Unpack the package and check the package contents. The shipping package contains:
● One UPS
● One user manual
● One monitoring soware CD
● One RS-232 cable (opon)
● One USB cable
● One share current cable (only available for parallel model)
NOTE: Before installaon, please inspect the unit. Be sure that nothing inside the package is damaged during trans-
portaon. Do not turn on the unit and nofy the carrier and dealer immediately if there is any damage or lacking
of some parts. Please keep the original package in a safe place for future use.
Unpack the External Baery Pack (if supplied)
NOTE: Baery is very heavy so be cauous when unpacking and liing the unit to avoid injury
• External Baery Pack
• Quick Guide
• Baery connecon cable x 1
NOTE: Before installaon, please inspect the system components. Be sure that nothing inside the package was
damaged during transportaon. Do not turn on the UPS system and nofy the carrier and dealer immediately if
there is any damage or missing parts. Please keep the original packaging in a safe place for future use.
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 8
Uninterrupble Power Supply
2.2 Rear Panel View
Diagram 1: Rear Panel Overlook Diagram 2: Input/Output Terminal
1. RS-232 communicaon port
2. USB communicaon port
3. Emergency power o funcon connector (EPO connector)
4. Share current port (only available for parallel model)
5. Parallel port (only available for parallel model)
6. Intelligent slot
7. Charger fan
8. Power stage fan
9. Maintenance bypass switch
10. Input circuit breaker
11. Isolaon transformer fan
12. Input/Output terminal (Refer to Diagram 2 for the details)
13. External baery connector
14. Non-isolated neutral
15. ISO TAP selecons
16. Output
17. Input
18. Input ground
19. Output ground
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 9
Uninterrupble Power Supply
2.3 Baery Pack Rear Panel View
TX91-BP20/BP40/BP60 baery pack
Figure 2-4
1. DC connector: connects to either UPS or 2nd baery pack.
2. DC breaker: Baery over-current protecon breaker.
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 10
Uninterrupble Power Supply
2.4 UPS Electrical Connecons/Installaon
Installaon and wiring must be performed in accordance with the local electric laws/regulaons and execute the
following instrucons by professional personnel.
1. Make sure the mains wire and breakers in the building are sized for the rated capacity of UPS to avoid
the hazards of electric shock or re.
2. Switch o the mains switch in the building before installaon.
3. Turn o all the connected devices before connecng to the UPS.
4. Prepare wiring based on the following table:
Model Wiring spec (AWG)
Input Output Non-isolated
Neutral
Ground
3.8K 8 8 8 8
5K 8 8 8 8
6K 6 6 6 6
10K 4 4 4 4
Model Recommended Input Overcurrent Protecon
3.8K 30A
5K 30A
6K 40A
10K 70A
NOTE: The selecons for size and color of wires should follow the local electrical laws and regulaons.
5.Remove the terminal block cover on the rear panel of UPS
UPS Terminal Block Wiring Diagram UPS Transformer Diagram
Figure 2-3 Figure 2-4
1. Connect input L1 wire to UPS input L1 terminal.
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 11
Uninterrupble Power Supply
2. Connect input L2 wire to UPS input L2 terminal.
3. Connect input GND wire to input GND terminal.
4. Connect output L1 wire to UPS output L1 terminal.
5. Connect output L2 wire to UPS output L2 terminal.
6. Connect output N wire to UPS N terminal.
7. Ensure ISO TAP Jumper is in correct posion (208V for 208V input or 240V for any other input
voltages).
8. Ensure Output voltage parameter is set to match the site input voltage. Refer to secon 3.3
NOTE 1: The ISO Tap Selector Jumper is electrically located between the output of the inverter and the
transformer primary. In the 208V posion it steps up the voltage by 15%. In the 240v posion there is
no voltage change. 208V is default Posion. Refer to gure 2-4.
Voltage Conguraon Chart
Standard Sengs
Input Voltage Iso Tap Posion Voltage Out
208 208 240/120 (Default)
240 240 240/120
Addional Sengs
Input Voltage Iso Tap Posion Voltage Out
208 240 208/104
220 208
240
244/122
220/110
230 208
240
256/128
230/115
240 208 266/133
NOTE 1: If other than default seng is desired, conguraon can be done at the factory for an
addional voltage conguraon fee.
6. Aer connecng the wires, replace the terminal block cover on the rear panel of the UPS.
NOTE 1: Install the output breaker between the output terminal and the Load. I.A.W NEC code.
NOTE 2: UPS Cabinet contains an Isolaon Transformer with N-G bond. This system qualies as a
separately derived source.
Warning:
Make sure the UPS is turned o before installaon.
The UPS should not be turned on during wiring connecon.
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 12
Uninterrupble Power Supply
2.5 Connecng UPS with Baery Packs
1. Connect one end of baery connecon cable to Baery DC connector.
2. Connect other end of baery connecon cable to UPS external baery connector.
3. If there is another external baery connect one end of Baery connecon cable to rst
baery pack DC connector. Then connect other end to second baery pack DC connector.
2.6 Baery Wiring Diagram
TX91-BP20 Baery Wiring Diagram TX91-BP40 Baery Wiring Diagram
Figure 2-18 Figure 2-19
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 13
Uninterrupble Power Supply
TX91-BP60 Baery Wiring Diagram
Figure 2-19
Type of Baery Required
• TX91 - (20) 12V 9AH baeries.
• TX91L - external baeries only.
• External baery pack – (20), (40), or (60) pieces of 12V 9AH baeries.
2.7 Storage & Maintenance
The unit contains no user-serviceable parts. If the baery service life (3~5 years at 25°C ambient temperature)
has been exceeded, the baeries must be replaced. In this case, please contact your dealer.
Be sure to deliver the spent baery to a recycling facil-
ity or ship it to your dealer in the replacement baery
packing material.
Before storing, charge the unit 7 hours. Store the unit covered and upright in a cool, dry locaon. During storage,
recharge the baery in accordance with the following table:
Storage Temperature Recharge Frequency Charging Duraon
-25°C - 40°C Every 3 months 1-2 hours
40°C - 45°C Every 2 months 1-2 hours
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 14
Uninterrupble Power Supply
Soware Installaon
For opmal computer system protecon, install UPS monitoring soware to fully congure UPS
shutdown. Refer to included Viewpower CD.
3 Operaons
3.1 User Interface
3.1.1 Buon Operaon
Buon Funcon
ON/Enter Buon Turn on the UPS: Press and hold the buon more than 0.5s to turn on the UPS.
Enter Key: Press this buon to conrm the selecon in seng menu.
OFF/ESC Buon Turn o the UPS: Press and hold the buon more than 0.5s to turn o the UPS.
Esc key: Press this buon to return to last menu in seng menu.
Test/Up Buon Baery test: Press and hold the buon more than 0.5s to test the baery while in AC
mode, or CVCF mode.
UP key: Press this buon to display next selecon in seng menu.
Mute/Down Buon Mute the alarm: Press and hold the buon more than 0.5s to mute the buzzer. Please refer
to secon 3-4-9 for details.
Down key: Press this buon to display previous selecon in seng menu.
Test/Up + Mute/
Down Buon
Press and hold the two buons simultaneous more than 1s to enter/escape the seng
menu.
* CVCF mode means converter mode.
3.1.2 LED Indicators
LCD Panel
LED indicators
LED Indicators:
There are 4 LEDs on front panel to show the UPS working status:
Mode LED Bypass Line Baery Fault
UPS Startup
No Output mode
Bypass mode
AC mode
Baery mode
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 15
Uninterrupble Power Supply
CVCF mode
Baery Test
ECO mode
Fault
Note: ● means LED is lighng, and ○ means LED is faded.
3.1.3 LCD Panel
Display Funcon
Backup me informaon
Indicates baery discharge me in numbers.
H: hours, M: minutes, S: seconds
Fault informaon
Indicates that the warning and fault occurs.
Indicates the fault codes, and the codes are listed in details in secon 3-9.
Mute operaon
Indicates that the UPS alarm is disabled.
Output & Baery voltage informaon
Indicates the output voltage, frequency or baery voltage.
Vac: output voltage, Vdc: baery voltage, Hz: frequency
Load informaon
Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates overload.
Indicates the load or the output is shorted.
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 16
Uninterrupble Power Supply
Mode operaon informaon
Indicates the UPS connects to the mains.
Indicates the baery is working.
Indicates the bypass circuit is working.
Indicates the ECO mode is enabled.
Indicates the Inverter circuit is working.
Indicates the output is working.
Baery informaon
Indicates the Baery capacity by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates the baery is not connected.
Indicates low baery level and low baery voltage.
Input & Baery voltage informaon
Indicates the input voltage or frequency or baery voltage.
Vac: Input voltage, Vdc: baery voltage, Hz: input frequency
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 17
Uninterrupble Power Supply
3.1.5 Operang Mode/Descripons
Operang mode/status
AC mode Descripon
When the input voltage is within acceptable range, UPS will provide pure
and stable AC power to output. The UPS will also charge the baery at AC
mode.
LCD display
ECO mode Descripon
When the input voltage is within voltage regulaon range and ECO mode is
enabled, UPS will bypass voltage to output for energy saving.
LCD display
CVCF mode Descripon
When input frequency is within 46 to 64Hz, the UPS can be set at a con-
stant output frequency, 50 Hz or 60 Hz. The UPS will sll charge baery
under this mode.
LCD display
Baery mode Descripon
When the input voltage is beyond the acceptable range or there is input
power failure, UPS will backup power from baery and alarm will beep
every 4 seconds.
LCD display
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 18
Uninterrupble Power Supply
Operang mode/status
Bypass mode Descripon
When input voltage is within acceptable range and bypass is enabled, turn
o the UPS and it will enter Bypass mode. Alarm beeps every two minutes.
LCD display
Baery Test Descripon
When UPS is in AC mode or CVCF mode, press Testkey for more than
0.5s. Then the UPS will beep once and start “Baery Test”. The line be-
tween I/P and inverter icons will blink to remind users. This operaon is
used to check the baery status.
LCD display
Fault status Descripon
When a UPS fault has happened, it will display fault messages in LCD panel.
LCD display
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 19
Uninterrupble Power Supply
3.2 UPS Operaon
Turn on the UPS with ulity power supply (in AC mode)
1) Aer power supply is connected correctly, Set the input breaker at “ON” posion. At this me the fan
is running and the UPS supplies power to the loads via the bypass. The UPS is operang in Bypass mode.
NOTE: When UPS is in Bypass mode, the output voltage will directly get power from ulity aer you switch on the
input breaker. In Bypass mode, the load is not protected by UPS. To protect your precious devices, you should turn
on the UPS. Refer to next step.
2) Press and hold the “ON” buon for 0.5s to turn on the UPS and the buzzer will beep once.
3) A few seconds later, the UPS will enter AC mode. If the ulity power is abnormal, the UPS will operate
in Baery mode without interrupon.
NOTE: When the UPS is running out baery, it will shut down automacally at Baery mode. When the ulity
power is restored, the UPS will auto restart.
Turn on the UPS without ulity power supply (in Baery mode)
1. Make sure that the breaker of the baery pack is at “ON” posion.
2. Press and hold the “ON” buon for 0.5s to turn on the UPS, and the buzzer will beep once.
3. A few seconds later, the UPS will be turned on and enter to Baery mode.
Connect devices to UPS
1. Turn on the UPS rst and then switch on the devices one by one, the LCD panel will display total load
level.
2. If it is necessary to connect inducve loads such as a printer, the in-rush current should be calculated
carefully to ensure if it meets the capacity of the UPS, because the power consumpon of this kind of loads
is too big.
3. If the UPS is overloaded, the buzzer will beep twice every second.
4. When the UPS is overloaded, please remove some loads immediately. It is recommended to have the
total loads connected to the UPS less than 80% of its nominal power capacity to prevent overload for sys-
tem safety.
5. If the overload me is over acceptable me listed in spec at AC mode, the UPS will automacally trans-
fer to Bypass mode. Aer the overload is removed, it will return to AC mode. If the overload me is over
acceptable me listed in spec at Baery mode, the UPS will become fault status. At this me, if bypass is
enabled, the UPS will power the load via bypass. If bypass funcon is disabled or the input power is not
within bypass acceptable range, it will cut o output directly.
Charge the baeries
1. Aer the UPS is connected to the ulity power, the charger will charge the baeries automacally except in Bat-
tery mode or during baery self-test.
2. It is suggested to charge baeries at least 10 hours before use. Otherwise, the backup me may be shorter than
expected.
Baery mode operaon
1. When the UPS is in Baery mode, the buzzer will beep according to dierent baery capacity. If the
baery capacity is more than 25%, the buzzer will beep once every 4 seconds; If the baery voltage drops
to the alarm level, the buzzer will beep quickly (once every sec) to remind users that the baery is at low
level and the UPS will shut down automacally soon. Users could switch o some non-crical loads to dis-
able the shutdown alarm and prolong the backup me (the UPS would cut o the programmable output
terminal automacally when the programmable mer funcon is enabled). If there is no more load to be
switched o at that me, you have to shut down all loads as soon as possible to protect the devices or save
data. Otherwise, there is a risk of data loss or load failure.
2. In Baery mode, if buzzer sound annoys, users can press the Mute buon to disable the buzzer.
Xtreme Power Conversion Corporaon
TX91 3.8- 10kVA Users Manual
Page 20
Uninterrupble Power Supply
3. The backup me may very from dierent environment temperature and load type.
4. The backup me depends on the quanty external baeries.
5. When seng backup me for 16.5 hours (default value from LCD panel), aer discharging 16.5 hours,
UPS will shut down automacally to protect the baery. This baery discharge protecon can be enabled
or disabled through LCD panel control. (Refer to 3.3 LCD Sengs secon)
Test the baeries
1. If you need to check the baery status when the UPS is running in AC mode/CVCF mode/ECO mode, you
could press the “Test” buon to let the UPS do baery self-test.
2. To keep the system reliable, the UPS will perform the baery self-test automacally periodically. The
default seng period is once per week.
3. Users also can set baery self-test through monitoring soware.
4. If the UPS is at baery self-test, the LCD display and buzzer indicaon will be the same as at Baery
mode except that the baery LED is ashing.
Turn o the UPS with ulity power supply in AC mode
1. Turn o the inverter of the UPS by pressing “OFF” buon for at least 0.5s, and then the buzzer will beep
once. The UPS will turn into Bypass mode.
NOTE 1: If the UPS has been set to enable the bypass output, it will bypass voltage from ulity power to output
terminal even though you have turned o the UPS (inverter).
NOTE 2: Aer turning o the UPS, please be aware that the UPS is working at Bypass mode and there is risk of
power loss for connected devices.
2. In Bypass mode, output voltage of the UPS is sll present. In order to cut o the output, switch o the
input breaker. A few seconds later, there is no display shown on the display panel and UPS is completely
o.
Turn o the UPS without ulity power supply in Baery mode
1. Turn o the UPS by pressing “OFF” buon for at least 0.5s, and then the buzzer will beep once.
2. Then UPS will cut o power to output and there is no display shown on the display panel.
Mute the buzzer
1. To mute the buzzer, please press the “Mute” buon for at least 0.5s. If you press it again aer the buzzer
is muted, the buzzer will beep again.
2. Some warning alarms can’t be muted unless the error is xed.
Operaon in warning status
1. When Fault LED ashes and the buzzer beeps once every second, it means that there are some prob-
lems for UPS operaon. Users can get the fault code from LCD panel. Please check the trouble shoong
table in secon 4 for details.
Operaon in Fault mode
1. When Fault LED illuminates and the buzzer beeps connuously, it means that there is a fatal error in the
UPS. Users can get the fault code from display panel. Please check the trouble shoong table in secon 4
for details.
2. Please check the loads, wiring, venlaon, ulity, baery and so on aer the fault occurs. Don’t try to
turn on the UPS again before solving the problems. If the problems can’t be xed, please contact the dis-
tributor or service people immediately.
3. For emergency case, please cut o the connecon from ulity, external baery, and output immediately
to avoid more risk or danger.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38