Eaton COOPER POWER SERIES Installation guide

Type
Installation guide

Eaton COOPER POWER SERIES 600 A 35 kV class PUSH-OP bushing adapter is a factory-assembled device that meets IEEE Std 386-2006 standards. It eliminates threading and associated problems with its non-bolted connection. This adapter is used to cap a 600 A PUSH-OP type bushing tap interface, allowing for live testing and visible grounding. It provides a fully shielded, submersible unit when used with an Eaton Cooper Power series 200 A insulated protective cap, M.O.V.E. arrester, or grounding elbow.

Eaton COOPER POWER SERIES 600 A 35 kV class PUSH-OP bushing adapter is a factory-assembled device that meets IEEE Std 386-2006 standards. It eliminates threading and associated problems with its non-bolted connection. This adapter is used to cap a 600 A PUSH-OP type bushing tap interface, allowing for live testing and visible grounding. It provides a fully shielded, submersible unit when used with an Eaton Cooper Power series 200 A insulated protective cap, M.O.V.E. arrester, or grounding elbow.

General
Eaton's Cooper Power™ series 600 A, 35 kV
Class PUSH-OP™ bushing adapter is a factory
as sembled LRTP and extender with a stainless
steel shroud and tin-plated copper probe. It meets
all the requirements of IEEE Std 386™-2006
standard – Separable Connector Sys tems.
The PUSH-OP bushing adapter has a non-bolted
connection that eliminates any need for threading
and its associated problems.
The device is used to cap a 600 A PUSH-OP type
bushing tap inter face with Eaton's Cooper Power
series 200 A loadbreak interface allowing for live
testing and visible grounding. The 200 A tap is
single-phase switch ing and three-phase fault close
rated. Used with an Eaton's Cooper Power series
200 A insulated pro tec tive cap, M.O.V.E. arrester
or ground ing elbow, a PUSH-OP bushing adapter
provides a fully shielded, submersible unit.
Installation
The PUSH-OP bushing adapter is installed
on a de-energized 600 A PUSH-OP bushing
inter face using a clampstick. Refer to Service
Information S600-19-1 600 A 15, 25, and 35 kV
Class PUSH-OP Bushing Adapter Cap Installation
Instructions for details. Installation of the factory
assembled LRTP and extender to the 600 A
PUSH-OP bushing requires no threading.
Production tests
Tests are conducted in accordance with IEEE Std
386™-2006 standard.
ac 60 Hz 1 Minute Withstand
50 kV
Minimum Corona Voltage Level
26 kV
Tests are conducted in accordance with Eaton
requirements.
Physical In spec tion
Periodic Dissection
Periodic Fluoroscopic Analysis
600 A 35 kV class PUSH-OP
bushing adapter
Deadbreak Connectors
Catalog Data
CA650 056EN
Effective May 2015
Supersedes 600-58 February 2000
COOPER POWER
SERIES
Ordering information
To order a 35 kV Class PUSH-OP Insulated Bushing Adapter Kit, refer
to Table 3.
Each kit contains:
Assembled Bushing Adapter
Shipping Cap (not for energized operation)
Silicone Lubricant
Installation Instruction Sheet
Figure 1. Cutaway illustration shows design detail and dimensions.
ote:N Dimensions given are for reference only.
COPPER PROBE
Field Replaceable Tin Plated
Copper Probe ensures
reliable electrical connection.
LOADBREAK
REDUCING
TAP PLUG
200 A INTERFACE
CATCH ASSEMBLY
Prevents unit from falling when
removed from PUSH-OP
bushing.
SEMICONDUCTING SHIELD
High Quality Peroxide Cured
Semiconducting EPDM Shield
meets the requirements of IEEE
Std 592™-2007 standard.
DRAIN WIRE
48 Inch #14 Stranded Plated Copper
Drain Wire Lead ensures deadfront
construction and avoids low energy
discharge from the molded semiconducting
shields.
SERIES 300 SHROUD
Stainless Steel Shroud provides
clampstick pulling eye and
locating pins for PUSH-OP type
bushing.
600 A
PUSH-OP
BUSHING
LOCATING
PINS
9.07"
(231 mm)
17.9 "
(456 mm)
HOTSTICK
EYE
Table 3. Insulated Bushing Adapter Kits
Description Catalog Number
Bushing Adapter PDBA635
Bushing Adapter w/200 A Insulated Protective Cap PDBA635C
Table 4. Replacement Parts
Description Catalog Number
Loadbreak Reducing Tap Plug LRTP635
Probe 2638198B01B
Catch Assembly 2638191B01
Table 1. Voltage Ratings and Characteristics
Description kV
Standard Voltage Class 35
Maximum Rating Phase-to-Phase (LRTP 200 A interface only) 21.1
Maximum Rating Phase-to-Ground 21.1
ac 60 Hz 1 Minute Withstand 50
dc 15 Minute Withstand 103
BIL and Full Wave Crest 150
Minimum Corona Voltage Level 26
Voltage ratings and characteristics are in accordance with IEEE Std 386™-2006 standard.
Table 2. Current Ratings and Characteristics
Description Amperes
200 A Interface*
Continuous 200 A rms
Switching** 10 operations at 200 A rms at 21.1 kV
Fault Closure 10,000 A rms symmetrical at 36.6 kV after 10 switching operations for 0.17 s
Short Time 10,000 A rms symmetrical for 0.17 s
3,500 A rms symmetrical for 3.0 s
Current ratings and characteristics are in ac cor dance with IEEE Std 386™-2006 standard.
* If available system fault current exceeds 10 kA, current limiting fusing must be used upstream,
otherwise fault close and short time ratings of the 200 A interface will be exceeded.
** Switching rating limited to single-phase 21.1 kV.
600 A 35 kV class PUSH-OP bushing adapterCatalog Data CA650056EN
Effective May 2015
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Power Systems Division
2300 Badger Drive
Waukesha, WI 53188
United States
Eaton.com/cooperpowerseries
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. CA650056EN
For Eaton's Cooper Power series PUSH-OP
connector product information
call 1-877-277-4636 or visit:
www.eaton.com/cooperpowerseries.
Eaton, Cooper Power, and PUSH-OP are
valuable trademarks of Eaton in the U.S. and
other countries. You are not permitted to
use these trademarks without prior written
consent of Eaton.
IEEE Std 386™-2006 and IEEE Std 592™-
2007 standards are trademarks of the Institute
of Electrical and Electronics Engineers,
Inc. (IEEE). This publication/product is not
endorsed or approved by the IEEE.
  • Page 1 1
  • Page 2 2

Eaton COOPER POWER SERIES Installation guide

Type
Installation guide

Eaton COOPER POWER SERIES 600 A 35 kV class PUSH-OP bushing adapter is a factory-assembled device that meets IEEE Std 386-2006 standards. It eliminates threading and associated problems with its non-bolted connection. This adapter is used to cap a 600 A PUSH-OP type bushing tap interface, allowing for live testing and visible grounding. It provides a fully shielded, submersible unit when used with an Eaton Cooper Power series 200 A insulated protective cap, M.O.V.E. arrester, or grounding elbow.