  • Hello! I am an AI chatbot trained to assist you with the Eaton 5S 700 Installation and User Manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Installation and
user manual
English - Français
Español - Português
EATON 5S
700/1000/1500
www.eaton.com
2
614-06818-01
2 3
1
4
EATON 5S
Packaging
Quick start
A
Caution!
•BeforeinstallingtheEaton 5S,readthebooklet
3
containingthesafetyinstructionsthatmustbefollowed.
Thenfollowtheinstructionsgiveninthismanual
2
.
•Avantl'installationdeEaton 5S,lirelelivret
3
quiprésentelesconsignesdesécuritéàrespecter.Suivre
ensuitelesinstructionsduprésentmanuel
2
.
•AntesdelainstalacióndelEaton 5S,leerelmanual
3
quepresentalasinstruccionesdeseguridadacumplir.A
continuación,seguirlasinstruccionesdelpresentemanual
2
.
•AntesdainstalaçãodoEaton 5S,lerocaderno
3
ondeconstamasinstruçõesdesegurançaarespeitar.
Depois,seguirasinstruçõesdopresentemanual
2
.
EN
FR
ES
PT
3
614-06818-01
4
B
C
1000 / 1500
700
E
D
Register warranty at: powerquality.eaton.com
Service cable
Modem
4
614-06818-01
Battery change
• Warning: take care not to inverse the polarity + (red) and - (black) when connecting the battery as this will destroy
the device.
b
c
a
Press and slide
a
b
c
Press and slide
700
1000 / 1500
Battery disposal and safety
•Caution. Batteryservicelifeisreducedby50%foreverytendegreesabove25°C(77°F).
•The battery must be replaced exclusively by qualied personnel (risk of shock),withnewbatteryapprovedby
EatontoensurecorrectoperationoftheUPS.
•Thebatterymustbedisposedofinaccordancewithapplicableregulations.Toremovethebattery,shutdownthe
UPS(button
6
OFF),removethepowercordandproceedasindicatedbelow"Batterychange".
5
614-06818-01
Technical characteristics
(*) Warning: Outputcablesshouldnotexceed10m(32.81ft)length.
Eaton 5S 700 1000 1500
•UPSpower 700VA/
420W
1000VA/
600W
1500VA/
900W
•Nominalinputvoltage 93V-138V
•Inputfrequency 50/60Hz(46-70Hzworkingrange)
•Voltage/frequencyofbatterybackup
outlets
19
inbatterymode
115V+15%-20%(60Hz±1Hz)
•Totaloutputcurrentforalloutlets 10Amax 15Amax
•Outputcurrentofbatterybackup
outlets
19
6.1Amax 8.7Amax 13.1Amax
•Leakagecurrent 0.4mA
•Inputprotection 10Aresettablecircuit
breaker
15Aresettablecircuitbreaker
•Transfertime 5mstypical
•Telephone/Datasurgeprotection Tel,ISDN,ADSL,Ethernet
•Sealedlead-acidbattery 12V,9Ah 2x12V,7Ah 2x12V,9Ah
•Automaticbatterytest Onceaweek
•Averagebatterylife 4yearstypical,dependingontemperatureandnumberofdischargecycles
•Operatingtemperature 0to35°C/32 to 95 °F
•Storagetemperature -25°Cto+55°C/-13 °F to 131 °F
•Operatingrelativehumidity 0to85%
•Operatingelevation 0to2000m/0 to 6562 ft
•Safetystandards UL1778
•Electromagneticcompatibility
standards
FCCPart15ClassB
•Dimensions(mm/inch) 260x87x250/
10.24 x 3.43 x 9.84
382x87x250/15.04 x 3.43 x 9.84
•Weigth(kg/lb) 5.9/13.0 9.7/21.4 11.6/25.6
6
614-06818-01
ENGLISH
1. Operating conditions
• ThisproductisanUninterruptiblePowerSupply(UPS)forcomputersandtheir
peripherals,televisionsets,stereosystemsandvideorecorders...Itmustnotbeused
tosupplyotherelectricalequipment(lighting,heating,householdappliances,etc.).
• UPScanbeinstalledinhorizontal,verticalposition.
2. Description
AVR
%
Min
Hz
kVA
kW
6
7
8
6
ON/OFFbuttonforthe
batterybackupoutlets
7
Scrolldown
8
Mutealarm
LCD
16
15
14
17
11
10
9
12
13
9
UPSON
10
AVRmode
11
Batterymode
12
Internalfault
13
Outputloadlevel
14
Batterylevel
15
Inputmeasurements
16
Outputmeasurements
17
Measuringunit
Outlets
20
21
19
18
20
21
19
18
18
Surgeprotectionoutlets
19
Batterybackupoutlets
20
Protection(circuitbreaker)
21
ACInputCord
7
614-06818-01
ENGLISH
3. UPS connections
• ConnecttheUPS
1
totheAC-powersystemviaawalloutletwithanearthconnector,
usingtheattachedcord
21
(seegureA).
• Plugcriticalequipment(computer,monitor,modem,etc.)intotheoutlets
19
providing
batterybackuppowerandsurgeprotection(seegureB),takingcarenottoexceed
theratedcurrentindicatedinamperes.
• Otherdevices(printer,scanner,fax,etc.)canbeconnecttothesurgeprotectionoutlets
18
(seegureB).Thesurgeprotectionoutletsarenotbackedupbybatterypowerin
theeventofapoweroutage.
Optional Internet modem / Network connection:
AmodemorEthernetdatalinecanbeprotectedagainstsurgesbyconnectingitviathe
UPS.ConnecttheexistingdevicecablebetweenthewalloutletandtheUPS,andusea
similarcablebetweentheUPSandthedevice,asindicatedinguresCandD(cablenot
supplied).
Optional USB connection:
TheUPSdevicecanbeconnectedtothecomputerusingtheUSBcable
4
supplied
(seegureC).
EatonUPSCompanionsoftwareisdownloadablefrompowerquality.eaton.com.
Registerforthewarrantyonpowerquality.eaton.com.
4. Master and EcoControl outlets operating procedure
Inordertolimitenergyconsumptionofperipherals(scanner,printer)instandbymode,
theEaton5SisequippedwithEcoControloutletsthataredependentontheMaster
outlet.WhenthemaindevicesuppliedbytheMasteroutlet(computer)isshutdown,the
EcoControloutletsareautomaticallydeactivatedandtheperipheralsshutdown.
Thisfunction(deactivatedbydefault)isvalidatedandconguredusingtheconguration
toolintegratedinthesoftware.
Note: when the function is activated, do not connect critical applications to EcoControl outlets.
Threshold setup
AdefaultsetupensuresthecorrectoperationoftheEcoControlfunction.However,
dependingontheconsumptionofthemainload,thetriggerthresholdoftheEcoControl
functionmayhavetobemodiedusingthecongurationsoftwaresuppliedwiththe
UPS:
• First,makesurethatthefunctionisactivatedinthe"EcoControlFunction"tabofthe
congurationtool.
• IftheperipheralsconnectedtotheEcoControloutletsdonotswitchoffwhenthemain
loadisnotinnormaloperation(ex:wheninstandbymode),thedetectionthreshold
valuemustbesettoHigh.
• IftheratedconsumptionlevelofthemainloadislowandtheEcoControloutletsshut
downwhenthemainloadisoperatingnormally,thedetectionthresholdvaluemust
besettoLow.
8
614-06818-01
ENGLISH
6. Operation
Battery charge
TheUPSchargesthebatteryassoonasitisconnectedtotheACoutlet,whetherbutton
6
ispressedornot.Whenusedforthersttime,thebatterywillonlyprovideits
maximumperformanceafterithasbeenchargedfor8hours.Itisrecommendedthat
theUPSbepermanentlyconnectedtotheACpowersupplytoensurethebestpossible
performance.
Switching-on the UPS
Pressbutton
6
forabout1second.
Surge protection outlets
18
without battery backup
EquipmentconnectedtotheseoutletsissuppliedassoonastheACcord
21
isplugged
in.Theyarenotaffectedbybutton
6
.
Battery backup outlets
19
Equipmentconnectedtotheseoutletsissuppliedassoonasbutton
6
turnsgreen
(seegureE).
TheseoutletscanbeturnedoneveniftheUPSisnotconnectedtoACpower
(button
6
ashes).
5. UPS setting through the LCD
l LCDshutoffifnoactivityfor3minutes.
5s 2s 2s
EcoControl Alarm
Release scroll down button to select menu
Save the new value
10s 5s 5s
Example of setting
9
614-06818-01
ENGLISH
(Forfurtherinformation,visitthewww.powerquality.eaton.comsiteorcontactpost-salessupport.)
Problem Diagnostic Solution
1
•Thebatterybackupoutlets
19
arenotsuppliedwithpower.
•Button
6
isnotliteon. •Pressbutton
6
andcheckthat
itturnsgreen.
2 •Theconnecteddevicesarenot
suppliedwhenACpowerfails.
•Thedevicesarenotconnected
tothebatterybackupoutlets
19
.
•Connectthedevicestothe
batterybackupoutlets
19
.
3 •ACpowerisavailable,butthe
UPSoperatesonbatterypower.
•Circuitbreaker
20
,locatedat
therearoftheUPS,hasbeen
trippedbyanoverloadonthe
UPSoutput.
•Disconnectexcessequipment
andresetthecircuitbreaker
20
bypressingthecorresponding
button.
4
•Greenbutton
6
ashesand
audiblealarmbeepsevery3
seconds.
•TheUPSbatterybackupoutlets
19
areoverloaded.
•Disconnectexcessequipment
connectedtothebatterybackup
outlets
19
.
5
•Faultsign
12
appearontheLCD
panelandaudiblealarmbeeps
continuously.
•AfaulthasoccurredontheUPS.
Thebatterybackupoutlets
19
are
nolongersupplied.
•Callpost-salessupport.
6 •EcoControloutletskeeppowered
whenmainapplication(Master
outlet)isstopped.
•EcoControlfunctionisnot
activatedornotproperlyset.
•Activateorsetproperly
EcoControlfunctionusingthe
softwareprovidedwiththe
product.
7. Troubleshooting
AC-power disturbance
• IfACpowerisdisturbedorfails,theUPScontinuestooperateonbatterypower.
Button
6
ashesgreen.Innormalmode,theaudiblealarmbeepseverytenseconds,
theneverythreesecondswhentheendofbatterybackuptimeisnear.Insilentmode,
theaudiblealarmsimplybeepsoncewhentheUPStransferstobatterypower.
• Ifthepoweroutagelastslongerthanthebatterybackuptime,theUPSshutsdown
andautomaticallyrestartswhenpowerisrestored.Followingacompletedischarge,a
fewhoursarerequiredtorechargethebatterybacktofullbackuptime.
Surge protection:
Alloutletsincludesurgeprotection.
Shutdown of the battery backup outlets
19
Pressbutton
6
formorethantwoseconds.
www.eaton.com
614-06818-01
/