Service Guide | Lighting control AK-SC 255
AX279033841250en-000101 | 3
© Danfoss | ADAP-KOOL® | 2018.08
Pre delay: Delay in minutes before the zone can come ON. (Scheduled time)
Post delay: Delay in minutes before the zone can be turned OFF.
Minimum ON time: The time that must elapse once the zone has been turned OFF,
before the zone can be turned OFF again.
Minimum OFF time: The time the zone MUST stay stay OFF before coming back
ON.
The ‘Min Out & Max Out’ fields would are interpreted as follows:
Min Out at:
If the skylight sensor indicated a reading greater than or equal to 1800 footcandles (fc),
the dimmer would be set to 2% . (Mnimum output)
Max out at:
If the skylight sensor indicated a reading at or below 800 fc, the dimmer would be set
to 65 % (Maximum output.)
All readings between these 2 extremes would set the dimmer output per the following:
(‘Min out at’ – sensor)
------------------------- x (‘Max. output’ – ‘Min. output’) + ‘Minimum output’
(‘Min out at’ – ‘Max out at’)
Thus, a sensor reading of 1200 fc would result in a dimmer output of:
(1800 – 1200) 600
----------------- x (65% - 2%) + 2 % = ------ x 63% + 2% = 39.8%
(1800 – 800) 1000