Dwyer Series VPS User manual

Type
User manual
Series VPS Valve Position Sensor
Specications - Installation and Operating Instructions
Bulletin F-65
The dual inductive, 2-wire AC/DC Series VPS Valve Position Sensor maintains VDI/
VDE 3845 dimensions so positioners can be easily mounted on top of the sensor and
target. The Model VPS2411 Sensor and Model P1 Target mount easily and directly to
actuators with ISO-NAMUR topworks (see picture below). Fully adjustable target in
2° increments, the sensor has two independent LED’s and bright Flow Line indicator
that provide local visual indication. All electrical connections are made with the Model
VIP82 4-pin quick disconnect cable (6 ft. in length) for ease in installation. Solid state
components are fully embedded in an epoxy resin to prevent condensation build-
up and to protect against vibration and shock. The rugged PBTP housing provides
excellent corrosion resistance and moisture protection.
Two VPS2411 and one P1 shown mounted with W.E. Anderson pneumatic actuator
and positioner.
SPECIFICATIONS
Power Requirements: 20-140 VAC (50/60 Hz) 10-200 VDC.
Output Operation: Dual normally open.
Load Current: ≤200 mA.
Minimum Load Current: 5 mA.
Leakage Current: ≤0.8 mA.
Voltage Drop: ≤5.0 V.
Repeatability: ≤0.01 mm.
Hysteresis: 3-15% of sensing range.
Switching Frequency: 25 Hz.
Temperature Limits: -13°F to 176°F (-25°C to 80°C).
Housing Material: Polybutylene Terephthalate (PBTP).
Electrical Connection: M12 4-Pin Quick Disconnect (Order Model VIP82 for 6’
Long Mating Cable).
Mounting Holes: NAMUR Mounting 3.15˝ x 1.18˝ (80 x 30mm) or 5.12 x 1.18 (130
x 30mm).
Models: Model VPS2411 - Valve Position Sensor, Model P1 - Valve Position Target,
VIP82 - Quick Disconnect Cable, 6 ft. long.
1-5/8
[42.85]
3/8
[7.95]
1
[26.21]
1/4
[6.35]
1-1/2
[39.67]
3/4
[19.84]
1/2
[12.70]
1-1/8
[29.97]
1-1/8
[28.58]
3/4
[20.62]
M12 x 1 THD, 4-PIN
QUICK DISCONNECT
Ø.218 [Ø5.54] (2) PL
Ø2-3/8
[60.33]
1-7/8
[47.73]
VPS2411 VPS2411P1 P1
PROXIMITY CONTROLS
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com
A DIVISION OF
DWYER INSTRUMENTS, INC.
By Dwyer
Printed in U.S.A. 2/19 FR# 443220-00 Rev. 1©Copyright 2019 Dwyer Instruments, Inc.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com
(+)
MODEL VPS2411
(-)
1 BROWN
4 BLACK
2 WHITE
3 BLUE
SW1
GRN LED
SW2
RED LED
PIN 4 BLACK
PIN 1 BROWN
PIN 3 BLUE
PIN 2 WHITE
HOUSING CONNECTOR
NOTE:
1. WIRE COLORS ARE FOR VIP82 QUICK DISCONNECT CABLE
LOAD
LOAD
NAMUR C BRACKET
COUPLING
COLLAR
NAMUR ACTUATOR DIMENSIONS
NAMUR A HOLE PATTERN 30mm X 80mm, SHAFT HEIGHT 20mm
NAMUR B HOLE PATTERN 30mm X 80mm, SHAFT HEIGHT 30mm
NAMUR C HOLE PATTERN 30mm X 130mm, SHAFT HEIGHT 30mm
TARGET RINGS
COVER
FLOW INDICATOR
MODEL
No. VPS
MODEL No. P1
INSTALLATION DRAWING
INSTALLATION PROCEDURE:
1. Fasten the Series VPS to the actuator with the appropriate fasteners (M5, 10-
24, 10-32). For Namur C actuators you must rst attach the Namur C bracket to the
actuator.
2. Attach the coupling to the actuator shaft for Namur A &C actuators only.
3. Attach the collar to the actuator shaft or coupling.
4. Install one stainless steel at head screw (two if it is a dual sensor installation) into
each of the target rings and plug the other holes with the plastic screws or plugs.
Slide the target rings over the collar and adjust as appropriate for open and closed
position. Note: Bottom target energizes the red LED and the top target energizes
the green LED.
5. Place the cover onto the top target being careful to align for proper ow indication
and secure with M6 x 16 fastener for Namur B actuators or M6 x 25 fastener for
Namur A & C actuators.
6. Insert ow indicator to complete assembly or install coupling to maintain VDI/VDE
3845 dimensions if accessories such as a positioner are to be installed.
WIRING DIAGRAM
MAINTENANCE
The unit requires no routine maintenance or lubrication. The unit is not repairable.
This symbol indicates waste electrical products should not be disposed
of with household waste. Please recycle where facilities exist. Check with
your Local Authority or retailer for recycling advice.
  • Page 1 1
  • Page 2 2

Dwyer Series VPS User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI