UNIT DESCRIPTION AND OPERATION
The WA-300 is a pass i ve infra red wall switch that turns lighting ON and OFF
based on occupancy and ambient light levels. SmartSet™ te c h n o logy allows the
sensor to be insta l l ed without any adjustments and auto m a t i ca l ly adjusts it to
the usage patterns in the space. Alte r n a te o perating modes, sele c t ed by DIP
s w i t ch settings, can be combined to cre a t e the ideal custom co n t rol.
The WA-300 co n tains two relays. Dual buttons on the front of the WA-300 allow
the user to co n t rol one or two loads independently. Pre s sing a button to g g l e s
the sta te of the co r responding relay, turning ON the load if it is curre n t l y OFF or
OFF if it is curre n t ly ON. If no motion is dete c ted during the time delay that is in
e f f ect, the load will turn OFF.
The WA-300 also co n tains a light level sensor that, when enabled, affects the
s e c ondary re l a y. If adequate daylight is present, the sensor holds the seco n d a r y
load OFF until light levels drop, even when the co n t r o l l ed area is occ u p i e d .
U s e rs can override this function by pre s sing the Relay 2 ON/OFF button. The
load will then remain ON until the space is unoccupied.
Turning The Load ON
The relays are pro g ram med independently for either Auto ON or Manual ON. In
either mode, the load can be turned ON or OFF using the ON/OFF butto n .
Load turns ON and OFF auto m a t i ca l l y based on occ u p a n c y. If the
load is turned OFF manually, as long as the sensor continues to
d e tect occupancy the load stays OFF. The lights stay OFF for five
m i n u t es after the last occupancy detection, then the sensor reve r t s
to the Auto ON mode. This prevents the load from auto m a t i ca l ly
turning ON after it was delibera t e l y turned OFF. Pre s sing the butto n
to turn the lights ON returns the sensor to the Auto ON mode.
Time Delays
The WA-300 holds the load ON until no motion is dete c ted for the sele c ted time
d e l a y. Select the time delay using DIP switch settings. The sensor auto m a t i ca l l y
sets the time delay when SmartSet is enabled; with the fixed time delay
settings you select a time delay between 5 to 30 minutes.
Both relays use the same delay, unle s s a delayed disconnect is enabled fo r
relay 2 using the “20 +10” delay fe a t u re. This delayed disconnect fe a t u r e is
useful in applications where you want both loads to turn OFF auto m a t i c a l ly, but
want relay 2 to stay ON longer, such as when running an ex h a u st fan after the
lights have shut OFF.
Manual
ON
O c cupants must turn ON the load by pre s sing the ON/OFF butto n .
The sensor keeps the load ON until no motion is dete c ted for the
s e l e c ted time delay. There is a 30 second reset delay. If motion is
d e te c ted during this time, the sensor turns the load back ON
a u t o m a t i ca l ly. After the reset delay time has elapsed, the ON/OFF
b u t t on must be pre s sed to turn ON the lo a d .