Legrand EFB10S-FC Installation guide

Type
Installation guide
Evolution
Series Floor Box
50A Adapter Kit
I N S T A L L A T I O N I N S T R U C T I O N S
I
nstallation Instruction No.: 1 010 786 February 2012
Legrand/Wiremold electrical systems conform to and should be properly
grounded in compliance with requirements of the current National
Electrical Code or codes administered by local authorities.
All electrical products may present a possible shock or fire
hazard if improperly installed or used. Legrand/Wiremold electrical
products may bear the mark of a Nationally Recognized Testing
Laboratory (NRTL) and should be installed in conformance with current
local and/or the National Electrical Code.
IMPORTANT: Please read all instructions
before beginning.
PRODUCTS COVERED: EFB-50A
APPLICATIONS: EFB-50A is designed for use with Evolution
Series Floor Box models: EFB8S,
EFB8S-OG, EFB8S-FC, EFB10S, EFB10S-OG, EFB10S-FC
EFB-50A KIT CONTENTS:
Module Back
Plate Cover
50 Amp Adapter
Base Cover
Ground Lug
50 Amp
Adapter Base
Hardware Bag
Instructions
Step 1. The EFB-50A Adapter will only work with the
plastic tunnel (EFB810-TUN). If you have the metal
tunnel (EFB810S-TUN), you will need to order the
p
lastic tunnel (EFB810-TUN).
Step 3. Remove the tunnel, mounting bracket, divider, end
cap closest to the tunnel, and extra divider screws.
Step 4. Install the 50A receptacle (sold separately) to the
50A adapter base.
NOTE: Use two (2) hex nuts (included) to secure
receptacle in place.
Tunnel
Mounting Bracket
Divider
End Cap
Module Back Plate
Receptacle
NOTE: Adapter is designed for 50A devices only.
Step 2. The EFB-50A Adapter is directional and can only
be used on the side shown.
EFB810S-TUN
Metal Tunnel
EFB810-TUN
Plastic Tunnel
NOTE: 50A Device will be pointed at the tunnel
(EFB810-TUN).
Step 5. Knock out the appropriate KO (See Below). Attach
wires to the EFB-50A per National Electric Code
using the provided ground lug (Not shown). Install
5
0A adapter base to the module backplate using
the supplied white screw.
Step 6. Attach covers to the 50A adapter base and
module back plate.
Module Back
Plate Cover
50A Adapter
Base Cover
Module
Back Plate
50A Adapter Base
1 1/4" Trade
Size KO
2" Trade
Size KO
1
1/4" Trade
S
ize KO
Step 7.
Remove the tunnel divider on the side of the 50A adapter base.
Cut off the divider shown at the score line with a hacksaw
WIREMOLD
U.S. and International:
60 Woodlawn Street West Hartford, CT 06110
1-800-621-0049 FAX 860-232-2062 Outside U.S.: 860-233-6251
Canada:
570 Applewood Crescent Vaughan, Ontario L4K 4B4
1-800-723-5175 FAX 905-738-9721
1 010 786 0212
© Copyright 2012 Legrand/Wiremold All Rights Reserved
When wiring a fire classified box, the conduit feed closest to
the 50 amp receptacle is the only one that can be used.
Conduit Feed
closest to 50A
receptacle
Step 9. Complete installation of box into the floor per the
instruction sheet provided with Evolution
Series
Floor Box.
SPECIAL NOTE WHEN USING EFB8S-FC OR EFB10S-FC
Step 8. Re-attach the tunnel cover.
Tunnel
NOTE: To maintain the UL Listing, the tunnel must be
installed when using the EFB-50A Adapter.
CAUTION: Make sure divider
has been removed to
ensure proper fit.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Legrand EFB10S-FC Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI