Vantage Technologies AF/SF, GB/GD, & SB/SD Series NPT Mount Receptacles Installation guide

Type
Installation guide
M-608-EC, 03/17 Page 1 of 4
EN, FR, DU
Vantage Technology
NPT Mount Receptacles
AF/SF, GB/SB and GD/SD Series
ASSEMBLY, TERMINATION and USAGE INSTRUCTIONS
Identification of Principal Parts
Assembly Notes
1. In the event of breaking of sealing compound, receptacle must be returned to factory for
resealing. Otherwise, all manufacturing and third party certifications are void.
2. NPT Receptacles come with three set screws to lock receptacle in place.
3. Check dimension table below for the NPT thread size of your receptacle.
4. When conditions require, lubricate coupling threads with silicone oil, Vantage Part Number
VT-9400-21D.
5. Use the receptacle cover mounting tab to prevent cover from being lost while receptacle is
in use. Caution: To prevent shock hazard the receptacle cover must be threaded onto
receptacle when receptacle is not in use. Attention: Pour empêcher le risque de choc,
remplacez la couverture de réceptacle quand pas en service. Aandacht: Om
elektroschokgevaar te verhinderen, vervang vergaarbakdekking wanneer niet in gebruik.
6. Use non conductive lubricant when assembling back shell hardware.
2
4G
1
3
MOUNTING TAB
AF / SF
Control Series
FACTORY SEALED
FACTORY SEALED
GB / SB and GD /SD
Power Series
COUPLING THREADS
THREADED
ENVIRONMENTAL
COVER
SET SCREW FOR LOCKING RECEPTACLE IN PLACE,
THREE SCREWS PER RECEPTACLE
NPT THREADS
SEE DIMENSION TABLE BELOW FOR SIZES
M-608-EC, 03/17 Page 2 of 4
EN, FR, DU
2
4G
1
3
HAZARDOUS LOCATIONS
1
CSA 600V / UL 480V
CATALOG NUMBER
LISTED
643A
AMPS
ATEX
FOR USE WITH PLUG
2
60/400 Hz
MFG CODE
3
4
2
CLASS I, DIV. 2, GROUPS C&D
CUS
CSA ALSO CLASS II, DIV. 2, GROUPS F&G
FACTORY SEALED RECEPTACLE ASSEMBLY
0575
II
2 G D
EEx d IIC T6 IP67 T70°C
0°C = Ta = +50°C
KEMA 04ATEX2179 X
Ex d IIC, T6
Class I Zone 1
AEx d IIC, T6
VANTAGE TECHNOLOGY
ENGLEWOOD, COLORADO 80110, USA
CAUTION: TO PREVENT SHOCK HAZARD THE RECEPTACLE COVER
MUST BE REPLACED UP ON REMOVING PLUG FROM RECEPTACL E
DO NOT SEPARATE WHEN ENERGIZED
NE PAS OUVRIR SOUS TENSION
AMPS
UL-CSA
3
HAZARDOUS LOCATIONS
5
CSA 600V / UL 480V
CATALOG NUMBER
LISTED
643A
AMPS
ATEX
FOR USE WITH PLUG
1
60/400 Hz
MFG CODE
3
6
4
CLASS I, DIV. 2, GROUPS C&D
CUS
CSA ALSO CLASS II, DIV. 2, GROUPS F&G
FACTORY SEALED RECEPTACLE ASSEMBLY
0575
II
2 G D
EEx d IIC T6 IP67 T70°C
0°C = Ta = +50°C
KEMA 04ATEX2179 X
Ex d IIC, T6
Class I Zone 1
AEx d IIC, T6
VANTAGE TECHNOLOGY
ENGLEWOOD, COLORADO 80110, USA
CAUTION: TO PREVENT SHOCK HAZARD THE RECEPTACLE COVER
MUST BE REPLACED UPON REMOVING PLUG FROM RECEPTACLE
DO NOT SEPARATE WHEN ENERGIZED
NE PAS OUVRIR SOUS TENSION
AMPS
UL-CSA 2
RECAPITULATION
OF EQUIPMENT MARKINGS
GB/SB AND GD/SD POWER SERIES
RECAPITULATION
OF EQUIPMENT MARKINGS
AF/SF CONTROL SERIES
HAZARDOUS LOCATIONS
5
600 VAC
60/400 Hz
CATALOG NUMBER
AMPS
ATEX
FOR USE WITH PLUG
1
MFG CODE
3
6
4
CLASS I, DIV. 2, GROUPS C&D
CUS
CSA ALSO CLASS II, DIV. 2, GROUPS F&G
FACTORY SEALED RECEPTACLE ASSEMBLY
0575
II
2 G D
EEx d IIC T6 IP67 T70°C
0°C = Ta = +50°C
KEMA 04ATEX2179 X
Ex d IIC, T6
Class I Zone 1
AEx d IIC, T6
VANTAGE TECHNOLOGY
ENGLEWOOD, COLORADO 80110, USA
CAUTION: TO PREVENT SHOCK HAZARD THE RECEPTACLE COVER
MUST BE REPLACED UPON REMOVING PLUG FROM RECEPTACLE
DO NOT SEPARATE WHEN ENERGIZED
NE PAS OUVRIR SOUS TENSION
AMPS
CSA
2
HAZARDOUS LOCATIONS
1
600 VAC
60/400 Hz
CATALOG NUMBER
AMPS
ATEX
FOR USE WITH PLUG
2
MFG CODE
3
4
2
CLASS I, DIV. 2, GROUPS C&D
CUS
CSA ALSO CLASS II, DIV. 2, GROUPS F&G
FACTORY SEALED RECEPTACLE ASSEMBLY
0575
II
2 G D
EEx d IIC T6 IP67 T70°C
0°C = Ta = +50°C
KEMA 04ATEX2179 X
Ex d IIC, T6
Class I Zone 1
AEx d IIC, T6
VANTAGE TECHNOLOGY
ENGLEWOOD, COLORADO 80110, USA
CAUTION: TO PREVENT SHOCK HAZARD THE RECEPTACLE COVER
MUST BE REPLACED UPON REMOVING PLUG FROM RECEPTACLE
DO NOT SEPARATE WHEN ENERGIZED
NE PAS OUVRIR SOUS TENSION
AMPS
CSA
3
Reference Product Data Sheets for the nameplate data of your NPT receptacle.
Control Series: PDF-AF-SF-NPT
Power Series: PDF-GD-SD-NPT
M-608-EC, 03/17 Page 3 of 4
EN, FR, DU
"A" HEX
ACROSS
FLATS
3X ALLEN HEAD SET
SCREW FOR LOCKING
PANEL MOUNTED
RECEPTACLE IN PLACE
3G
4
16
5
6
7
8
19
14
15
2
1
18
13
17
12
11
9
10
36" (914.4 mm)
STANDARD LENGTH
AF-B1916-612SL-L36 Shown
3.53
(89.7mm)
0.75
(19.1mm)
"B" HEX
ACROSS
CORNERS
C
DTHREAD 'E'
ØF
COVER ADDS .8 INCHES (20.3mm)
TO DIMENSIONS "C" AND "D"
Dimensions
Dimensions for NPT Mount Receptacles
Shell
Size
A INCHES
(mm)
B INCHES
(mm)
C INCHES
(mm)
D INCHES
NPT THREAD
F INCHES
(mm)
AF/SF
GD/SD
16 2.5 (63.5) 2.875 (73.0) 5 (127.0) 4.156 (105.6) 1 ½ - 11 ½ 1.969 (50.0)
20 3 (76.2) 3.469 (88.1) 5.031 (127.8) 4.156 (105.6) 2 – 11 ½ 2.469 (62.7)
24 3.5 (88.9) 4.031 (102.4) 5.406 (137.3) 4.156 (105.6) 2 ½ - 8 2.969 (75.4)
28 4 (101.6) 4.625 (117.5) 5.469 (138.9) 4.156 (105.6) 3 - 8 3.469 (88.1)
GB/SB
GDU/SDU
16 2.5 (63.5) 2.875 (73.0) 6 (152.4) 5.156 (131.0) 1 ½ - 11 ½ 1.969 (50.0)
20 3 (76.2) 3.469 (88.1) 6.031 (153.2) 5.156 (131.0) 2 – 11 ½ 2.469 (62.7)
24 3.5 (88.9) 4.031 (102.4) 6.406 (162.7) 5.156 (131.0) 2 ½ - 8 2.969 (75.4)
28 4 (101.6) 4.625 (117.5) 6.469 (164.3) 5.156 (131.0) 3 - 8 3.469 (88.1)
M-608-EC, 03/17 Page 4 of 4
EN, FR, DU
Voice 303-761-2121
FAX 281-445-7404
E-mail service@VantageXP.com
Web Site www.VantageXP.com
4140 World Houston Pkwy, Ste 130
Houston, Texas 77032, USA
Note: Electrical installation shall be in compliance with the National Electric Code
(NEC), EN/IEC60079-14, and/or any other presiding local or national electrical code.
CABLE AND ENCLOSURE ASSEMBLIES
Factory Assembly of Connectors and Cable
If your connector(s) arrived pre-assembled to cable and/or other third-party
components, consider the following:
1. Follow the instructions and recommended maintenance practices for
the attachment plug and/or receptacle.
2. Review the useage instructions on the connector nameplate.
3. For European ATEX applications, in the potentially explosive atmosphere,
the unterminated end of an integrally mounted cable shall be terminated
in a suitable junction box, e.g. in type of protection flameproof
enclosures "d" or increased safety "e".
  • Page 1 1