Service Guide | Improved Neutral Zone Ref. Control AK-SC 255
© Danfoss | ADAP-KOOL® | 2018.08
4 | AX279033990251en-000101
[nzwp.p65]
3
AKCESS © 1999 Danfoss Inc. 17 May 1999
Zone to the Plus Zone, and if the Up
Timer has reached or reaches its delay
setting, refrigeration capacity is added
and the Up Timer is restarted at zero.
Each time the Up Timer reaches its
delay setting, a step of refrigeration
capacity is added.
4. If the pressure is in the Plus Zone and
the slope of the pressure curve changes
from positive (rising) to negative
(falling) the Up Timer is paused. Accu-
mulated time is preserved on the timer.
5. If the pressure is in the Plus Zone and
the slope of the pressure curve changes
from negative to positive, the Up Timer
is re-started.
6. If the pressure enters the Plus Plus
Zone, and if the Up Timer has reached
or reaches the Plus Plus Zone delay
time [(Plus Zone Delay) X (Plus Plus
Delay Multiplier)], refrigeration capac-
ity will be added. While the pressure is
in the Plus Plus Zone, capacity steps are
added based strictly on the Up Timer
value, regardless of the slope of the
pressure curve. Each time the Up
Timer reaches the Plus Plus Zone delay
time, a step of refrigeration capacity is
added. The Up Timer continues to run
in the Plus Plus Zone regardless of the
slope of the pressure curve.
7. When the pressure falls from the Plus
Plus Zone to the Plus Zone, no change
in refrigeration capacity occurs and the
Up Timer is paused and remains paused
as long as the slope of the pressure
curve remains negative. The Down
Timer starts.
8. If the pressure falls from the Neutral
Zone to the Minus Zone, and if the
Down Timer has reached or reaches the
Minus Zone Delay setting, refrigeration
capacity is dropped and the Down
Timer is re-started at zero. Each time
the Down Timer reaches the Minus
Zone delay setting, a step of refrigera-
tion capacity is dropped.
9. If the pressure is in the Minus Zone,
and the slope of the pressure curve is
negative, and the Down Timer timer
reaches the Minus Zone Delay setting,
refrigeration capacity is dropped and the
Down Timer is restarted at zero.
10. If the pressure is in the Minus Zone,
and the slope of the pressure curve
changes from negative (falling) to
positive (rising), the Down Timer is
paused. Accumulated time is preserved
on the timer.
11. If the pressure is in the Minus Zone and
the slope of the pressure curve changes
from positive to negative, the Down
Timer is re-started.
12. If the pressure enters the Minus Minus
Zone, and if the Down Timer has
reached or reaches the Minus Minus
Zone Delay time [(Minus Zone Delay)
X (Minus Minus Delay Multiplier)],
refrigeration capacity will be dropped.
While the pressure is in the Minus
Minus Zone, capacity steps are dropped
based strictly on the Down Timer,
regardless of the slope of the pressure
curve. Each time the Down Timer
reaches the Minus Minus Zone delay
time, a step of refrigeration capacity is
added. The Down Timer continues to
run in the Minus Minus Zone regardless
of the slope of the pressure curve.
Now let us look at an example, based on the
graph given above:
1. In the Neutral Zone, refrigeration
capacity is not changed; there are no
control actions. This is the situation in
our graph from its beginning to point a,
and is indicated by the level arrow on
the “Cap” line in the diagram (indicat-
ing no change in capacity). The Up
Timer is running (in our example, the
timer is set to 120 seconds.)
2. Somewhere between points a and b, the