Autonics TZN Series Dual Speed PID Temperature Controllers User manual

Type
User manual
-|Transparent Guide|-
Follow instructions in ‘Cautions during Use’. Otherwise, it may cause unexpected
accidents.
Check the polarity of the terminals before wiring the temperature sensor. For RTD
temperature sensor, wire it as 3-wire type, using cables in same thickness and length.
For thermocouple (TC) temperature sensor, use the designated compensation wire for
extending wire.
Keep away from high voltage lines or power lines to prevent inductive noise. In case
󸠱
and shielded wire at input signal line. Do not use near the equipment which generates
strong magnetic force or high frequency noise.
Install a power switch or circuit breaker in the easily accessible place for supplying or
disconnecting the power.
Dual-Speed PID Temperature Controllers
TZ / TZN Series
INSTRUCTION MANUAL
TCD210237AB
Thank you for choosing our Autonics product.
Read and understand the instruction manual and manual thoroughly before
using the product.
For your safety, read and follow the below safety considerations before using.
For your safety, read and follow the considerations written in the instruction
manual, other manuals and Autonics website.
󸠱
󸠱
improvement Some models may be discontinued without notice.
Follow Autonics website for the latest information.
Safety Considerations
Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.
dicates caution due to special circumstances in which hazards may occur.
 
01. Fail-safe device must be installed when using the unit with machinery that
may cause serious injury or substantial economic loss.(e.g. nuclear power
control, medical equipment, ships, vehicles, railways, aircraft, combustion
apparatus, safety equipment, crime/disaster prevention devices, etc.)
󸠱
02. 󸠳
high humidity, direct sunlight, radiant heat, vibration, impact or salinity
may be present.
󸠱
03. Install on a device panel to use.
Failure to follow this instruction may result in electric shock.
04. Do not connect, repair, or inspect the unit while connected to a power
source.
󸠱
05. Check ‘Connections’ before wiring.
󸠱
06. Do not disassemble or modify the unit.
󸠱
 
01. 2)
cable or over, and tighten the terminal screw with a tightening torque of 0.74
to 0.90 N m.


a tightening torque of 0.74 to 0.90 N m..
󸠱
failure.
02. 󸠲
󸠱
03. Use a dry cloth to clean the unit, and do not use water or organic solvent.
󸠱
04. 󸠳
into the unit.
󸠱
Cautions during Use
Product Components
󹌍 󹌓󹌍󹌍󹌍
󹌚󹌓󹌍󹌓󹌍󹌛󹌍󹌍󹌑󹌍󹌒
󹌍 󹌍
󹌍 󹌍
Manual
For proper use of the product, refer to the manuals and be sure to follow the safety
considerations in the manuals.
Download the manuals from the Autonics website.
Software
󸠱
DAQMaster
󹌍󹌍󹌍󹌍󹌍󹌕󹌍󹌍󹌍󹌍󹌍
󹌍󹌓󹌍󹌕
Sold Separately
11 pin socket: PG-11, PS-11 (N) Communication converter: SCM Series
Do not use the unit for other purpose (e.g. voltmeter, ammeter), but temperature
controller.
󸠰󸠱
the input sensor, modify the value of the corresponding parameter.
Do not overlapping communication line and power line. Use twisted pair wire for
󸠰
external noise.
Make a required space around the unit for radiation of heat. For accurate temperature


supplying power.
Do not wire to terminals which are not used.
This unit may be used in the following environments.
󸠱


- Installation category II
Ordering Information
This is only for reference, the actual product does not support all combinations.
󸠱

 
R: Relay output
S: SSR drive output
C: Current Output
S: 
SP: Series)
ST: Series)
M: 
 
W: 
L: 
Option output
PN Option output 1 Option output 2
1Event -
2Event Event
REvent PV Transmission
TEvent Communication
AEvent 
BEvent 
Comm. protocol BCC
Application standard 
 31 units (address
Synchronous method Asynchronous
Comm. method Two-wire half duplex
󸠱 
Comm. speed 
Start bit 󸠱
Data bit 󸠱
Parity bit None
Stop bit 󸠱
EEPROM life cycle 
Communication Interface

󸠲
Series TZ/TZN Series
Power supply 
Power consumption 
Sampling period 
󸠲 󹌍󹌍'Input Type and Using Range'.
Display accuracy 
Control
output
Relay 
SSR 
Current 
Option
output
 
PV
Transmission 
Comm. 
Display type 7 Segment (red, green), LED type
Control type 
Alarm output
Hysteresis 
Proportional band (P) 
Integral time (I) sec
Derivative time (D) sec
Control cycle (T) sec
LBA setting 
RAMP setting 
Relay
life
cycle
Mechanical 

Electrical




Dielectric strength 
for 1 min
Vibration 

Malfunction vibration 

Insulation resistance 
Noise immunity )
R-phase, S-phase
Memory retention 
Ambient temperature 
Ambient humidity 
Approval 
Unit weight
(packaged)
 
 
 
 
 

Input Type Setting
󹌍󸠱󹌍󹌍󹌍󹌍󹌍󹌍󹌕󹌍
󹌍󹌍󹌓󹌍󸠱󹌍󹌍󹌐󹌍󹌐󹌍󹌍󹌍󹌕
Detaching the case
Input type  
Thermocouple
1 1 mA V
RTD
Analog
Voltage

   mA V
Current
   mA V
Press the front case then pull the case to
detach the case from the body.
󸠱
type.
Unit Descriptions
TZ Series TZN Series
4
5
1
2
3
4
1
2
3
1. PV Display part (red)
RUN mode: 󹌍PV (present value)
• Setting mode: 󹌍parameter name
2. SV Display part (green)
RUN mode: 󹌍SV (setting value)
• Setting mode: 󹌍parameter setting value
3. Indicator 4. Control key
5. Key adjustment order chart
Display Name Description
  
AT Auto tuning Flash during auto tuning
OUT Control output
operation
Turns ON when the control
output is ON.
Not operate when control
output is current output
EV1 Event 1 output 
Output 󹌍
 
Display Name
[MD] Mode key
[AT] Auto tuning execution key


Setting value control key



Input Type and Using Range
The setting range of some parameters is limited when using the decimal point display.
Input type Decimal point Display Using  Using 
Thermo-
couple
K (CA) 1KCaH  to   to 
K (CA)  KCaL  to  -
J (IC) 1JIcH to   to 
J (IC)  JIcL  to  -
R (PR) 1R PR to   to 
E (CR) 1ECrH to   to 
E (CR)  ECrL  to  -
T (CC) 1TCcH  to   to 
T (CC)  TCcL  to  -
S (PR) 1S PR to   to 
N (NN) 1 NN to   to 
W (TT) 1U TT to   to 
RTD
 1JPtH to   to 
  JPtL  to   to 
 1DPtH to   to 
  DPtL  to   to 
Analog Voltage - A--1 
(Display range will vary depending on
the decimal point.)
1 -  A--2
Current  - A--3
󹌓󹌍󹌔󹌍󹌔󹌓󹌍󹌔󹌓󹌍󹌓󹌍󹌍󹌍󹌓󹌍
󹌗󹌗󹌖󹌖󹌖󹌗
-|Transparent Guide|-
Display Description Troubleshooting
OPEN 
sensor is break or disconnected. Check input sensor status.
HHHH Flashes when PV is higher than input
range. When input is within the rated input range,
this display disappears.
LLLL Flashes when PV is lower than input
range.
ERR0 Flashes when 󹌍󹌍󹌍󹌍
󹌍󹌍 (󸢔
󹌍󹌍󹌍󹌍󹌍󹌍󹌍󹌍
󹌕
󹌍󹌍󹌍󹌍.
-󹌍󹌍󹌍󹌍󹌍󹌍󹌍
If the control output indicator is not
working, check parameter settings.
If the control output indicator is working,
disconnect the wiring from the output
terminal of the temperature controller and
check the output (replay contact, SSR drive,
current)
Errors
Bracket
TZ4ST, TZ4SP, TZN4S Series TZ4L, TZN4L, TZ4M, TZ4H,

󹌕
󹌕
󹌕

73



TZN4M Series





Dimensions
Unit: mm, For the detailed drawings, follow the Autonics website.

D
C E
F
A
B
Panel cut-out
I
H
J
Body Panel 󹌖
A B C D E F H I J
TZ4SP   11.1      

TZ4ST   11.1      

TZN4S    -    

TZ4M         

TZN4M    -    

    13     

   13 -    

TZ4H    13     

TZN4H   13 -    

TZ4L    13     

TZN4L   13 -    

Connections
TZ4SP
EV1 OUT

1A 1a


MAIN OUT


Resistive load
SOURCE


C
L
-
B'
RTD
TC
SENSOR
B
A
-
5
2
10
9
1
11
4
3
7
6
MAIN OUT
SSR Current
-
9
10
V

-
9
10
mA


TZ4ST
EV1 OUT




MAIN OUT


Resistive load


SOURCE

C
L
-
-
B'
RTD
TC
SENSOR
B
A
-
1
2
3
4
10
11
12
13
14
5
6
7
9
MAIN OUT
SSR Current
-
12
13 V

-
12
13
mA


TZN4S
SOURCE


EV1 OUT

1A 1a



MAIN OUT


Resistive load
B'
RTD
TC
SENSOR
B
A
C
L
-
-
MAIN OUT
SSR Current
-
V
3
2


-
3
2
mA


TZ4M



MAIN OUT


Resistive load
B'
RTD
TC
SENSOR
B
A
-
C
L
-


-
PV OUT

SOURCE


EV1 OUT

1A 1a


1A 1a
6
5
4
3
2
1
14 15 16
13
12
11
10
9
7
MAIN OUT
SSR Current
-
13
12 V

-
mA
13
12


TZN4M
EV1 OUT






MAIN OUT


Resistive load
PV OUT

SOURCE




C
L
-
-
B'
RTD
TC
SENSOR
B
A
-
MAIN OUT
SSR Current
-
V
7
6


-
7
6
mA


󸠲
Unit: mm, Use the crimp terminal of follow shape.




Fork crimp terminal Round crimp terminal

SOURCE


EV1 OUT

1A 1a


1A 1a

Max.


MAIN OUT


Resistive load
B'
RTD
TC SENSOR
B A
-
C
L
-
17 16 15 14 13 12 11 10 9
7654321

-

 
(B-)
MAIN OUT
SSR Current
V
-
15
14


mA
-
15
14


TZ4H/TZN4H
SOURCE


EV1 OUT






MAIN OUT


Resistive load
B'
TC
RTD
SENSOR
B
A
CL
-
7
6
5
4
3
2
1
17
16
15
14
13
12
11
10
9
-


-
PV OUT

MAIN OUT
SSR Current
V
-
15
14


mA
-
15
14


TZ4L/TZN4L
EV1 OUT






MAIN OUT


Resistive load
B'
TC
RTD
SENSOR
B
A
-
CL
-
7
6
5
4
3
2
1
17
16
15
14
13
12
11
10
9
SOURCE




-
PV OUT

MAIN OUT
SSR Current
V
-
15
14


mA
-
15
14


Mode Setting
RUN
 SV setting


Save: [MD]
RUN
[MD] over 3 sec Parameter 1
group [MD] over 3 sec
 Parameter 2
group
[AT] 3 sec Auto tuning 
Parameter 2 group
Parameter Display Default Setting range Condition
 Input spec. IN-T KCaH Refer to 'Input Type and Using Range'. -
 Event 1 EU-1 AL-1
󸠰
AL-1: Deviation high limit alarm

AL-3: Deviation high, low limit alarm
󹌍alarm


SBA: Sensor break alarm
LBA: Loop break alarm (LBA)
-
 Event EU-2 AL-2 

 Alarm option AL-T AL-A
AL-A: Standard alarm
AL-B: Alarm latch
AL-C: Standby sequence
AL-D: Alarm latch and standby
sequence
Event

 Auto tuning
mode AtT TVN1 TUN1: Tuning based on SV
󹌍 -
 PID type PIDT PIdS PID.S: 󹌍󹌍
PID.F: 󹌍󹌍 -
 Control output
mode O-FT HEAT

Please set according to control
application. Do not change the
settings during operation. It may result
󸠱
-
 Temperature
unit UNIT ?C  -
 SV high limit H-SC 1300 Within input range
Refer to 'Input Type and Using Range'.
-
 SV low limit L-SC `00 -
 Decimal point DOT 0

spec. :
Analog

Transmission
output high
limit
FS-H 1300 
Within input range
Refer to 'Input Type and Using Range'.
-

Transmission
output low
limit
FS-L `00
 RAMP function RAMP OFF OFF, ON -
 Comm. speed BPS 2400 
 -
 Comm.
address ADRS 01 
 -
 Lock LOC
OFF
 -
Parameter Display Default Setting range Condition
1-1  SU-2 0Refer to 'Input Type and Using Range'. -
 Event 1 alarm
temperature AL1 10 Refer to 'Input Type and Using Range'. Event

1-3 Event
temperature AL2 10 
Refer to 'Input Type and Using Range'.
 LBA time LBA 600 [Relay, SSR drive output model]

Event

 Alarm output
hysteresis AHYS 2 Event

 Proportional
band P#0  -
1-7 Integral time I 0 

Proportional
band: 󸢔
 Derivative time D 0 
 Control cycle T20
[Relay, SSR drive output model]

Set to a small value in SSR drive

  HYS 2

Proportional

1-11 Input
correction IN-B 0 -
 Manual reset REST )0 

Proportional
band: 󸢔

Integral
derivative

1-13 RAMP up time RAPU 10  
function: ON

RAMP 󹌍time
RAPD 10
 Lock LOC OFF
OFF
ON: Parameter 1 group lock
lock
-

other parameters. Refer to the descriptions of each item.





seconds.
The range in parentheses '( )' is the setting range when the set value of the 'input
󸠱


Parameter 1 group