Bit tray
Product Information
Part no 6159935311
Issue no 01
Series no -
Date 01/2008
Page 3 / 4
Example:
Only module - parallel mode - BCD mode - Selection mode
BRIEF DESCRIPTION:
6 tool shafts are designed per module. The modules can be cascaded.
A maximum of 5 modules can be inserted together (corresponding to 30 tools).
During operation, no more than one tool at a time may be removed from the whole chain of the tool
change boxes (maximum of one tool shaft may be empty).
Each tool shaft contains one Hall sensor which can be used to detect the state "tool removed" or
"tool present".
In addition, there is an LED assigned to each shaft which visualises the state detected by the CPU
for the respective shaft.
SELECTION MODE
In selection mode, only the outputs of the bit tray are used.
As soon as a tool has been removed, the number of the respective tool is outputted on the parallel
interface in the set format (binary/BCD).
If no tool or more than one tool is removed, a 0 is outputted.
PRE-SELECTION MODE
In pre-selection mode the bit tray receives the number of the required tool shaft via the control
interface (parallel or serial).
The tool shaft can have the following states:
1. Tool is not to be removed, tool shaft is occupied. LED off.
2. Tool is not to be removed, tool shaft is empty. LED on (continuous light).
3. Tool is to be removed, tool shaft is occupied. LED flashes.
4. Tool is to be removed, tool shaft is empty. LED on (continuous light).
5. Tool is to be removed, tool shaft is empty but at least one further tool shaft is also empty.
DIP1 DIP2 DIP3 DIP4 Parallel mode: e.g. CVI (S/C)
X X OFF OFF Only module
X X OFF ON With additional module(s)
ON X OFF X BCD mode
OFF X OFF X Binary mode (if more than 15 cycles)
X ON OFF X Selection of operating mode (directly with CVI (S/C))
X OFF OFF X Pre-selection mode
DIP1 DIP2 DIP3 DIP4 Additional modules: serial/parallel mode
ON ON ON ON Not the last and not the only module
ON ON ON OFF Last module in the chain