Dormakaba 10-3-FPD Installation guide

Category
Fire protection
Type
Installation guide

This manual is also suitable for

PDD-FT-3
Fire Panel Interface
With EOL Trigger
Installation and Specifications Manual
PDD-FT-3
InstallatIon
ISPSFPD-3
PCN16045
R12/17GR
© 2017 RUTHERFORD CONTROLS INT’L | dormakaba Group
www.rutherfordcontrols.com • Phone: 1.800.265.6630 • fax: 1.800.482.9795 • e-mail: [email protected]
Details
The PDD-FT-3 board is a fire panel control interface. This board can be used to control DC
output based on a fire alarm control panel. Two outputs switch state on alarm.
Features
• NonLatchingorLatchingmode
• Universal12VDCor24VDCOperation
• Reversepolarityprotected
• NormallyON&NormallyOFFOutput
• OutputLED’sindicatecondition
• OutputscanbeTriggeredwith:
1)N/OorN/CSwitchwithSupervisedEndofLineResistor(EOL)
2)N/CSwitchwith(OVR)override
3)N/CSwitchwith(AUX-IN)auxiliary
4)Groundonanytriggerinputwhen(GRN)Jumperisenabled
• FormCDPDTRelayIndicatesTriggerStatus
• 3AmpTransferRelayContacts
• Autoormanualresetbyjumperselection
Installation Instructions
1. MountthePDD-FT-3boardinasuitablelocationincloseproximitytothepowersupply.
Note:
a) Groundfaultdetectionwillonlyworkifconductivestandoffsareusedandpower
supplyenclosureisproperlygrounded.
b) Asthisdevicecanbeusedtopowermultipledevicesensurethatallwiringisofan
appropriategaugeforthedevicesbeinginstalled.
c) ThisRCIboardisforuseinacontrolledindoorenvironment.ThePDD-FT-3and
alldevicesconnectedtoorpoweredthroughthePDD-FT-3shallbeinstalledwithin
thesamecontinuousbuildingstructure.Installationmustbeinaccordancewith
localbuildingandfirecodes.CheckwithAuthorityHavingJurisdiction(AHJ)for
detailspriortoinstalling.
d) Allpowerlimitedwiringmustbeaminimumof.25”fromnon-powerlimitedwiring.
e) Maximumtorqueof7in*lbforblackinputandoutputterminals.
2.Connect“INPUT”terminalstooutputofDCsupply,payingcloseattentiontopolarityof
DCoutputfrompowersupply.
3.ConnectdevicestobepoweredtooutputterminalsofPDD-FT-3controlboard,paying
closeattentiontopolarityrequirements.Minimum22AWGandmaximumdistanceof
6170ft.forfieldwiring.
4.Setjumpers(RST,OVR,AUX,andGRN)asrequiredforproperinstallation.
2
5. ConnectfirealarmcontrolpaneltoEOLinputterminals,ensurethe2.2Kresistoris
installed at the terminals in the fire alarm panel.
a) Seefirealarmcontrolpanelinstallationandoperationmanualfordetailsabout
signalingrequirements.
b) Fig’s2-6inthisinstallationguidewillprovidedetailsonwiringtothefirealarm
control panel.
6. Connectanyrequiredmonitoringequipmenttothetriggerrelaysusing
appropriatecabling.
7. Thisunitistobepoweredfroma10SeriesRCIPowerSupplyoraULlisted
powersupply.
8. Applypowertopowersupplytoactivatecontrolboardandtestallconnecteddevices.
Specifications
• ForULlistedpowersupply
• UL2946eandULCS319Class1AccessControlSystemUnit
AccessControlLevels:
Endurance:Level4LineSecurity:Level1
PowerStandby:Level1DestructiveAttack:Level1
Input
• InputVoltage:12or24VDC±10%
• TypicalCurrentDrawwithnoOutputLoad:10mA@12VDC
15mA @24VDC
Output
• OutputRelayRating:3A
Monitor Inputs
• EOL(EndofLine)Trigger:Triggerat+or–50%of2.2K
• OVRTrigger
• AUXTrigger
• ResetInput
• GroundFaultTrigger(seenote1a)
Monitor Outputs
• TriggerRelayRating:1ADPDT
Environmental
• Useinacontrolledindoorenvironment
Warning:Improperwiringconnectionsmayresultindamagetothisproduct.
Miseengarde:Unmauvaisraccordementdescâblesrisqued’endommagerceproduit.
3
Description of PDD-FT-3 Connections SeeFig.1
Input Power
“-INPUT+”:2positionterminalblockwithselfclampingscrewswillacceptmultiple12AWG
wiresUniversalinput.
Output Power
Two,2positionterminalblocks.Selfclampingscrewswillacceptmultiple12AWGwires.
“-N/ON+”arenormallyONoutputpower.ThisoutputisONwhenthePDD-FT-3isnottrig-
gered.“-N/OFF+”isnormallyOFF.ThisoutputisONwhenthisunitistriggered.Thetrans-
ferrelayisratedat3Amps.
Power LED’s
Aredledaboveeachoutputindicateswhichoutputisactive.
Input Trigger EOL*
2positionterminalblock–Willaccept12AWGwire.Thisinputmustseethe2.2Kohmend
oflineresistortobeinthenormalsetcondition.Achangeinresistanceof±50%willcause
thetriggerrelaystodropoutintheTriggeredmode.Thischangeinresistanceiscausedby
thesupervisedwirebetweentheEOLatthefirepanelandthePDD-FT-3beingshortedor
opened.TheEOLsupervisesthepairofwires.
Input Trigger OVR*
2positionterminalblock-Willaccept12AWGwire.Thispairisnormallyclosedandcanbe
connectedtoanoverrideswitch.WhenOVRisopen,unitwilltrigger.
Input Trigger AUX-IN*
2positionterminalblock-Willaccept12AWGwire.Thispairisnormallyclosedandcanbe
connectedtoanauxiliarydevice.WhenAUX-INisopen,unitwilltrigger.
Reset 2 Position Terminal Block*
2positionterminalblock-Willaccept12AWGwire.Whenthispairisshorted,inputtrig-
gersdonotlatch.Ifpairisopen,theinputtriggerswilllatchuntilalarmiscorrectedand
RESETismomentaryclosedtoresettrigger.
*Minimum22AWGandmaximumdistanceof6170ftforfieldwiring.
Jumpers RST - OVR - AUX
Jumpersareusedtoactivate(remote)featuresasrequired.
Jumpers GRN
Thisjumperisusedtoenablegroundsupervisionortheinputs.Ifthejumperisconnected
tobothheaders,andthemountingholeadjacenttojumperisconnectedtoearthground,a
groundonanyoftheinputtriggerswillcauseatrigger.
Trigger Status Terminal block
Two,3positionterminalblocks-Willaccept12AWGwire.FormCDPDTrelaywitha1
Ampratingwillindicatetheconditionoftrigger.CandNOarenormallyopeninthenormal
energizenottriggeredstate.CandNCarenormallyclosedinthenormalenergizednottrig-
geredstate.ThesecontactsmaybeusedtoprovidefeedbacktotheFACPorotherauxilary
devices.
4
Fig.2-FirePanelConnectionsforNon-Latching
AutomaticResetOperation
ThisapplicationillustrateshowtoconnectthePDD-FT-3toapowersupplyformaininput
aswellasafirealarmcontrolpanel.Ifwiredinthismanner,outputswillchangestateonly
aslongasthefirealarmrelayisactive.WhenthefirealarmresetsthePDD-FT-3outputs
will also reset.
- N/OFF +- N/ON +
- INPUT +
GRN
EOL
RESET
AUX
OVR
RST
AUX - IN
OVR
CNO NC
TRIGGERED
2.2 K
PDD-FT
CNO NC
TRIGGERED
DC Input
Trigger Output
Ground Fault Jumper
Reset Input
End Of Line
Override Input
Auxilary Input
Normally "On" Output
Normally "Off" Output
Output Led's
-BAT+
- Output +24V 12V
DC
- N/OFF +- N/ON +
- INPUT +
GRN
EOL
RESET
AUX
OVR
RST
AUX - IN
OVR
CNO NC
TRIGGERED
PDD-FT
CNO NC
TRIGGERED
OUTPUT
NC
FIRE PANEL
BY OTHERS
NO
CNC NO
2.2 K
OUTPUT
2.2 K
NC
C NO
5
Fig.1-PDD-FT-3Connections
Application Diagrams
Fig.3-FirePanelConnectionsforLatchingReleasewithN/OManual
Reset
ThisapplicationillustrateshowtoconnectthePDD-FT-3toapowersupplyformaininput
aswellasafirealarmcontrolpanel.Ifwiredinthismanner,outputswillchangestate
wheneverthefirealarmrelayactivatesandremainlatchedinthetriggeredstateuntilreset
byactivatingtheN/Oswitch.
Note:RemoveRSTjumperformanualresetoperation.
Remarque:RetirezlabretelleRSTpoureffectueruneréinitialisation manuelle.
Fig.4-ConnectionsforNon-Latchingreleaseresetusingmultiple
PDD-FT-3 boards
ThisapplicationillustrateshowtoconnectthePDD-FT-3toapowersupplyformaininput
aswellasafirealarmcontrolpanel.Ifwiredinthismanner,outputswillchangestateonly
aslongasthefirealarmrelayisactive.WhenthefirealarmresetsthePDD-FT-3outputs
willalsoreset.ConnectingtheEOLinputofoneboardtothetriggerrelayofthenextboard
asshownwillallowforoverrideandresetofmultipleboards.
Note:TheRSTjumpermustbeleftinplaceonallboardsforautomaticresetoperation.
Remarque:LabretelleRSTdoitêtre laisséeenplacesurtouslespanneauxpoureffectuer
une réinitialisationautomatique.
-BAT+
- Output +24V 12V
DC
- N/OFF +- N/ON +
- INPUT +
GRN
EOL
RESET
AUX
OVR
RST
AUX - IN
OVR
CNO NC
TRIGGERED
PDD-FT
CNO NC
TRIGGERED
OUTPUT
NC
FIRE PANEL
BY OTHERS
NO
CNC NO
2.2 K
OUTPUT
2.2 K
NC
C NO
-BAT+
- Output +24V 12V
DC
- N/OFF +- N/ON +
- INPUT +
GRN
EOL
RESET
AUX
OVR
RST
AUX - IN
OVR
CNO NC
TRIGGERED
PDD-FT
CNO NC
TRIGGERED
OUTPUT
NC
FIRE PANEL
BY OTHERS
NO
CNC NO
2.2 K
OUTPUT
2.2 K
NC
C NO
-BAT+
- Output +24V 12V
DC
- N/OFF +- N/ON +
- INPUT +
GRN
EOL
RESET
AUX
OVR
RST
AUX - IN
OVR
CNO NC
TRIGGERED
PDD-FT
CNO NC
TRIGGERED
2.2 K
6
Fig.5-ConnectionsforlatchingreleasewithN/Omanualresetusing
multiplePDD-FT-3boards(Master&Slave)
ThisapplicationillustrateshowtoconnectthePDD-FT-3toapowersupplyformaininput
aswellasafirealarmcontrolpanel.Ifwiredinthismanner,outputswillchangestate
wheneverthefirealarmrelayactivatesandremainlatchedinthetriggeredstateuntil
MasterisresetbyactivatingtheN/Oswitch.ConnectingtheEOLinputofoneboardtothe
triggerrelayofthenextboardasshownwillallowforresetofmultipleboards.
Note:TheRSTjumpermustbeleftinplaceonallslaveboardsexcepttheonethatis
directlyconnectedtothefirealarm(Master),reset,andswitches.
Remarque: LabretelleRSTdoitêtre laisséeenplacesurtouslespanneauxasservis,sauf
celuiquisetdirectementconnecté àl’alarmedefeu(d’exploitation),situé près des boutons
de réinitialisationetd’annulation.
Fig.6-Fire Panel
Connectionsfor
Latching Trigger
withN/OManual
ResetandN/Cover-
ridewithBattery
Backup
This application illus-
trates how to connect
thePDD-FT-3toanRCI
PowerSupplyformain
input,ACfailureaswell
as a fire alarm control
panel.Ifwiredinthis
manner,triggeroutputs
willchangestatewhen-
everthefirealarm,or
ACfailurerelaysactivate.ThePDD-FT-3outputswillremaininthetriggeredstateuntilboth
relayshavebeenresetandtheN/Omanualresetistriggered.
Note: EnsurejumpersforRST,OVR,andAUXINareremovedtoallowterminalstooperate
correctly.
Remarque:Assurez-vousquelesbretellesRST,OVRetAUXINsontretirées afin de per-
mettreauxterminauxdefonctionnercorrectement.
-BAT+
- Output +24V 12V
DC
- N/OFF +- N/ON +
- INPUT +
GRN
EOL
RESET
AUX
OVR
RST
AUX - IN
OVR
CNO NC
TRIGGERED
PDD-FT
CNO NC
TRIGGERED
OUTPUT
NC
FIRE PANEL
BY OTHERS
NO
CNC NO
2.2 K
OUTPUT
2.2 K
NC
C NO
-BAT+
- Output +24V 12V
DC
- N/OFF +- N/ON +
- INPUT +
GRN
EOL
RESET
AUX
OVR
RST
AUX - IN
OVR
CNO NC
TRIGGERED
PDD-FT
CNO NC
TRIGGERED
2.2 K
L
N
-BAT+
G
- Output +
GRN
24V 12V
NO C NC
AC Fail
DC
AC
- N/OFF +- N/ON +
- INPUT +
GRN
EOL
RESET
AUX
OVR
RST
AUX - IN
OVR
CNO NC
TRIGGERED
PDD-FT
CNO NC
TRIGGERED
OUTPUT
NC
FIRE PANEL
BY OTHERS
NO
CNC NO
2.2 K
OUTPUT
2.2 K
NC
C NO
2.2 K
POWER SUPPLY
INTER-CONNECT.
N/O MANUAL RESET
SEE NOTE 4.
EOL
RESET
RST
BATTERY
-BAT+
N/C MANUAL OVER-RIDE
SEE NOTE 3.
AC FAIL CIRCUIT
ONLY REQUIRED WITH
BATTERY BACKUP.
SEE NOTE 5.
Non-power limited
Power limited
Power limited
3) FOR MANUAL OVER-RIDE REMOVE JUMPER "OVR"
4) FOR MANUAL RESET REMOVE JUMPER "RST"
5) FOR AUX-IN REMOVE JUMPER "AUX"
6) JUMPER GRN IS FOR GROUND FAULT DETECTION
ON ENABLES GROUND FAULT, REMOVED DISABLES
GROUND FAULT.
AND INSTALL N/C SWITCH.
AND INSTALL A N/O SWITCH.
AND INSTALL A N/C CIRCUIT.
1) DISCONNECT AC INPUT PRIOR TO SERVICING.
SPACING OF .25" FROM NON-POWER LIMITED CIRCUITS.
2) ALL POWER LIMITED CIRCUITS TO HAVE A MINIMUM
NOTES 3-6 REFER TO PDD-FT ONLY
NOTE:
GROUND FAULT JUMPER
SEE NOTE 6.
7
Notes
For Technical Support:
1.800.265.6630|WWW.RUTHERFORDCONTROLS.COM
PDD-FT-3TroubleshootingGuide
Problem Solution
-CheckACPower.
-CheckPowerSupplyforvoltageoutput.
-Checkdevicesconnectedtooutputsfor
ashortcircuit.(PTC’smayrequireshort
toberemovedforseveralminutes
beforeautomaticallyresetting).
-Checktriggerjumpers.OutputLED
shouldbelitifoutputisactive.
-Checkforproperwiringconnectionson
triggerconnections.
-Ensurethat2.2Kresistorisinstalledat
EndofLinepositioninthewiring.
-Checkdevicesconnectedtooutputsfor
ashortcircuit.(PTC’smayrequire
shorttoberemovedforseveralminutes
 beforeautomaticallyresetting.)
NoDCoutputfromterminals.
Triggerisactiveandwillnotreset.
Troubleoutputrelayisde-energized.
(Relayterminalsarelabeledshownin
theNormal,energized,“notrouble”
condition.Relaysareenergizedwhen
notroubleisdetected.)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Dormakaba 10-3-FPD Installation guide

Category
Fire protection
Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI