RCI 10-3/10-3-FPD

Dormakaba RCI 10-3/10-3-FPD, 10-3-FPD, PDD-FT-3 Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Dormakaba RCI 10-3/10-3-FPD Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
PDD-FT-3
Fire Panel Interface
With EOL Trigger
Installation and Specifications Manual
PDD-FT-3
InstallatIon
ISPSFPD-3
PCN16045
R12/17GR
© 2017 RUTHERFORD CONTROLS INT’L | dormakaba Group
www.rutherfordcontrols.com • Phone: 1.800.265.6630 • fax: 1.800.482.9795 • e-mail: [email protected]
Details
The PDD-FT-3 board is a fire panel control interface. This board can be used to control DC
output based on a fire alarm control panel. Two outputs switch state on alarm.
Features
• NonLatchingorLatchingmode
• Universal12VDCor24VDCOperation
• Reversepolarityprotected
• NormallyON&NormallyOFFOutput
• OutputLED’sindicatecondition
• OutputscanbeTriggeredwith:
1)N/OorN/CSwitchwithSupervisedEndofLineResistor(EOL)
2)N/CSwitchwith(OVR)override
3)N/CSwitchwith(AUX-IN)auxiliary
4)Groundonanytriggerinputwhen(GRN)Jumperisenabled
• FormCDPDTRelayIndicatesTriggerStatus
• 3AmpTransferRelayContacts
• Autoormanualresetbyjumperselection
Installation Instructions
1. MountthePDD-FT-3boardinasuitablelocationincloseproximitytothepowersupply.
Note:
a) Groundfaultdetectionwillonlyworkifconductivestandoffsareusedandpower
supplyenclosureisproperlygrounded.
b) Asthisdevicecanbeusedtopowermultipledevicesensurethatallwiringisofan
appropriategaugeforthedevicesbeinginstalled.
c) ThisRCIboardisforuseinacontrolledindoorenvironment.ThePDD-FT-3and
alldevicesconnectedtoorpoweredthroughthePDD-FT-3shallbeinstalledwithin
thesamecontinuousbuildingstructure.Installationmustbeinaccordancewith
localbuildingandfirecodes.CheckwithAuthorityHavingJurisdiction(AHJ)for
detailspriortoinstalling.
d) Allpowerlimitedwiringmustbeaminimumof.25”fromnon-powerlimitedwiring.
e) Maximumtorqueof7in*lbforblackinputandoutputterminals.
2.Connect“INPUT”terminalstooutputofDCsupply,payingcloseattentiontopolarityof
DCoutputfrompowersupply.
3.ConnectdevicestobepoweredtooutputterminalsofPDD-FT-3controlboard,paying
closeattentiontopolarityrequirements.Minimum22AWGandmaximumdistanceof
6170ft.forfieldwiring.
4.Setjumpers(RST,OVR,AUX,andGRN)asrequiredforproperinstallation.
2
5. ConnectfirealarmcontrolpaneltoEOLinputterminals,ensurethe2.2Kresistoris
installed at the terminals in the fire alarm panel.
a) Seefirealarmcontrolpanelinstallationandoperationmanualfordetailsabout
signalingrequirements.
b) Fig’s2-6inthisinstallationguidewillprovidedetailsonwiringtothefirealarm
control panel.
6. Connectanyrequiredmonitoringequipmenttothetriggerrelaysusing
appropriatecabling.
7. Thisunitistobepoweredfroma10SeriesRCIPowerSupplyoraULlisted
powersupply.
8. Applypowertopowersupplytoactivatecontrolboardandtestallconnecteddevices.
Specifications
• ForULlistedpowersupply
• UL2946eandULCS319Class1AccessControlSystemUnit
AccessControlLevels:
Endurance:Level4LineSecurity:Level1
PowerStandby:Level1DestructiveAttack:Level1
Input
• InputVoltage:12or24VDC±10%
• TypicalCurrentDrawwithnoOutputLoad:10mA@12VDC
15mA @24VDC
Output
• OutputRelayRating:3A
Monitor Inputs
• EOL(EndofLine)Trigger:Triggerat+or–50%of2.2K
• OVRTrigger
• AUXTrigger
• ResetInput
• GroundFaultTrigger(seenote1a)
Monitor Outputs
• TriggerRelayRating:1ADPDT
Environmental
• Useinacontrolledindoorenvironment
Warning:Improperwiringconnectionsmayresultindamagetothisproduct.
Miseengarde:Unmauvaisraccordementdescâblesrisqued’endommagerceproduit.
3
Description of PDD-FT-3 Connections SeeFig.1
Input Power
“-INPUT+”:2positionterminalblockwithselfclampingscrewswillacceptmultiple12AWG
wiresUniversalinput.
Output Power
Two,2positionterminalblocks.Selfclampingscrewswillacceptmultiple12AWGwires.
“-N/ON+”arenormallyONoutputpower.ThisoutputisONwhenthePDD-FT-3isnottrig-
gered.“-N/OFF+”isnormallyOFF.ThisoutputisONwhenthisunitistriggered.Thetrans-
ferrelayisratedat3Amps.
Power LED’s
Aredledaboveeachoutputindicateswhichoutputisactive.
Input Trigger EOL*
2positionterminalblock–Willaccept12AWGwire.Thisinputmustseethe2.2Kohmend
oflineresistortobeinthenormalsetcondition.Achangeinresistanceof±50%willcause
thetriggerrelaystodropoutintheTriggeredmode.Thischangeinresistanceiscausedby
thesupervisedwirebetweentheEOLatthefirepanelandthePDD-FT-3beingshortedor
opened.TheEOLsupervisesthepairofwires.
Input Trigger OVR*
2positionterminalblock-Willaccept12AWGwire.Thispairisnormallyclosedandcanbe
connectedtoanoverrideswitch.WhenOVRisopen,unitwilltrigger.
Input Trigger AUX-IN*
2positionterminalblock-Willaccept12AWGwire.Thispairisnormallyclosedandcanbe
connectedtoanauxiliarydevice.WhenAUX-INisopen,unitwilltrigger.
Reset 2 Position Terminal Block*
2positionterminalblock-Willaccept12AWGwire.Whenthispairisshorted,inputtrig-
gersdonotlatch.Ifpairisopen,theinputtriggerswilllatchuntilalarmiscorrectedand
RESETismomentaryclosedtoresettrigger.
*Minimum22AWGandmaximumdistanceof6170ftforfieldwiring.
Jumpers RST - OVR - AUX
Jumpersareusedtoactivate(remote)featuresasrequired.
Jumpers GRN
Thisjumperisusedtoenablegroundsupervisionortheinputs.Ifthejumperisconnected
tobothheaders,andthemountingholeadjacenttojumperisconnectedtoearthground,a
groundonanyoftheinputtriggerswillcauseatrigger.
Trigger Status Terminal block
Two,3positionterminalblocks-Willaccept12AWGwire.FormCDPDTrelaywitha1
Ampratingwillindicatetheconditionoftrigger.CandNOarenormallyopeninthenormal
energizenottriggeredstate.CandNCarenormallyclosedinthenormalenergizednottrig-
geredstate.ThesecontactsmaybeusedtoprovidefeedbacktotheFACPorotherauxilary
devices.
4
Fig.2-FirePanelConnectionsforNon-Latching
AutomaticResetOperation
ThisapplicationillustrateshowtoconnectthePDD-FT-3toapowersupplyformaininput
aswellasafirealarmcontrolpanel.Ifwiredinthismanner,outputswillchangestateonly
aslongasthefirealarmrelayisactive.WhenthefirealarmresetsthePDD-FT-3outputs
will also reset.
- N/OFF +- N/ON +
- INPUT +
GRN
EOL
RESET
AUX
OVR
RST
AUX - IN
OVR
CNO NC
TRIGGERED
2.2 K
PDD-FT
CNO NC
TRIGGERED
DC Input
Trigger Output
Ground Fault Jumper
Reset Input
End Of Line
Override Input
Auxilary Input
Normally "On" Output
Normally "Off" Output
Output Led's
-BAT+
- Output +24V 12V
DC
- N/OFF +- N/ON +
- INPUT +
GRN
EOL
RESET
AUX
OVR
RST
AUX - IN
OVR
CNO NC
TRIGGERED
PDD-FT
CNO NC
TRIGGERED
OUTPUT
NC
FIRE PANEL
BY OTHERS
NO
CNC NO
2.2 K
OUTPUT
2.2 K
NC
C NO
5
Fig.1-PDD-FT-3Connections
Application Diagrams
Fig.3-FirePanelConnectionsforLatchingReleasewithN/OManual
Reset
ThisapplicationillustrateshowtoconnectthePDD-FT-3toapowersupplyformaininput
aswellasafirealarmcontrolpanel.Ifwiredinthismanner,outputswillchangestate
wheneverthefirealarmrelayactivatesandremainlatchedinthetriggeredstateuntilreset
byactivatingtheN/Oswitch.
Note:RemoveRSTjumperformanualresetoperation.
Remarque:RetirezlabretelleRSTpoureffectueruneréinitialisation manuelle.
Fig.4-ConnectionsforNon-Latchingreleaseresetusingmultiple
PDD-FT-3 boards
ThisapplicationillustrateshowtoconnectthePDD-FT-3toapowersupplyformaininput
aswellasafirealarmcontrolpanel.Ifwiredinthismanner,outputswillchangestateonly
aslongasthefirealarmrelayisactive.WhenthefirealarmresetsthePDD-FT-3outputs
willalsoreset.ConnectingtheEOLinputofoneboardtothetriggerrelayofthenextboard
asshownwillallowforoverrideandresetofmultipleboards.
Note:TheRSTjumpermustbeleftinplaceonallboardsforautomaticresetoperation.
Remarque:LabretelleRSTdoitêtre laisséeenplacesurtouslespanneauxpoureffectuer
une réinitialisationautomatique.
-BAT+
- Output +24V 12V
DC
- N/OFF +- N/ON +
- INPUT +
GRN
EOL
RESET
AUX
OVR
RST
AUX - IN
OVR
CNO NC
TRIGGERED
PDD-FT
CNO NC
TRIGGERED
OUTPUT
NC
FIRE PANEL
BY OTHERS
NO
CNC NO
2.2 K
OUTPUT
2.2 K
NC
C NO
-BAT+
- Output +24V 12V
DC
- N/OFF +- N/ON +
- INPUT +
GRN
EOL
RESET
AUX
OVR
RST
AUX - IN
OVR
CNO NC
TRIGGERED
PDD-FT
CNO NC
TRIGGERED
OUTPUT
NC
FIRE PANEL
BY OTHERS
NO
CNC NO
2.2 K
OUTPUT
2.2 K
NC
C NO
-BAT+
- Output +24V 12V
DC
- N/OFF +- N/ON +
- INPUT +
GRN
EOL
RESET
AUX
OVR
RST
AUX - IN
OVR
CNO NC
TRIGGERED
PDD-FT
CNO NC
TRIGGERED
2.2 K
6
Fig.5-ConnectionsforlatchingreleasewithN/Omanualresetusing
multiplePDD-FT-3boards(Master&Slave)
ThisapplicationillustrateshowtoconnectthePDD-FT-3toapowersupplyformaininput
aswellasafirealarmcontrolpanel.Ifwiredinthismanner,outputswillchangestate
wheneverthefirealarmrelayactivatesandremainlatchedinthetriggeredstateuntil
MasterisresetbyactivatingtheN/Oswitch.ConnectingtheEOLinputofoneboardtothe
triggerrelayofthenextboardasshownwillallowforresetofmultipleboards.
Note:TheRSTjumpermustbeleftinplaceonallslaveboardsexcepttheonethatis
directlyconnectedtothefirealarm(Master),reset,andswitches.
Remarque: LabretelleRSTdoitêtre laisséeenplacesurtouslespanneauxasservis,sauf
celuiquisetdirectementconnecté àl’alarmedefeu(d’exploitation),situé près des boutons
de réinitialisationetd’annulation.
Fig.6-Fire Panel
Connectionsfor
Latching Trigger
withN/OManual
ResetandN/Cover-
ridewithBattery
Backup
This application illus-
trates how to connect
thePDD-FT-3toanRCI
PowerSupplyformain
input,ACfailureaswell
as a fire alarm control
panel.Ifwiredinthis
manner,triggeroutputs
willchangestatewhen-
everthefirealarm,or
ACfailurerelaysactivate.ThePDD-FT-3outputswillremaininthetriggeredstateuntilboth
relayshavebeenresetandtheN/Omanualresetistriggered.
Note: EnsurejumpersforRST,OVR,andAUXINareremovedtoallowterminalstooperate
correctly.
Remarque:Assurez-vousquelesbretellesRST,OVRetAUXINsontretirées afin de per-
mettreauxterminauxdefonctionnercorrectement.
-BAT+
- Output +24V 12V
DC
- N/OFF +- N/ON +
- INPUT +
GRN
EOL
RESET
AUX
OVR
RST
AUX - IN
OVR
CNO NC
TRIGGERED
PDD-FT
CNO NC
TRIGGERED
OUTPUT
NC
FIRE PANEL
BY OTHERS
NO
CNC NO
2.2 K
OUTPUT
2.2 K
NC
C NO
-BAT+
- Output +24V 12V
DC
- N/OFF +- N/ON +
- INPUT +
GRN
EOL
RESET
AUX
OVR
RST
AUX - IN
OVR
CNO NC
TRIGGERED
PDD-FT
CNO NC
TRIGGERED
2.2 K
L
N
-BAT+
G
- Output +
GRN
24V 12V
NO C NC
AC Fail
DC
AC
- N/OFF +- N/ON +
- INPUT +
GRN
EOL
RESET
AUX
OVR
RST
AUX - IN
OVR
CNO NC
TRIGGERED
PDD-FT
CNO NC
TRIGGERED
OUTPUT
NC
FIRE PANEL
BY OTHERS
NO
CNC NO
2.2 K
OUTPUT
2.2 K
NC
C NO
2.2 K
POWER SUPPLY
INTER-CONNECT.
N/O MANUAL RESET
SEE NOTE 4.
EOL
RESET
RST
BATTERY
-BAT+
N/C MANUAL OVER-RIDE
SEE NOTE 3.
AC FAIL CIRCUIT
ONLY REQUIRED WITH
BATTERY BACKUP.
SEE NOTE 5.
Non-power limited
Power limited
Power limited
3) FOR MANUAL OVER-RIDE REMOVE JUMPER "OVR"
4) FOR MANUAL RESET REMOVE JUMPER "RST"
5) FOR AUX-IN REMOVE JUMPER "AUX"
6) JUMPER GRN IS FOR GROUND FAULT DETECTION
ON ENABLES GROUND FAULT, REMOVED DISABLES
GROUND FAULT.
AND INSTALL N/C SWITCH.
AND INSTALL A N/O SWITCH.
AND INSTALL A N/C CIRCUIT.
1) DISCONNECT AC INPUT PRIOR TO SERVICING.
SPACING OF .25" FROM NON-POWER LIMITED CIRCUITS.
2) ALL POWER LIMITED CIRCUITS TO HAVE A MINIMUM
NOTES 3-6 REFER TO PDD-FT ONLY
NOTE:
GROUND FAULT JUMPER
SEE NOTE 6.
7
Notes
For Technical Support:
1.800.265.6630|WWW.RUTHERFORDCONTROLS.COM
PDD-FT-3TroubleshootingGuide
Problem Solution
-CheckACPower.
-CheckPowerSupplyforvoltageoutput.
-Checkdevicesconnectedtooutputsfor
ashortcircuit.(PTC’smayrequireshort
toberemovedforseveralminutes
beforeautomaticallyresetting).
-Checktriggerjumpers.OutputLED
shouldbelitifoutputisactive.
-Checkforproperwiringconnectionson
triggerconnections.
-Ensurethat2.2Kresistorisinstalledat
EndofLinepositioninthewiring.
-Checkdevicesconnectedtooutputsfor
ashortcircuit.(PTC’smayrequire
shorttoberemovedforseveralminutes
 beforeautomaticallyresetting.)
NoDCoutputfromterminals.
Triggerisactiveandwillnotreset.
Troubleoutputrelayisde-energized.
(Relayterminalsarelabeledshownin
theNormal,energized,“notrouble”
condition.Relaysareenergizedwhen
notroubleisdetected.)
/