Santerno SUNWAY M XS 3800TL User manual

Type
User manual

This manual is also suitable for

15P0177B100
SUNWAY M XS
2200TL 3000TL 3800TL
SINGLE-PHASE SOLAR INVERTER
USER MANUAL
-Installation and Programming Instructions-
Issued 10/04/2012
R.00.1
Inverter Software Version: 1.055
Display Software Version: 1.3.3
Elettronica Santerno S.p.A.
Strada Statale Selice, 47 - 40026 Imola (BO) Italy
Tel. +39 0542 489711 - Fax +39 0542 489722
santerno.com sales@santerno.com
This manual is integrant and essential to the product. Carefully read the instructions contained
herein as they provide important hints for use and maintenance safety.
This device is to be used only for the purposes it has been designed to. Other uses should be
considered improper and dangerous. The manufacturer is not responsible for possible damages
caused by improper, erroneous and irrational uses.
Elettronica Santerno is responsible for the device in its original setting.
Any changes to the structure or operating cycle of the device must be performed or authorized by
the Engineering Department of Elettronica Santerno.
Elettronica Santerno assumes no responsibility for the consequences resulting by the use of non-
original spare-parts.
Elettronica Santerno reserves the right to make any technical changes to this manual and to the
device without prior notice. If printing errors or similar are detected, the corrections will be included
in the new releases of the manual.
The information contained herein is the property of Elettronica Santerno and cannot be reproduced.
Elettronica Santerno enforces its rights on the drawings and catalogues according to the law.
All the names and marks mentioned in this manual are the proprietary of their respective owners.
SUNWAY M XS
2200 TL
3000 TL
3800 TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
SUNWAY M XS 3000TL
3/124
0. TABLE OF CONTENTS
0. TABLE OF CONTENTS............................................................................................ 3
0.1. INDEX OF FIGURES ............................................................................................... 5
0.2. INDEX OF TABLES .................................................................................................. 7
1. SCOPE OF THIS MANUAL ...................................................................................... 8
2. GENERAL INFORMATION ...................................................................................... 8
2.1. DESCRIPTION OF THE PRODUCT ........................................................................ 8
2.2. BENEFITS ............................................................................................................... 8
2.3. OPERATING PRINCIPLE ........................................................................................ 9
2.4. MAIN STANDARD INTEGRATED FUNCTIONS ...................................................... 9
2.5. ATTACHED DOCUMENTATION ............................................................................ 10
3. BASIC INSTALLATION ...........................................................................................11
3.1. CAUTION STATEMENTS ...................................................................................... 11
3.2. CHECKING THE PRODUCT ON DELIVERY ......................................................... 13
3.2.1. DATAPLATE ............................................................................................................................ 14
3.3. TRANSPORT AND HANDLING ............................................................................. 17
3.4. INSTALLATION ...................................................................................................... 19
3.4.1. ENVIRONMENTAL REQUIREMENTS FOR THE EQUIPMENT STORAGE,
INSTALLATION AND OPERATION ....................................................................................... 19
3.4.2. WALL MOUNTING .................................................................................................................. 20
3.4.3. ELECTRICAL CONNECTION ................................................................................................ 23
3.5. COMMISSIONING ................................................................................................. 34
3.5.1. STOPPING THE INVERTER .................................................................................................. 35
3.6. QUICK CONFIGURATION ..................................................................................... 36
3.6.1. SETTING THE LANGUAGE ................................................................................................... 36
3.6.2. SETTING THE COUNTRY ..................................................................................................... 37
3.6.3. SETTING THE TIME ZONE .................................................................................................... 38
3.6.4. SETTING THE DATE AND TIME ........................................................................................... 39
3.6.5. SETTING THE CURRENCY ................................................................................................... 41
3.6.6. SETTING THE FEED-IN TARIFF ........................................................................................... 42
3.6.7. RESETTING THE HISTORY DATA ....................................................................................... 43
3.6.8. RESETTING THE DISPLAY ................................................................................................... 44
3.7. CONNECTIVITY .................................................................................................... 45
3.7.1. WI-FI CONNECTIVITY ............................................................................................................ 45
3.7.2. ACCESSING THE INVERTER DATA .................................................................................... 49
3.7.3. SUNWAYPORTAL.IT .............................................................................................................. 51
3.7.4. TECHNICAL SUPPORT ......................................................................................................... 52
3.7.5. CONNECTIVITY TROUBLESHOOTING ............................................................................... 53
3.8. DATALOGGING ..................................................................................................... 54
4. GRAPHIC INTERFACE MODULE ...........................................................................55
SUNWAY M XS 3000TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
4/124
4.1. NAVIGATING IN THE GRAPHIC INTERFACE ...................................................... 56
4.1.1. NAVIGATION BAR .................................................................................................................. 58
4.1.2. MENU AREA ............................................................................................................................ 58
4.1.3. STATUS BAR AREA ............................................................................................................... 58
4.2. DISPLAY WINDOWS AND DATA ENTER WINDOWS .......................................... 61
4.2.1. GRAPH WINDOW ................................................................................................................... 61
4.2.2. ALPHANUMERIC KEYPAD WINDOW .................................................................................. 62
4.2.3. LIST WINDOW ......................................................................................................................... 63
4.2.4. COMMAND EXECUTION WINDOW ..................................................................................... 63
4.3. DESCRIPTION OF THE MENUS ........................................................................... 64
4.3.1. ORGANISATION OF MEASURES AND PARAMETERS .................................................... 65
4.3.2. INFO MENU ............................................................................................................................. 67
4.3.3. GRAPH MENU ......................................................................................................................... 74
4.3.4. CONNECTIVITY MENU .......................................................................................................... 76
4.3.5. TOOLS MENU ......................................................................................................................... 80
4.3.6. ALARMS MENU ....................................................................................................................... 98
4.3.7. STATUS MENU ..................................................................................................................... 111
4.3.8. WARNINGS ............................................................................................................................ 113
4.3.9. WI-FI STATUS MENU ........................................................................................................... 114
5. ADVANCED INSTALLATION ................................................................................116
5.1. SERIAL COMMUNICATIONS .............................................................................. 116
5.1.1. GENERAL .............................................................................................................................. 116
5.1.2. DIRECT LINKING .................................................................................................................. 116
5.1.3. CONNECTION ....................................................................................................................... 116
5.1.4. COMMUNICATIONS PROTOCOL ...................................................................................... 117
5.1.5. SPECIFICATIONS OF THE SERIAL COMMUNICATIONS .............................................. 117
5.2. USB CONNECTION ............................................................................................. 118
5.3. GRID INTERFACE PROTECTION AUTOTEST ................................................... 118
5.4. MAINTENANCE ................................................................................................... 120
5.5. REMOVING THE INVERTER ............................................................................... 121
6. SPECIFICATIONS .................................................................................................123
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
SUNWAY M XS 3000TL
5/124
0.1. Index of Figures
Figure 1: Block diagram of the SUNWAY M XS ................................................................................................ 9
Figure 2: Packaging of the SUNWAY M XS .................................................................................................... 13
Figure 3: Dataplates of the SUNWAY M XS.................................................................................................... 14
Figure 4: Label placed on the metal enclosure of the product ........................................................................ 16
Figure 5: Procedure for opening the package ................................................................................................. 17
Figure 6: Procedure for removing the SUNWAY M XS from its packing ......................................................... 18
Figure 7: SUNWAY M XS box with packing elements .................................................................................... 18
Figure 8: Minimum clearance (in mm) to respect for proper ventilation of the SUNWAY M XS ..................... 21
Figure 9: Detail of the SUNWAY M XS bracket with the fixing screws ........................................................... 21
Figure 10: The SUNWAY M XS in upright position ......................................................................................... 22
Figure 11: Detail of the SUNWAY M XS with the side handles ....................................................................... 22
Figure 12: Removing the cable cover .............................................................................................................. 23
Figure 13: SUNWAY M XS connectors ........................................................................................................... 24
Figure 14: Fixed element of the grid connector ............................................................................................... 26
Figure 15: Flying connector for the connection to the grid .............................................................................. 26
Figure 16: Mounting the floating connector for the connection to the grid ...................................................... 27
Figure 17: Polarity for string connection to the main PV field and DC-side disconnect switch ....................... 30
Figure 18: Removing the protective film from the touchscreen display ........................................................... 32
Figure 19: Slots for the application of the fiscal seal ....................................................................................... 33
Figure 20: Example of the Start Menu ............................................................................................................. 34
Figure 21: Language setting page ................................................................................................................... 36
Figure 22: Setting the dialogue language ........................................................................................................ 37
Figure 23: Country setting page ...................................................................................................................... 37
Figure 24: Setting the Country ......................................................................................................................... 38
Figure 25: Name of the Country displayed in the start menu .......................................................................... 38
Figure 26: Time zone setting page .................................................................................................................. 39
Figure 27: Setting the time zone ...................................................................................................................... 39
Figure 28: Setting the date .............................................................................................................................. 40
Figure 29: Setting the date .............................................................................................................................. 40
Figure 30: Setting the currency ....................................................................................................................... 41
Figure 31: Setting the currency ....................................................................................................................... 41
Figure 32: Net metering setting page .............................................................................................................. 42
Figure 33: Setting the feed-in tariff .................................................................................................................. 42
Figure 34: History data resetting page ............................................................................................................ 43
Figure 35: History data resetting page ............................................................................................................ 43
Figure 36: Display resetting page .................................................................................................................... 44
Figure 37: Resetting the display ...................................................................................................................... 44
Figure 38: Inserting the Wi-Fi transmitter ........................................................................................................ 45
Figure 39: Activating the Wi-Fi connection ...................................................................................................... 45
Figure 40: Setting the AD HOC connectivity ................................................................................................... 46
Figure 41: Setting the ROUTER connectivity .................................................................................................. 47
Figure 42: Selecting the desired network ........................................................................................................ 47
Figure 43: Setting the network access password ............................................................................................ 47
Figure 44: IP address assignment mode ......................................................................................................... 48
Figure 45: Setting the IP address .................................................................................................................... 48
Figure 46: Setting the subnet mask ................................................................................................................. 48
Figure 47: Setting the gateway ........................................................................................................................ 49
Figure 48: Setting the DNS .............................................................................................................................. 49
Figure 49: Icon of the SUNWAY M XS application on the iPhone .................................................................. 51
Figure 50: Activating the Sunwayportal.it service ............................................................................................ 51
Figure 51: Activating the Technical Support Service ....................................................................................... 52
Figure 52: Checking the Technical Support Service ....................................................................................... 52
Figure 53: Displaying a measure graph ........................................................................................................... 54
Figure 54: Graphic interface module/Touchscreen display Start menu ....................................................... 55
Figure 55: Screens of the graphic interface module at power on .................................................................... 56
Figure 56: Start menu ...................................................................................................................................... 56
Figure 57: Example of a screen ....................................................................................................................... 57
Figure 58: Screen of the Alarms menu ............................................................................................................ 58
Figure 59: Screen of the Wi-Fi Status menu ................................................................................................... 59
SUNWAY M XS 3000TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
6/124
Figure 60: Screen of the inverter Status menu ................................................................................................ 60
Figure 61: Example of a measure graph ......................................................................................................... 61
Figure 62: Example of an alphanumeric keypad window ................................................................................ 62
Figure 63: Example of a list window ................................................................................................................ 63
Figure 64: Example of a Run Command window ............................................................................................ 63
Figure 65: Icons of the Menu Area in the start menu ...................................................................................... 64
Figure 66: Info menu tree ................................................................................................................................ 67
Figure 67: Graph menu.................................................................................................................................... 74
Figure 68: Selection page for the measure to be graphically displayed .......................................................... 74
Figure 69: Steps to take for the customization of the measures to be graphically displayed ......................... 75
Figure 70: Setting page of the Default View .................................................................................................... 75
Figure 71: Setting the Graph menu as the Default View ................................................................................. 76
Figure 72: Connectivity menu tree ................................................................................................................... 76
Figure 73: Tools menu tree ............................................................................................................................. 80
Figure 74: Tools menu, Customization submenu ............................................................................................ 83
Figure 75: Tools menu, Advanced Configuration Submenu ............................................................................ 85
Figure 76: Tools menu, Advanced Configuration > Inverter ............................................................................ 87
Figure 77: Tools menu, Advanced Settings > Grid submenu .......................................................................... 88
Figure 78: Example of an alarm screen ........................................................................................................... 98
Figure 79: ALARM RESET screen ................................................................................................................ 110
Figure 80: Resetting an alarm ....................................................................................................................... 111
Figure 81: Example of a status window ......................................................................................................... 111
Figure 82: Example of a warning ................................................................................................................... 113
Figure 83: Example of the Wi-Fi Status window ............................................................................................ 114
Figure 84: RUN status page .......................................................................................................................... 118
Figure 85: Test page ...................................................................................................................................... 120
Figure 86: Removing the grid connector ....................................................................................................... 121
Figure 87: Pliers to remove the quick-coupling connectors ........................................................................... 121
Figure 88: Removing the quick-coupling connectors .................................................................................... 122
Figure 89: Removing the inverter .................................................................................................................. 122
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
SUNWAY M XS 3000TL
7/124
0.2. Index of Tables
Table 1: Environmental requirements .............................................................................................................. 19
Table 2: Dimensioning of the MCCB and cable specifications ........................................................................ 25
Table 3: Specifications of the PV field ............................................................................................................. 29
Table 4: Logged variables ............................................................................................................................... 54
Table 5: Template of the measure descriptive tables ...................................................................................... 66
Table 6: Template of the parameter descriptive tables ................................................................................... 66
Table 7: Template of the variable descriptive tables ....................................................................................... 66
Table 8: Info menu, Field submenu ................................................................................................................. 68
Table 9: Info menu, Inverter submenu ............................................................................................................. 70
Table 10: Info menu, Grid submenu ................................................................................................................ 72
Table 11: Connectivity menu, Wi-Fi submenu ................................................................................................. 77
Table 12: Connectivity menu, Services submenu ........................................................................................... 79
Table 13: Tools menu, Quick Configuration submenu .................................................................................... 81
Table 14: Tools menu, Customization > Display submenu ............................................................................. 83
Table 15: Tools menu, Customization > Web Page submenu ........................................................................ 84
Table 16: Tools menu, Customization submenu > Access Level .................................................................... 85
Table 17: Tools menu, Advanced Configuration > Field submenu ................................................................. 86
Table 18: Tools menu, Advanced Configuration > Inverter > Advanced Parameters submenu ..................... 87
Table 19: Settings menu, Advanced Configuration > Grid > Grid Interface submenu .................................... 89
Table 20: Tools menu, Advanced Configuration > Grid > Energy submenu ................................................... 94
Table 21: Tools menu, Commands submenu ................................................................................................. 95
Table 22: Alarms Menu.................................................................................................................................... 99
Table 23: Measures in the Alarm History and Event History ........................................................................... 99
Table 24: List of the SUNWAY M XS alarms................................................................................................. 100
Table 25: Status messages for the SUNWAY M XS inverters ...................................................................... 112
Table 26: DB9 connector - RS485 serial port ................................................................................................ 116
Table 27: Specifications of the RS485 serial port ......................................................................................... 117
Table 28: Specifications of RS485 serial port ............................................................................................... 117
Table 29: Protection trip times ....................................................................................................................... 119
Table 30: Trip times ....................................................................................................................................... 119
Table 31: Specifications of the SUNWAY M XS inverters ............................................................................. 123
SUNWAY M XS 3000TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
8/124
1. SCOPE OF THIS MANUAL
Elettronica Santerno is committed to update its User Manuals available for download from santerno.com with
the latest software version officially released. Please contact Elettronica Santerno if you require technical
documents related to previous software versions.
2. GENERAL INFORMATION
2.1. Description of the Product
The inverters of the SUNWAY M XS series are full-digital devices that convert DC energy produced by
photovoltaic (PV) panels when radiated by sunlight into AC energy, which is delivered to the grid.
A solar system for the self-generation of electric power is composed of two elements:
The PV generator, consisting of a set of PV panels.
The SUNWAY M XS inverter, delivering power supply from the PV generator to the grid.
Operation in parallel to the grid allows consumers to exploit the power supply produced directly by the
system when radiated by sunlight, and to deliver power which is not locally consumed to the grid, by
conferring it to the Grid Administrator. Therefore, residual power can be used by other consumers connected
to the grid, thus allowing the exploitation of the green energy produced by the PV generator, as well as the
constant operation of the same PV generator at its max ratings for optimum performance.
At night-time or when sunlight is weak, consumers can exploit the grid to power their loads.
All the parameter values related to the operation of the equipment may be easily programmed through the
touchscreen display and the parameter menus and submenus.
The inverters of the SUNWAY M XS series have been designed and manufactured in compliance with the
requirements of the “Low Voltage Directive” and the “Electromagnetic Compatibility Directive” and comply
with the prescriptions for grid connection applying to self-generation electric plants.
2.2. Benefits
Wide range of supply voltages: 125 to 580 Vdc;
Full-digital DC/AC conversion through 32-bit microprocessor obtained with PWM technique and
IGBT bridge ensuring high efficiency, high reliability and low distortion of the grid current;
Transformerless topology;
Die cast aluminium enclosure for maximum robustness, thermal performance and weight
optimization, suitable for outdoor installation (IP65-rated);
DC disconnect switch ensuring maximum safety when maintaining the inverter (optional);
Input filters and output filters for the suppression of conducted disturbance and radiated disturbance;
Testing circuit to check the isolation resistance between the input and the earth;
Operation in parallel to the grid, power factor = 1;
Fast connection through quick-coupling MC4 connectors for the connection of up to 4 strings;
User interface based on graphic touchscreen display, 240x320 pixels, 262,000 colours for user-
friendly control of the inverter functionality;
RS485 serial link with Modbus protocol for remote monitoring and programming (optional);
Wi-Fi connectivity for the access to LANs and interaction via smartphones;
Remote Technical Support if the inverter is connected to the Internet;
Power supply from the grid in order to maintain operation even in the event of weak solar radiation
from the PV field.
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
SUNWAY M XS 3000TL
9/124
2.3. Operating Principle
The power conversion system (inverter) is connected directly to the PV field. By using an IGBT bridge
associated with a high-frequency voltage booster, the DC current coming from the PV field is converted into
AC at the grid frequency. The transformerless architecture ensures maximum efficiency without affecting
safety: the residual current device (RCD) is integrated into the inverter and the redundant grid connecting
devices ensure proper safety even in the event of single fault.
The EMC filters for the suppression of electromagnetic disturbance, the isolation sensor monitoring the
isolation to earth of the PV panels as well as the device controlling the operation in parallel to the grid are
integrated into the inverter. Therefore, no additional device external to the inverter is required.
Figure 1: Block diagram of the SUNWAY M XS
2.4. Main Standard Integrated Functions
This section contains a brief description of the equipment functions, to allow users who are not familiar with
the operation of PV fields to better understand this manual.
Device for constant isolation control: this is a device which checks the isolation between the earth and
the polarities of the PV field and the earth before the inverter is connected in parallel to the grid. This function
is obtained by measuring the isolation resistance: the equipment is factory-set to detect isolation loss when
the isolation resistance between polarity + or polarity and the earth drops below 850 kΩ.
MPPT (Maximum Power Point Tracking): A sophisticated computing performed by the microprocessor
allows the inverter to detect the optimum operation point of the PV field, corresponding to the maximum
power that can be produced by the PV field depending on current solar radiation conditions.
Not fitted in the Sunway MXS 2200 TL
SUNWAY M XS 3000TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
10/124
Automatic Disconnecting Means: This device automatically disconnects the self-generation plant from the
grid when parallel operation is no longer possible. This typically occurs when the grid “opensdue to
maintenance needs or to safety circuit tripping. This function allows the inverter to instantly disconnect from
the grid, thus avoiding unwanted stand-alone operation of the plant and electric shock hazards for the
operators working on the grid. Trip times and levels are factory-set according to the applicable safety
standards. To modify the factory settings, please refer to the sections relating to the inverter programming.
The ratings of this safety function have been certified as prescribed by the Grid Administrator.
When required by the Grid Administrator, a simple self-test procedure performed via the touchscreen display
allows checking the efficiency of the grid disconnection device.
2.5. Attached Documentation
The SUNWAY M XS inverter is supplied complete with the following documents:
Multilingual “Quick Start Guide”, included as a hard copy and available for download from
santerno.com;
“Wi-Fi Connection Quick Start Guide”, included as a hard copy and available for download from
santerno.com;
Multilingual “Certification and Grid Interface File”, available for download from santerno.com;
“User Manual” (this document) available for download from santerno.com.
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
SUNWAY M XS 3000TL
11/124
3. BASIC INSTALLATION
The basic installation consists in connecting the basic elements for the system operation (grid and PV
generator).
Advanced configurations of the SUNWAY M XS inverter are covered in section 4. Fully read the basic
installation instructions before carrying out the advanced configurations.
3.1. Caution Statements
This section covers safety statements. The non-observance of the safety instructions below may cause
serious injury or death and equipment failure. Carefully read the instructions below before installing, starting
and operating the inverter.
Only competent personnel must carry out the equipment installation.
KEY TO SYMBOLS:
DANGER Indicates operating procedures that, if not correctly performed, may cause
serious injury or death due to electric shock.
CAUTION Indicates operating procedures that, if not respected, may cause serious
equipment failure.
NOTE Indicates important information concerning the operation of the equipment.
SAFETY STATEMENTS TO FOLLOW WHEN INSTALLING AND OPERATING THE EQUIPMENT:
NOTE
Always read this instruction manual thoroughly before starting the
equipment.
DANGER Always earth the equipment.
CAUTION The SUNWAY M XS must be powered by a photovoltaic field only, and
must be used exclusively for operation in parallel with the grid. Any other
use is to be considered as improper.
SUNWAY M XS 3000TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
12/124
DANGER
CONNECTION TO THE PV FIELD When exposed to solar
radiation,
the photovoltaic panels produce DC voltage that is applied to the
inverter.
ELECTRIC SHOCK HAZARD
Do not touch the electric parts of the
inverter and do not operate on the inverter when it is powered. Always wait
at least 15
minutes from the instant when the DC and AC supply is
removed from the
inverter before carrying out any operation, because
electric energy is accumulated inside the inverter.
Do not operate on the equipment when it is powered.
Before operating on the electric connections, remove both DC and AC
voltage from the equipment and wait at least 15 minutes.
EXPLOSION AND FIRE The risk of explosion and fire may exist if the
equipment is installed in presence of flammable fumes. Do not install the
equipment where there is a risk of explosion and fire.
CAUTION
Do not connect supply voltages which exceed the rated voltage. If voltage
exceeding the rated value is applied, the internal circuits may be damaged.
In
the event of installation in presence of flammable and/or explosive
substances, please consult the relevant applicable standards.
In the event of an alarm, consult section 4.3.6 Alarms Menu.
Only restart
the equipment after the problem has been rectified.
Do not carry out isolation tests between the power terminals or between the
control terminals.
Make sure that the screws on the connection terminal boards have been
properly tightened.
Observe the environmental requirements for installation.
Do not open the inverter to avoid affecting the IP rating and/or damaging
the internal circuits.
CAUTION Certain parts of the product (side walls, heatsink and reactors) may reach
temperatures as high as 100 °C. Take all the necessary precautions to
avoid burns.
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
SUNWAY M XS 3000TL
13/124
3.2. Checking the Product on Delivery
On receiving delivery of the equipment, make sure that the packaging shows no signs of damage. Check that
it complies with your order by referring to the dataplates described below. In the event of any damage,
please contact the relative insurance company or the supplier. If the delivery does not match your order,
contact the supplier immediately.
Figure 2: Packaging of the SUNWAY M XS
If the equipment is to be stored before installation, make sure that the ambient conditions in the warehouse
meet the necessary specifications (see section 3.4.1). The warranty covers manufacturing defects. The
manufacturer shall not be held liable for any damage which may have occurred during transport and
unpacking. Under no circumstances shall the manufacturer be held liable for damage or faults cause by
incorrect use, misuse, incorrect installation or inadequate temperature or humidity conditions or exposure to
corrosives, nor for faults caused by operation outside the rated values. Nor shall the manufacturer be held
liable for consequential or accidental damage.
NOTE For the terms of warranty, please refer to the warranty certificate supplied
with the product.
SUNWAY M XS 3000TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
14/124
3.2.1. Dataplate
The product is described and identified by two dataplates placed on its side, as shown in Figure 3.
Figure 3: Dataplates of the SUNWAY M XS
The dataplate measures 60mm x 30mm.
The product code is made up of the following elements:
SUNWAY M XS 3000 TL
1 2 3 4 5
1 Product line:
2
3 Product family:
4 Model (identifies the rated power injected into the grid)
5
TL = transformerless
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
SUNWAY M XS 3000TL
15/124
Purchase code of the product:
ZZ01770 PP D A C U W X Y Z
1 2 3 4 5 6 7 8 9 10 11
1
ZZ01770 for the SUNWAY M XS series
2
Size (two figures):
22 = 2200 (2200 W rated power for 230 V grid)
30 = 3000 (3000 W rated power for 230 V grid)
38 = 3800 (3800 W rated power for 230 V grid)
3 Blank field
4
0 = Not fitted
5
6
0 = Carmine Red (RAL 3002)
1 = Night Blue (RAL 5022)
2 = Traffic Black (RAL 9017)
7 UL certification:
0 = Non UL-certified version
1 = UL-certified version (unavailable at the moment)
8 RS485 Option
2 = Not fitted
3 = Fitted
9 Unused field:
10
11 Unused field:
SUNWAY M XS 3000TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
16/124
Figure 4: Label placed on the metal enclosure of the product
The basic configuration of the SUNWAY M XS inverter comprises the following:
N. 1 SUNWAY M XS inverter
N. 1 Wall-mounting bracket
N.1 PV field connectors kit
N.1 Grid connector
N.1 Wi-Fi connector with adapter
N. 1 Quick start Guide
N. 1 Authentication form
N. 1 Warranty certificate
The following options are available for the SUNWAY M XS:
Available options Component Configuration
RS485 Port RS485 connector mounted on the upper cover of
the inverter Integrated into the
product
DC Disconnect switch Integrated disconnect switch for the disconnection
of the photovoltaic field from the inverter Integrated into the
product
NOTE Before commissioning the SUNWAY M XS, make sure that all the options
required are fitted. Contact the Customer Service of Elettronica Santerno
SpA for any clarifications.
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
SUNWAY M XS 3000TL
17/124
3.3. Transport and Handling
State-of-the-art packing is provided when shipping the SUNWAY M XS. Handling should be done using a
transpallet or a lift truck with a carrying capacity of at least 50 kg, in order not to damage the product.
Get near the installation place, then unpack following the instructions provided below.
CAUTION
The whole original packing is to be kept for the full duration of the
warranty period.
CAUTION
Based on the configuration of the product, the content of the packing may
have a maximum weight of 21.6 kg. The centre of gravity of the SUNWAY M
PLUS does not match with the geometrical centre of the packing. It is
therefore recommended that the packing be handled with extreme care by
at least two persons. Always use proper handling equipment.
1. Unpacking the product:
Cut with pincers the plastic straps that fix the package of the SUNWAY M XS to the pallet;
Cut with a cutter the adhesive tape closing the box.
Figure 5: Procedure for opening the package
SUNWAY M XS 3000TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
18/124
2. Remove the SUNWAY M XS from its packing by lifting it from its sides. To avoid damaging the
packing, lift the product keeping it horizontal to the floor (see Figure 6).
Figure 6: Procedure for removing the SUNWAY M XS from its packing
3. Put all the packing elements in the box and store it in a dry place (see Figure 7).
Figure 7: SUNWAY M XS box with packing elements
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
SUNWAY M XS 3000TL
19/124
3.4. Installation
NOTE Do not remove the inverter lid during installation. Removing the lid may
affect the IP rating of the inverter and may damage the internal parts.
Removing the lid voids the inverter warranty.
3.4.1. Environmental Requirements for the Equipment Storage, Installation
and Operation
SUNWAY M XS Model 2200TL 3000TL 3800TL
IP Rating (*) IP65 IP65 IP65 (*)
Mechanical dimensions (mm) 380 x 570 x 218
Weight (kg) 17.5 20.8 21.6
Operating ambient
temperature -25 °C ÷ +60 °C
Rated operating temperature
(**) -25 °C ÷ +45 °C
Ambient temperature for
storage and transport
-25 °C ÷ +70 °C
Maximum number of packed
SUNWAY M XS that can be
stacked up
3
Installation site
Outdoor installation, degree of pollution 3 or better.
Do not install the equipment where it is exposed to direct sunlight or where
it is exposed to conductive dust, corrosive gases, vibrations. Do not install
in salty environments.
Altitude
Up to 2000m a.s.l.
For altitudes ranging from 2000m to 3000m a.s.l., derate the output current
by 1% every 100m. For higher altitudes, please contact Elettronica
Santerno.
Operating ambient humidity 0 % to 100 %, 1 g/m
3
to 25 g/m
3
, non-condensing and non-freezing (class
3k3 according to EN 50178).
Storage ambient humidity 0 % to 100 %, 1 g/m
3
to 25 g/m
3
, non-condensing and non-freezing (class
1k3 according to EN 50178).
Ambient humidity during
transport Max. 100%. Up to 60g/m
3
, condensation may appear when the equipment
is not running (class 2k3 according to EN 50178).
Operating and storage
atmospheric pressure
86 kPa to 106 kPa (class 3k3 and 1k4 according to EN 50178).
Atmospheric pressure during
transport
70 kPa to 106 kPa (class 2k3 according to EN 50178).
Table 1: Environmental requirements
* The external fans are IP54 rated.
** Beyond 45 °C, the SUNWAY M XS automatically decreases the output power in order to avoid
overheating. See the product specifications.
CAUTION Environmental conditions significantly affect the life-
expectancy of the
product. Consequently, DO NOT install the product in a location which does
not meet the required specifications.
SUNWAY M XS 3000TL
INSTALLATION AND
PROGRAMMING INSTRUCTIONS
20/124
3.4.2. Wall Mounting
The SUNWAY M XS is provided with a bracket that can be used for wall mounting. The inverter is to be
installed in upright position. Make sure that the wall can withstand the weight of the product.
CAUTION
Do not install the SUNWAY M XS in direct sunlight or above heat
sources.
NOTE The installation place for the SUNWAY M XS is to be chosen on
the basis
of its degree of protection. It is recommended that the SUNWAY M XS be
not installed in environments directly exposed to water jets.
NOTE It is recommended that the SUNWAY M XS be installed in a place sheltered
from rain and snow.
CAUTION Based on the configuration of the product, the content of the packing may
weigh up to 21.6 kg
(see the product specifications). Make sure that
adequate handling measures are taken.
CAUTION
The protective cover of the connector unit is made of plastic and cannot
withstand mechanical stress. Avoid using it as a grip point during
installation.
CAUTION
Make sure that the surface where the inverter is to be installed on is
perfectly flat and is not tilted.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124

Santerno SUNWAY M XS 3800TL User manual

Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI