Fluidwell F116 Owner's manual

Type
Owner's manual
The Netherlands The Netherlands Fluidwell bv - © 2022 FW_F116-P_M_v2201-01_EN.docx
F116-P
DIFFERENTIAL / SUM FLOW COMPUTER
with analog and pulse outputs
Signal input flowmeter: pulse, Namur and coil
Signal outputs: (0)4-20mA / 0-10V ref. flow rate and pulse ref. total and
negative flow
Options: Intrinsically safe, Modbus communication and backlight
F-Series - Field mounted indicators for safe and hazardous areas.
More info: www.fluidwell.com/fseries
FW_F116-P_M_v2201-01_EN.docx
Page 2
SAFETY INSTRUCTIONS
Any responsibility is lapsed if the instructions and procedures as described in this manual
are not followed.
LIFE SUPPORT APPLICATIONS: The F116-P is not designed for use in life support
appliances, devices, or systems where malfunction of the product can reasonably be
expected to result in a personal injury. Customers using or selling these products for use
in such applications do so at their own risk and agree to fully indemnify the manufacturer
and supplier for any damages resulting from such improper use or sale.
Electro static discharge does inflict irreparable damage to electronics! Before installing or
opening the F116-P, the installer has to discharge himself by touching a well-grounded
object.
The F116-P must be installed in accordance with the EMC guidelines (Electro Magnetic
Compatibility).
Connect a proper grounding to the metal enclosure as indicated if the F116-P has an
incoming power or signal line which carries a hazardous live voltage.
The Protective Earth (PE) wire may never be disconnected or removed.
Intrinsically Safe applications: follow the instructions as mentioned in Chapter 5.
Certificates and related documents are available on our website or from your distributor.
DISPOSAL OF ELECTRONIC WASTE
The WEEE Directive requires the recycling of disposed electrical and electronic
equipment in the European Union. When the WEEE Directive does not apply to your
region, we support its policy and ask you to be aware on how to dispose of this product.
The crossed out wheelie bin symbol as illustrated and found on our products tells that
this product shall not be disposed of into the general waste system or into a landfill.
At the end of its life, equipment shall be disposed of according to the local regulations
regarding waste of the electrical and the electronic equipment.

helpdesk for information on the product disposal.
SAFETY RULES AND PRECAUTIONARY MEASURES
The manufacturer accepts no responsibility whatsoever if the following safety rules and
precautions, instructions and the procedures as described in this manual are not
followed.
Modifications of the F116-P implemented without preceding written consent from the
manufacturer, will result in the immediate termination of product liability and warranty
period.
Mounting, electrical installation, start-up and maintenance of this device may only be
carried out by trained persons authorized by the operator of the facility. Persons must
read and understand this manual before carrying out its instructions.
This device may only be operated by persons who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Check the mains voltage and information on the manufacturer's plate before installing the
F116-P.
Check all connections, settings and technical specifications of the various peripheral
devices with the F116-P supplied.
Open the enclosure only if all leads are free of potential.
Never touch the electronic components (ESD sensitivity).
Never expose the system to heavier conditions than allowed according to the
classification of the enclosure (see manufacture's plate and chapter 4.2.).
If the operator detects errors or dangers, or disagrees with the safety precautions taken,
he should inform the owner or principal responsible.
The local labor and safety laws and regulations must be adhered to.
FW_F116-P_M_v2201-01_EN.docx
Page 3
ABOUT THE MANUAL
This manual is divided into two main sections:
The daily use of the unit is described in chapter 2 "Operation". These instructions are meant for
users.
The following chapters and appendices are exclusively meant for electricians/technicians. These
provide a detailed description of all software settings and hardware installation guidance.
This manual describes the standard unit as well as the available options. For additional information,
please contact your supplier.
A hazardous situation may occur if the F116-P is not used for the purpose it was designed for
or is used incorrectly. Please carefully note the information in this manual indicated by the
pictograms:
A "warning !" indicates actions or procedures which, if not performed correctly, may lead to
personal injury, a safety hazard or damage of the F116-P or connected instruments.
A "caution !" indicates actions or procedures which, if not performed correctly, may lead to
personal injury or incorrect functioning of the F116-P or connected instruments.
A "note !" indicates actions or procedures which, if not performed correctly, may indirectly
affect operation or may lead to an instrument response which is not planned.
WARRANTY AND TECHNICAL SUPPORT
For warranty and technical support for your products, please contact your supplier, visit our internet
site www.fluidwell.com or contact us at support@fluidwell.com.
Hardware version : 03.01.xx
Software version : 03.01.xx
Manual : FW_F116-P_M_v2201-01_EN.docx
© Copyright 2023 : Fluidwell B.V. - the Netherlands
Information in this manual is subject to change without prior notice. The
manufacturer is not responsible for mistakes in this material or for incidental
damage caused as a direct or indirect result of the delivery, performance or
use of this material.
© All rights reserved. No parts of this publication may be reproduced or used
in any form or by any means without written permission of your supplier.
FW_F116-P_M_v2201-01_EN.docx
Page 4
TABLE OF CONTENTS
SAFETY INSTRUCTIONS.................................................................................................................... 2
DISPOSAL OF ELECTRONIC WASTE ............................................................................................... 2
SAFETY RULES AND PRECAUTIONARY MEASURES ................................................................... 2
ABOUT THE MANUAL ........................................................................................................................ 3
WARRANTY AND TECHNICAL SUPPORT ........................................................................................ 3
TABLE OF CONTENTS ....................................................................................................................... 4
1 INTRODUCTION ........................................................................................................................ 6
1.1 System description ........................................................................................................... 6
2 OPERATIONAL ......................................................................................................................... 8
2.1 General information .......................................................................................................... 8
2.2 Control panel .................................................................................................................... 8
2.3 Operator information and functions .................................................................................. 8
3 CONFIGURATION ................................................................................................................... 10
3.1 Introduction ..................................................................................................................... 10
3.2 Programming SETUP-level ............................................................................................ 10
3.2.1 Entering SETUP-level ........................................................................................ 10
3.2.2 Navigating through SETUP-level ....................................................................... 10
3.2.3 Programming sequence ..................................................................................... 11
3.2.4 Returning to OPERATOR-level .......................................................................... 12
3.3 Configuration settings .................................................................................................... 12
3.3.1 Setup menu - Settings........................................................................................ 12
3.3.2 Menu 1 Total - A .............................................................................................. 13
3.3.3 Menu 2 - Flow rate - A ........................................................................................ 13
3.3.4 Menu 3 Total - B .............................................................................................. 14
3.3.5 Menu 4 Flow rate B ...................................................................................... 14
3.3.6 Menu 5 - Display ................................................................................................ 15
3.3.7 Menu 6 - Power management ............................................................................ 15
3.3.8 Menu 7 - Flowmeter ........................................................................................... 16
3.3.9 Menu 8 - Analog output ...................................................................................... 16
3.3.10 Menu 9 - Pulse output ...................................................................................... 18
3.3.11 Menu A - Communication (option) ................................................................... 18
3.3.12 Menu B - Others ............................................................................................... 18
4 INSTALLATION ....................................................................................................................... 19
4.1 General directions .......................................................................................................... 19
4.2 Installation - surrounding conditions .............................................................................. 19
4.3 Handling the F-Series Enclosure ................................................................................... 20
4.3.1 Identification ....................................................................................................... 20
4.3.2 Opening / removing the cover ............................................................................ 21
4.3.3 Closing / replacing the cover .............................................................................. 21
4.4 Mechanical installation ................................................................................................... 22
4.4.1 Dimensions Aluminum and stainless steel enclosures ................................... 22
4.4.2 Dimensions Non-metallic enclosures .............................................................. 23
4.4.3 Mounting ............................................................................................................ 24
4.5 Electrical installation ....................................................................................................... 25
4.5.1 Electrical safety .................................................................................................. 25
4.5.2 Protective Earth (PE) connections ..................................................................... 25
4.5.3 Field wiring connections ..................................................................................... 26
4.5.4 Power supply wiring ........................................................................................... 26
4.5.5 Sensor supply .................................................................................................... 27
4.6 Terminal connectors safe area applications Type XX / XF ......................................... 28
4.6.1 Terminal 00-02: Power supply ........................................................................... 28
4.6.2 Terminal 03-04: Pulse output R2 ....................................................................... 29
4.6.3 Terminal 05-06: pulse output R1 ........................................................................ 29
4.6.4 Terminal 07-08: Analog output ........................................................................... 30
4.6.5 Terminal 09-11: Flowmeter A input .................................................................... 32
4.6.6 Terminal 12-14: Flowmeter B input .................................................................... 34
4.6.7 Terminal 26-31: Type CB / CH / CI - Communication (option) ......................... 35
5 INTRINSICALLY SAFE APPLICATIONS ............................................................................... 36
5.1 Identification ................................................................................................................... 36
FW_F116-P_M_v2201-01_EN.docx
Page 5
5.2 Electrical installation in hazardous area ......................................................................... 37
5.2.1 General information and instructions .................................................................. 37
5.2.2 Installations based on ATEX or IECEx certificate .............................................. 38
5.2.3 Electrical data Annex 1 .................................................................................... 39
5.2.4 Power supply wiring ............................................................................................ 41
5.2.5 Sensor supply ..................................................................................................... 41
5.3 Terminal connectors Intrinsically Safe applications Type XI ....................................... 42
5.3.1 Terminal 26-29: Type CT - Communication ....................................................... 42
5.4 Configuration examples Intrinsically safe applications ................................................... 43
6 MAINTENANCE ........................................................................................................................ 45
6.1 General directions ........................................................................................................... 45
6.2 Instructions for repair ...................................................................................................... 45
6.3 Battery replacement instructions .................................................................................... 46
6.3.1 Safety instructions .............................................................................................. 46
6.3.2 Replace the battery ............................................................................................. 47
6.3.3 Disposal of batteries ........................................................................................... 47
APPENDIX A TECHNICAL SPECIFICATION ................................................................................. 48
APPENDIX B PROBLEM SOLVING ............................................................................................... 51
APPENDIX C COMMUNICATION VARIABLES ............................................................................. 52
APPENDIX D DECLARATION OF CONFORMITY ......................................................................... 56
INDEX OF THIS MANUAL.................................................................................................................. 57
LIST OF FIGURES IN THIS MANUAL ............................................................................................... 58
FW_F116-P_M_v2201-01_EN.docx
Page 6
1 INTRODUCTION
1.1 SYSTEM DESCRIPTION
Functions and features
The flow rate / totalizer model F116-P is a microprocessor driven instrument designed to show the
flow rate, the total and the accumulated total of two flow meter inputs, and to calculate and show the
differential or summed flow rate and total.
This product has been designed with a focus on:
ultra-low power consumption to allow long-life battery powered applications (type PB/PC)
intrinsic safety for use in hazardous applications (type XI)
several mounting possibilities with aluminum or GRP enclosures for harsh industrial
surroundings
ability to process all types of flowmeter signals
transmitting possibilities with analog / pulse and communication outputs.
Flowmeter input
This manual describes the unit with a pulse input from the flowmeters.
Two flowmeters with a passive or active pulse, Namur or sine wave (coil) signal output can be
connected to the F116-P. To power the sensors, several options are available.
Standard outputs
Pulse output to transmit a pulse that represents a totalized quantity as programmed.
Linear (0)4-20mA or 0-10V analog output to represent the actual flow rate as programmed. The
(0)4-20mA or 0-10V signal limits can be tuned.
Fig. 1: Typical application
FW_F116-P_M_v2201-01_EN.docx
Page 7
Configuration of the unit
The F116-P is designed for use in many types of applications. For that reason, a setup menu is
available to program the F116-P according to your specific requirements.
The setup includes several important features, such as K-Factors, engineering units, signal
selection, power management (to extend battery life-time), etc. All settings are stored in a non-
volatile memory and therefore saved in the event of a power failure or an exhausted battery.
Display information
The unit has a LCD with (optional) backlight to show the process information, status and alarm
messages. The display refresh rate is programmed in the setup menu.
At a key press, the display refresh rate will switch to FAST for 30 seconds. When 'OFF' is selected,
the display goes off after 30 seconds after the last key press. The display temporarily comes on after
a key press.
A backup of the total and accumulated total in EEPROM memory is made every minute.
Options
The following options are available: isolated or active (0)4-20mA / 0-10V analog output, full Modbus
communication RS232/485/TTL (also battery powered), intrinsic safety, mechanical relay or active
output, power- and sensor-supply options, panel mount, wall mount and weather proof enclosures,
flame proof enclosure and LED backlight.
FW_F116-P_M_v2201-01_EN.docx
Page 8
2 OPERATIONAL
2.1 GENERAL INFORMATION
This chapter describes the daily use of the F116-P. This instruction is meant for users / operators.
This device may only be operated by persons who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Take careful notice of the "Safety rules, instructions and precautionary measures" in the
front of this manual.
2.2 CONTROL PANEL
The control panel has three keys. The following keys are available:
Fig. 2: Control panel.
Functions of the keys
PROG-key
This key is used to program and save new values or settings.
The PROG-key is also used to gain access to SETUP-level; please read chapter 3.
SELECT-key
This key is used to SELECT the displayed information, like accumulated total and flow
rate.
CLEAR-key
This key is used to CLEAR the value of total.
2.3 OPERATOR INFORMATION AND FUNCTIONS
In general, the F116-P will always function at Operator level. The information displayed is dependent
upon the SETUP-settings. The signal from the connected sensor is processed by the F116-P in the
background, whichever screen refresh rate setting is chosen. After pressing a key, the display will be
updated very quickly during a 30 second period, after which it will slow-down again.
Fig. 3: Example of display information during process.
For the Operator, the following functions are available:
Display differential or summed flow rate / total
This is the main display information of the F116-P. After the selection of any other information, it
will always return to this main display automatically. Total is shown on the upper line of the
display and flow rate on the bottom line. When selected in the setup menu, the display shows the
flow rate only. When you press the select key, the total shows momentarily.
When "-------" is shown, then the flow rate value is too high to be shown. The arrows indicate
the increase/decrease of the flow rate trend.
FW_F116-P_M_v2201-01_EN.docx
Page 9
Clear total
The value for total can be reset. To do so, press the CLEAR/ key twice. When the key is
pressed once, the text "PUSH CLEAR" is shown. To avoid a reset at this stage, press another
key other than the CLEAR/ key or wait for 20 seconds. A reset of the total does not influence
the accumulated total.
Display accumulated total
When the SELECT/ key is pressed, total and accumulated total are shown. The accumulated
total cannot be reset. The value will count up to 99,999,999,999. The unit and number of
decimals are shown according to the settings for the total.
Display Flow rate-A, Flow rate-B, (accumulated) total-A, (accumulated) total-B
The display can be configured to show the differential or summed flow rate. By pressing the
SELECT/
accumulated total A, flowrate B and accumulated total B.
Low-battery alarm
When the battery voltage drops, the "low-battery" icon will be displayed continuously. The battery
MUST be replaced shortly after!
The remaining lifetime after the first moment of indication is generally several days up to some
weeks. See paragraph 6.3 for further information on battery replacement.
Fig. 4: Example of low-battery alarm.
Alarm
When the alarm indicator is shown, refer to Appendix B: Problem Solving.
FW_F116-P_M_v2201-01_EN.docx
Page 10
3 CONFIGURATION
3.1 INTRODUCTION
This and the following chapters are exclusively meant for electricians and non-operators. In these,
an extensive description of all software settings and hardware connections are provided.
Mounting, electrical installation, start-up and maintenance of this device may only be
carried out by trained persons authorized by the operator of the facility. Persons must
read and understand this manual before carrying out its instructions.
This device may only be operated by persons who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Make sure, the measuring system is correctly wired up according to the wiring diagrams.
Protection against accidental contact is no longer assured when the enclosure cover is
removed or the panel cabinet has been opened (danger from electrical shock). The
enclosure may only be opened by trained persons authorized by the operator of the
facility.
Take careful notice of the "Safety rules, instructions and precautionary measures" in the
front of this manual.
3.2 PROGRAMMING SETUP-LEVEL
Changing the settings of the F116-P may have an influence on the current operation of the
device, even when SETUP-level is still active.
Make sure that the unit is not being used for any application when altering the settings.
3.2.1 ENTERING SETUP-LEVEL
Configuration of the F116-P is done at SETUP-level, which can be reached at all times while the
F116-P remains fully operational. At SETUP-level the display will deactivate the RUN indicator and
activate the SETUP indicator.
Use the control panel to access SETUP-level
PROG-key
To enter SETUP-level, press the PROG-key for 7 seconds at OPERATOR-level.
During this time, the symbols  will be displayed.
When SETUP-level is entered, a password might be required to continue. You can
enter the password by following the procedure for programming values as described in
the following paragraphs.
A password may be required to enter SETUP.
Without this password access to SETUP is denied.
3.2.2 NAVIGATING THROUGH SETUP-LEVEL
Each function has a unique menu-number, which is displayed below the SETUP indicator at the
bottom of the display. The menu-number is a combination of two figures, e.g. 1.2. The first number
indicates the function-group and the second number indicates the function. Additionally, each
function and function-group is expressed with a keyword.
Fig. 5: SETUP matrix structure
1.1
1.2
2.1.
2.1
1.3
2.2
3.1
3.
FUNCTION GROUP
FUNCTION
FW-4100-000001-001-EN
FW_F116-P_M_v2201-01_EN.docx
Page 11
Use the control panel to navigate through SETUP-level
PROG-key
When a function is selected, this key is used to start the programming sequence.
When only a function group is selected (and no function), this key is used to scroll back
a function group (e.g. 3 2 1 3).
SELECT-key
This key is used to select the next function in the list (e.g. 1 1.1 1.2 1). When
the top of the list is reached, it will wrap around and return to the function group
selection.
CLEAR-key
This key is used to select the previous function in the list (e.g. 1.2 1.1 1 2).
When the bottom of the list is reached, it will return to the function group selection.
When only a function group is selected (and no function), this key is used to scroll to
the next function group. (e.g. 1 2 3 1).
3.2.3 PROGRAMMING SEQUENCE
After selecting a function at SETUP-level, a new value can be programmed using the control panel.
A function either contains a value (a number with optionally a decimal point, e.g. 123.45) or a list
with items (e.g. Disable Enable).
For each function that needs to change, navigate to that function and follow the steps indicated
below. During the programming sequence, the display will deactivate the SETUP indicator and
activate the PROGRAM indicator.
When programming new values, alterations will only be set after the PROG-key has been
pressed to confirm the new value! (STEP 3)
Step 1: Starting the programming sequence
PROG-key
When a function is selected at SETUP-level, this key is used to start the programming
sequence.
Step 2a: Changing a value
SELECT-key
This key is used to increment the selected digit.
When the entered value is out of range, the increase sign or decrease-sign will
be displayed while you are programming. If this value is confirmed by pressing the
PROG-key, the value will be brought within a valid range automatically.
CLEAR-key
This key is used to select the next digit. If a decimal point can be set, this will be
included in the sequence as well (e.g. [decimal point] digit 1 digit 2 digit 3
[decimal point].
SELECT-key + CLEAR-key
The combination of the SELECT-key and CLEAR-key is used to select a negative
value. When a value can also be entered as a negative number, pressing the SELECT-
key and CLEAR-
Step 2b: Changing the selected item in a list
SELECT-key
This key is used to select the next item in the list (e.g. Disable Enable).
At the end of the list, the selection will wrap around to the first selection.
CLEAR-key
This key is used to select the previous item in the list (e.g. Enable Disable ).
At the bottom of the list, the selection will wrap around to the last selection.
Step 3: Finishing the programming sequence
PROG-key
During the programming sequence, this key is used to confirm the new value and
return to SETUP-level. To cancel the operation, either press the PROG-key for 3
seconds or wait for 20 seconds: the programming sequence is cancelled and the
former value is reinstated.
FW_F116-P_M_v2201-01_EN.docx
Page 12
3.2.4 RETURNING TO OPERATOR-LEVEL
When all settings are configured correctly, the unit can be returned to OPERATE-level.
Please keep a record of all settings for later reference.
Use the control panel to return to OPERATE-level
PROG-key
In order to return to the operator level, press the PROG-key for three seconds.
When no keys are pressed for 2 minutes, SETUP-level will be left automatically.
3.3 CONFIGURATION SETTINGS
All settings of the F116-P can be set via the control panel.
The following paragraphs give a detailed description of each setting.
3.3.1 SETUP MENU - SETTINGS
SETUP FUNCTIONS AND VARIABLES
1
TOTAL - A
1.1
UNIT
L; m3; kg; lb; GAL; USGAL; bbl; no unit
1.2
DECIMALS
0000000; 111111.1; 22222.22; 3333.333
1.3
K-FACTOR
0.000010 - 9999999
1.4
DECIMALS K-FACTOR
0 - 6
2
FLOW RATE - A
2.1
UNIT
mL; L; m3; mg; g; kg; ton; gal; bbl; lb; cf; rev; - - - - (no unit); scf; nm3; nL; p
2.2
TIME
/sec; /min; /hour; /day
2.3
DECIMALS
0000000; 111111.1; 22222.22; 3333.333
2.4
K-FACTOR
0.000010 - 9,999,999
2.5
DECIMALS K-FACTOR
0 - 6
2.6
FILTER
0 - 99
2.7
PERIOD
0.1 99.9 seconds
3
TOTAL - B
3.1
K-FACTOR
0.000010 - 9999999
3.2
DECIMALS K-FACTOR
0 - 6
4
FLOW RATE - B
4.1
K-FACTOR
0.000010 - 9,999,999
4.2
DECIMALS K-FACTOR
0 - 6
5
DISPLAY
5.1
FUNCTION
total; rate; all
5.2
LIGHT
0% (off); 20%; 40%; 60%; 80%; 100% (full brightness)
5.3
CALCULATE
add; differ
5.4
MEASUREMENT
bi-direct, not negative, threshold, stationary
5.5
STATIONARY FLOW RATE
0000.000 9999999
5.6
STATIONARY TOTAL
0000.000 9999.999
6
POWER MANAGEMENT
6.1
LCD NEW
fast; 1 sec; 3 sec; 15 sec; 30 sec; off
6.2
BATTERY MODE
operational; shelf
7
FLOWMETER
7.1
SIGNAL A
npn; npn-lp; reed; reed-lp; pnp; pnp-lp; namur; coil-hi; coil-lo; 8-1 DC; 12 DC; 24 DC
7.2
SIGNAL B
npn; npn-lp; reed; reed-lp; pnp; pnp-lp; namur; coil-hi; coil-lo; 8-1 DC; 12 DC; 24 DC
8
ANALOG
8.1
OUTPUT
disable; enable
8.2
RATE-MIN
000.000 - 999999
8.3
RATE-MAX
000.000 - 999999
8.4
CUT-OFF
0.0 - 9.9%
8.5
TUNE-MIN
0 - 9999
8.6
TUNE-MAX
0 - 9999
8.7
FILTER
01 - 99
9
PULSE
9.1
MODE
signed, not negative, separated
9.2
WIDTH
0.001 - 9.999
9.3
DECIMALS
0000000; 111111.1; 22222.22; 3333.333
9.4
AMOUNT
0.001 - 9999999
FW_F116-P_M_v2201-01_EN.docx
Page 13
A
COMMUNICATION
A.1
SPEED
1200; 2400; 4800; 9600
A.2
ADDRESS
1 255
A.3
MODE
bus-rtu; bus-asc; off
B
OTHERS
B.1
MODEL
F116-P
B.2
SOFTWARE VERSION
nn:nn:nn
B.3
SERIAL NO.
nnnnnnn
B.4
PASSWORD
0000 - 9999
B.5
TAG-NR
0000000 - 9999999
3.3.2 MENU 1 TOTAL - A
1
TOTAL- A
1.1
UNIT
This setting is used to select the engineering unit for the indication of the
(accumulated) totals, both for input A and B, and the pulse output.
When you change the engineering unit, you must recalculate and
reprogram the K-factor for the (accumulated) total. When you recalculate
and reprogram the K-Factor, the history for (accumulated) total is not
correct anymore, because the (accumulated) total is not recalculated. For
future reference, best practice is to make a note of the accumulated total
before you program the recalculated K-Factor.
1.2
DECIMALS
This setting is used to set the amount of digits behind the decimal point for
the (accumulated) totals indication, both for input A and B.
1.3
K-FACTOR
This setting is used to set the K-Factor for the total of input A. With the K-
Factor, the flowmeter pulse signals are converted to a quantity. The K-
Factor is based on the number of pulses generated by the flowmeter per
selected engineering unit, for example m3. A more accurate K-Factor (more
decimals, as set in decimals K-Factor) allows for a more accurate
operation of the system.
Example 1: Calculating the K-Factor.
The flowmeter generates 2.4813 pulses per liter and the selected unit is
m3. A cubic meter consists of 1000 liter which gives 2.4813 pulses*1000
liter=2481.3 pulses per m3. So, the K-Factor is 2481.3. Enter for the
Flowmeter K-Factor: 24813 and for the flowmeter K-Factor decimals: 1.
Example 2: Calculating the K-Factor.
The flowmeter generates 6.5231 pulses per gallon and the selected
engineering unit is gallons. So, the K-Factor is 6.5231. Enter for the
Flowmeter K-Factor: 65231 and for the Flowmeter K-Factor decimals: 4.
When you recalculate and reprogram a new K-Factor, the history for
(accumulated) total is not correct anymore, because the (accumulated)
total is not recalculated. For future reference, best practice is to make a
note of the accumulated total before you program the recalculated K-
Factor.
1.4
DECIMALS K-
FACTOR
This setting is used to set the amount of digits behind the decimal point for
the K-Factor setting for input A.
3.3.3 MENU 2 - FLOW RATE - A
The settings for total and flow rate are entirely separate. In this way, different engineering units can
be used for each e.g. cubic meters for total and liters for flow rate.
2
FLOW RATE - A
2.1
UNIT
This setting is used to select the engineering unit for the indication of the
flow rates of input A and B.
Alteration of the engineering unit will have consequences for operator and
setup values, they will not be automatically recalculated to the value of the
new selected unit. The K-Factor has to be adapted as well; the calculation
is not done automatically.
2.2
TIME
This setting is used to set the time unit for the flow rate calculation of inputs
A and B. Note that the flow rate is given in engineering unit/time unit, e.g.
liters/minute (l/min).
When you change this setting, also recalculate and change the settings for
the analog rate-min and analog rate-max.
FW_F116-P_M_v2201-01_EN.docx
Page 14
2.3
DECIMALS
This setting is used to set the amount of digits behind the decimal point for
the flow rate indication of input A and B.
2.4
K-FACTOR
This setting is used to set the K-Factor for the flow rate of input A. With the
K-Factor, the flowmeter pulse signals are converted to a quantity. The K-
Factor is based on the number of pulses generated by the flowmeter per
selected engineering unit, for example m3. A more accurate K-Factor (more
decimals, as set in decimals K-Factor) allows for a more accurate
operation of the system.
2.5
DECIMALS K-
FACTOR
This setting is used to set the amount of digits behind the decimal point for
the K-Factor of input A.
2.6
FILTER
This setting is used to stabilize the output signal. With the help of this
digital filter a more stable but less actual representation of the flow rate can
be obtained.
The filter principal is based on three input values: the filter level (01 99), the
last calculated flow rate and the last average value. The higher the filter
level, the longer the response time on a value change will be.
2.7
PERIOD
This setting is used to calculate the flow rate by counting the number of
pulses within a certain time, for example 1 second. The longer the time the
more accurate the flow rate will be.
This setting does influence the update interval for the flowrate and thus the
update interval of the analog output. If the output response is too slow,
decrease the period.
3.3.4 MENU 3 TOTAL - B
Engineering units for input B are the same as set for input A (Setup Menu 1)
3
TOTAL - B
3.1
K-FACTOR
This setting is used to set the K-Factor for the total (B). With the K-Factor,
the flowmeter pulse signals are converted to a quantity. The K-Factor is
based on the number of pulses generated by the flowmeter per selected
engineering unit, for example per m3. A more accurate K-Factor (more
decimals, as set in decimals K-Factor) allows for a more accurate
operation of the system.
3.2
DECIMALS K-
FACTOR
This setting is used to set the amount of digits behind the decimal point for
the K-factor of total - B.
3.3.5 MENU 4 FLOW RATE B
Engineering units for input B are the same as set for input A (Setup Menu 1)
4
FLOW RATE - B
4.1
K-FACTOR
This setting is used to set the K-Factor for the flow rate (B). With the K-
Factor, the flowmeter pulse signals are converted to a quantity. The K-
Factor is based on the number of pulses generated by the flowmeter per
selected engineering unit, for example per m3. A more accurate K-Factor
(more decimals, as set in decimals K-Factor) allows for a more accurate
operation of the system.
4.2
DECIMALS K-
FACTOR
This setting is used to set the amount of digits behind the decimal point for
the K-factor of flow rate - B.
FW_F116-P_M_v2201-01_EN.docx
Page 15
3.3.6 MENU 5 - DISPLAY
5
DISPLAY
5.1
FUNCTION
Selects the display of (differential or summed) total or rate.
TOTAL
total and flow rate are shown simultaneously. When SELECT is pressed,
the accumulated total is shown temporarily.
RATE
flow rate is shown with its engineering unit. When SELECT is pressed, the
total and the accumulated total are shown temporarily.
ALL
flow rate is shown with its engineering unit. When SELECT is pressed, the
total/accumulated total, the flow rate A, the accumulated total A, the flow
rate B and the accumulated total B are shown temporarily.
5.2
LIGHT
The backlight brightness can be adjusted from 0% (off) to 100% (full
brightness) in steps of 20%.
When the F116-P is only loop powered, the backlight is disabled. An
external power supply is required to supply the backlight.
5.3
CALCULATE
DIFFERENTIAL Flow rate/total are calculated as input A input B
ADD Flow rate/total are calculated as input A + input B.
5.4
MEASUREMENT
To solve undesired display readings during low or even negative
consumption situations, four different measurement methods are available.
The following choices can be made for handling positive or negative flow.
Flow rate shown as:
Total shown as:
BI-DIRECTIONAL
Positive or negative
Increasing or decreasing
NOT-NEGATIVE
Positive or zero
Increasing or decreasing
THRESHOLD
Positive when greater than threshold
set at Setup 5.5, else zero.
Increasing when flow is greater then
threshold set at Setup 5.5, else
stopped.
STATIONARY
Fixed value as set at Setup 5.5
when lower than threshold set at
Setup 5.5
Fixed increase as set at Setup 5.6
when flow is lower than threshold
set at Setup 5.5.
Note: when Setup 5.6 is set at zero,
total is calculated as bi-directional.
This setting does influence the analog output value as well.
5.5
STATIONARY
FLOW RATE
Sets the value used with Setup 5.4 THRESHOLD or STATIONARY.
Displayed flow rate will always be zero when no pulses are input.
5.6
STATIONARY
TOTAL
Sets the value used with Setup 5.4 STATIONARY for calculating the total
while flow rate is below the setting of 5.5.
Totalization will stop when no pulses are input.
Entering zero will disable stationary totalization.
3.3.7 MENU 6 - POWER MANAGEMENT
When used with the internal battery option (type PB/PC), the user can expect reliable measurement
over a long period of time. The F116-P has several smart power management functions to extend
the battery life time significantly. Two of these functions can be set.
6
POWER MANAGEMENT
6.1
LCD NEW
Calculation of the display-information influences the power consumption
significantly. When a fast display refresh rate is not necessary, it is strongly
advised to select a slow rate. Please understand that NO information will
be lost; every pulse will be counted and the output signals will be
generated in the normal way.
At a key press, the display refresh rate will switch to FAST for 30 seconds.
When 'OFF' is selected, the display goes off after 30 seconds after the last
key press. The display temporarily comes on after a key press.
Example battery life-time with a coil pick-up:
1kHz pulse and FAST update: about 2 years;
1kHz pulse and 1 sec update: about 5 years.
FW_F116-P_M_v2201-01_EN.docx
Page 16
6.2
BATTERY MODE
The F116-P has two modes: operational or shelf.
After "shelf" has been selected, the F116-P can be stored for several
years; it will not process the sensor signal; the display is switched off but all
settings and totals are stored. In this mode, power consumption is
extremely low.
To wake up the F116-P again, press the SELECT/ key two times.
3.3.8 MENU 7 - FLOWMETER
7
FLOWMETER
7.1
SIGNAL A
With this setting the type of flowmeter A output is selected. The settings
with LP (low-pass) filter are used to apply a build-in noise reduction.
Selections "active pulse" offer a detection level of 50% of the supply
voltage.
TYPE OF SIGNAL
EXPLANATION
RESISTANCE
FREQ. / mVPP
REMARK
NPN
NPN input
100 kΩ pull-up
max. 6 kHz.
(open collector)
NPN - LP
NPN with low pass
filter
100 kΩ pull-up
max. 1.2 kHz.
(open collector) less
sensitive
REED
Reed-switch input
1 MΩ pull-up
max. 1.2 kHz.
REED - LP
Reed-with low pass
filter
1 MΩ pull-up
max. 120 Hz.
Less sensitive
PNP
PNP input
100 k pull-down
max. 6 kHz.
PNP - LP
PNP with low pass
filter
100 k pull-down
max. 1.2 kHz.
Less sensitive
NAMUR
NAMUR input
820 pull-down
max. 4 kHz.
External power
required
COIL-HI
High sensitive coil
input
-
min. 20 mVpp
Sensitive for
interference!
COIL-HI (type ZF)
min. 10 mVpp
COIL-HI (type ZG)
min. 5 mVpp
COIL LO
Low sensitive coil
input
-
min. 80 mVpp
Normal sensitivity
8-1 DC
Active pulse input
detection level 8.2 V
DC
3k9
max. 10 kHz.
External power
required
12 DC
Active pulse input
detection level 12 V
DC
4 k
max. 10 kHz.
External power
required
24 DC
Active pulse input
detection level 24 V
DC
3 k
max. 10 kHz.
External power
required
7.2
SIGNAL B
Selects the output type of flowmeter B. For description of the options, see
explanation at menu 7.1 SIGNAL A.
3.3.9 MENU 8 - ANALOG OUTPUT
A linear 4-20 mA signal (option AB: 0-20 mA or option AU: 0-10 V) output signal is generated that
represents the (differential or summed) flow rate. The settings for the flow rate influence the analog
output directly. The relationship between the flow rate and the analog output is set with the following
settings.
8
ANALOG OUTPUT
8.1
OUTPUT
If the analog output is not used, select disable to minimize the power
consumption (e.g. save battery life-time).
Option AP: When a power supply is available but the output is disabled, a
3.5 mA signal will be generated.
8.2
RATE-MIN
Enter here the flow rate at which the output should generate the minimum
signal (0)4 mA or 0 V - in most applications at zero flow. The number of
decimals shown depend upon setup 2.3. The engineering units/time (e.g.
L/min) are dependent upon setup 2.1 and 2.2.
FW_F116-P_M_v2201-01_EN.docx
Page 17
8.3
RATE-MAX
Enter here the flow rate at which the output should generate the maximum
signal (20 mA or 10 V) - in most applications at maximum flow. The
number of decimals shown depend upon setup 2.3. The engineering
units/time (e.g. L/min) are dependent upon setup 2.1 and 2.2.
8.4
CUT-OFF
A low flow cut-off, e.g. to ignore leakage, can be set as a percentage of the
full range of 16 mA, 20 mA or 10 V.
When the flow is less than the required rate, the current will be the
minimum signal (4 mA, 0 mA, 0 V). Example:
RATE-MIN
4 mA
RATE-MAX
20 mA
CUT-OFF
%
REQUIRED RATE
OUTPUT
0 L/min
100 L/min
2%
(100-0)*2% = 2.0 L/min
4+(16*2%) = 4.32 mA
20 L/min
800 L/min
3.5%
(800-20)*3.5%= 27.3 L/min
4+(16*3.5%)=4.56 mA
8.5
TUNE-MIN
The (0)4 mA or 0 V value can be tuned precisely with this setting. The
initial minimum analog output value is (0) 4mA or 0 V. However, this value
might differ slightly due to ambient influences such as temperature for
example.
Before tuning the signal, make sure that the analog signal is idle (not
used) for any application!
After pressing PROG, the current will be about 4 mA (0 mA or 0 V). The
current can be increased / decreased with the arrow keys and is directly
active. Press ENTER to store the new value.
If required, you can program the analog output 'up-side-down'. The (0)4
mA or 0 V represents the maximum flow rate and the 20 mA or 10 V
represents the minimum flow rate.
8.6
TUNE-MAX
The 20 mA or 10 V value can be tuned precisely with this setting. The initial
maximum analog output value is 20 mA or 10 V However, this value might
differ slightly due to ambient influences such as temperature for example.
Before tuning the signal, make sure that the analog signal is idle (not
used) for any application!
After pressing PROG, the current will be about 20 mA or 10 V. The current
can be increased / decreased with the arrow keys and is directly active.
Press ENTER to store the new value.
If required, you can program the analog output 'up-side-down'. The (0)4
mA or 0 V represents the maximum flow rate and the 20 mA or 10 V
represents the minimum flow rate.
8.7
FILTER
This setting is used to stabilize the output signal. With the help of this
digital filter a more stable but less actual representation of the flow rate can
be obtained.
The filter principal is based on three input values: the filter level (01-99),
the last calculated flow rate and the last average value. The higher the filter
level, the longer the response time on a value change will be.
FILTER VALUE
RESPONSE TIME ON STEP CHANGE OF ANALOG VALUE (% OF END VALUE)
50%
75%
90%
99%
01
filter disabled
filter disabled
filter disabled
filter disabled
02
0.1 sec
0.2 sec
0.4 sec
0.7 sec
03
0.2 sec
0.4 sec
0.6 sec
1.2 sec
05
0.4 sec
0.7 sec
1.1 sec
2.1 sec
10
0.7 sec
1.4 sec
2.2 sec
4.4 sec
20
1.4 sec
2.8 sec
4.5 sec
9.0 sec
30
2.1 sec
4 sec
7 sec
14 sec
50
3.5 sec
7 sec
11 sec
23 sec
75
5.2 sec
10 sec
17 sec
34 sec
99
6.9 sec
14 sec
23 sec
45 sec
FW_F116-P_M_v2201-01_EN.docx
Page 18
3.3.10 MENU 9 - PULSE OUTPUT
One transistor or mechanic relay output is available as a scaled pulse output according to
accumulated total.
9
PULSE OUTPUT
9.1
MODE
The unit has two pulse outputs. The relation of the outputs and the
measured total and the flow direction can be set as follows.
Pulse output R1:
Pulse output R2:
SIGNED
Pulse when total has increased or
decreased with quantity set at Setup
9.4 AMOUNT.
Low when flow is positive (total
increases)
High when flow is negative (total
decreases)
NOT NEGATIVE
Pulse when total has increased with
quantity set at Setup 9.4 AMOUNT.
Low when flow is positive
High when flow is negative
SEPARATED
Pulse when total has increased with
quantity set at Setup 9.4 AMOUNT.
Pulse when total has decreased with
quantity set at Setup 9.4 AMOUNT.
9.2
WIDTH
The pulse width determines the time that the output will be active; in other

The pulse signal always has a 50% duty cycle, hence the minimum time
between the pulses is equal to the pulse width setting. If the frequency
should go out of range when the flow rate increases for example an

flow rate slows down, the buffer will 
It might be that pulses will be missed due to a buffer-overflow, so it is
advised to program this setting within its range!
9.3
DECIMALS
This setting is used to set the number of digits behind the decimal point for
Setup 9.4 AMOUNT.
9.4
AMOUNT
Enter a quantity to be used with Setup 9.1 MODE. The number of decimals
is set at 9.3 DECIMALS.
3.3.11 MENU A - COMMUNICATION (OPTION)
The F116-P can optionally be equipped with a communication interface using the Modbus protocol
(Type CB/CH/CI/CT). Please consult Appendix C for a more detailed explanation of the protocol,
data types and available registers.
A
COMMUNICATION
A.1
SPEED
This setting is used to set the baud rate and should match the speed used
on the communications bus.
The following communication speeds can be selected:
1200 2400 4800 9600
A.2
ADDRESS
This setting is used to configure the bus address of your device on the
communications bus. This address can vary from 001-255.
A.3
MODE
This setting is used to configure the Modbus communication mode of your
device on the communications bus.
The following modes can be selected: ASCII RTU OFF
3.3.12 MENU B - OTHERS
B
OTHERS
B.1
MODEL
For support and maintenance it is important to have information about the
characteristics of the F116-P. Your supplier will ask for this information in
the case of a serious breakdown or to assess the suitability of your model
for upgrade considerations.
B.2
SOFTWARE
VERSION
B.3
SERIAL NO.
B.4
PASSWORD
All SETUP values can be password protected.
This protection is disabled with value 0000 (zero).
A 4 digit password can be programmed, for example 1234.
B.5
TAG-NR
For identification of the unit and communication purposes, a unique tag
number of maximum 7 digits can be entered.
FW_F116-P_M_v2201-01_EN.docx
Page 19
4 INSTALLATION
4.1 GENERAL DIRECTIONS
Mounting, electrical installation, start-up and maintenance of this device may only be
carried out by trained persons authorized by the operator of the facility. Persons must
read and understand this manual before carrying out its instructions.
The F116-P may only be operated by persons who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Ensure that the measuring system is correctly wired up according to the wiring diagrams.
Protection against accidental contact is no longer assured when the enclosure cover is
removed or the panel cabinet has been opened (danger from electrical shock). The
enclosure may only be opened by trained personnel.
Take careful notice of the "Safety rules, instructions and precautionary measures" at the
front of this manual.
The F1-Series can be supplied as suitable for Safe Area or Hazardous Area. This is indicated in the
model code (shown on the product label) by the Type X* designator, with following options:
Type XX: Suitable for safe area applications only (e.g. F116-P-XX)
Follow the mechanical and electrical installation instructions shown in chapter 4.
Type XF: Suitable for explosion proof / flame proof applications (e.g. F116-P-XF)
Follow the electrical installation instructions as shown in chapter 4 and
the mechanical installation instructions of the enclosure that are supplied separately.
Type XI: Suitable for intrinsically safe applications (e.g. F116-P-XI)
Follow the general mechanical and electrical installation instructions of chapter 4
and the specific installation instructions of chapter 5.
4.2 INSTALLATION - SURROUNDING CONDITIONS
Take the relevant IP classification of the
enclosure into account (see identification plate).
Even an enclosure rated for IP67 / TYPE 4(X)
should NEVER be exposed to strongly varying
(weather) conditions.
When used in very cold surroundings or varying
climatic conditions, inside the instrument case,
take the necessary precautions against moisture.
Mount the F-Series onto a solid structure to avoid
vibrations.
For use in Safe and Hazardous Areas (or Locations), the following conditions apply:
Relative humidity:
< 90% RH
Outdoor use:
suitable for outdoor use
IP and TYPE rating:
IP65 (panel mount), IP67 (field mount) and Type 4X
Supply voltage fluctuation:
As indicated by the supply range (e.g. 10V to 30V),
otherwise +/- 10% unless stated otherwise
Means of protection:
Intrinsically safe:
IS
Ordinary locations:
Class I (PE connected metal enclosure)
Class II (non-metallic enclosure)
Over-voltage category:
II (when supplied from mains)
Pollution degree:
2 (internal environment), 3 (external environment)
Ambient:
Intrinsically safe:
-40 °C to +70 °C, -40 °F to +158 °F
(limited to +50 °C, 122 °F for EPL Da)
Ordinary locations:
-40 °C to +80 °C, -40 °F to +176 °F
Altitude:
up to 2000 m
FW_F116-P_M_v2201-01_EN.docx
Page 20
4.3 HANDLING THE F-SERIES ENCLOSURE
4.3.1 IDENTIFICATION
The F1-Series can be supplied as suitable for Safe Area or Hazardous Area.
Suitability for Intrinsic Safety is indicated in the model code by Type XI (e.g. F116-P-XI).
For Intrinsically Safe applications: Installation and identification labels are shown in chapter 5.
Identification label
To identify your F1-Series device, all field mount enclosures have a weatherproof identification label
placed on the outside of the unit.
Fig. 6: Identification Example of F1-Series identification label (safe area)
Installation label
A second label is located on the inside and shows additional installation data. For panel mount
enclosures, the outside label is not available, so the inside label also serves as identification label.
After installation, the inside label is only visible from the rear side of the panel.
Fig. 7: Identification Example of F1-Series installation label (safe area)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60

Fluidwell F116 Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI