Danfoss VLT AQUA Drive FC 202 Programming Guide

Type
Programming Guide

This manual is also suitable for

MAKING MODERN LIVING POSSIBLE
Programming Guide
VLT
®
AQUA Drive FC 200
Contents
1 Introduction
1-1
1.1.1 Approvals 1-1
1.1.2 Symbols 1-1
1.1.3 Abbreviations 1-1
1.1.4 Definitions 1-2
1.1.5 Electrical Wiring - Control Cables 1-6
2 How to Program
2-1
2.1 The Graphical and Numerical Local Control Panel
2-1
2.2 How to Program on the Graphical LCP
2-1
2.2.1 The LCP Display 2-2
2.2.2 Quick Transfer of Parameter Settings between Multiple Adjustable Fre-
quency Drives 2-4
2.2.3 Display Mode 2-4
2.2.4 Display Mode - Selection of Readouts 2-4
2.2.5 Parameter Set-Up, General Information 2-5
2.2.6 Quick Menu Key Functions 2-5
2.2.7 Quick Menu, Q3 Function Set-ups 2-7
2.2.8 Main Menu Mode 2-8
2.2.9 Parameter Selection 2-8
2.2.10 Changing Data 2-8
2.2.11 Changing a Text Value 2-9
2.2.12 Changing a Group of Numeric Data Values 2-9
2.2.13 Infinitely Variable Change of Numeric Data Value 2-9
2.2.14 Value, Step-by-Step 2-9
2.2.15 Readout and Programming of Indexed Parameters 2-10
2.3 How to Program on the Numerical LCP
2-10
2.3.1 Local Control Keys 2-11
2.4 Initialization to Default Settings
2-12
3 Parameter Description
3-1
3.1 Parameter Selection
3-1
3.2 Parameters 0-** Operation and Display
3-2
3.3 Parameters 1-** Load and Motor
3-15
3.4 Parameters 2-** Brakes
3-29
3.5 Parameters 3-** Reference/Ramps
3-32
3.6 Parameters 4-** Limits/Warnings
3-38
3.7 Parameters 5-** Digital In/Out
3-42
Contents
VLT
®
AQUA Drive Programming Guide
MG20O622 - VLT
®
is a registered Danfoss trademark
3.8 Parameters 6-** Analog In/Out
3-56
3.9 Parameters 8-** Communications and Options
3-62
3.10 Parameters 9-** Profibus
3-68
3.11 Parameters 10-** CAN Fieldbus
3-68
3.12 Parameters 13-** Smart Logic Control
3-73
3.13 Parameters 14-** Special Functions
3-85
3.14 Parameters 15-** Adjustable Frequency Drive Information
3-92
3.15 Parameters 16-** Data Readouts
3-98
3.16 Parameters 18-** Data Readouts 2
3-104
3.17 Parameters 20-** FC Closed-loop
3-106
3.18 Parameters 21-** Extended Closed Loop
3-115
3.19 Parameters 22-** Application Functions
3-123
3.20 Parameters 23-** Time-based Functions
3-136
3.21 Parameters 24-** Application Functions 2
3-146
3.22 Parameters 25-** Cascade Controller
3-147
3.23 Parameters 26-** Analog I/O Option MCB 109
3-158
3.24 Parameters 29-** Water Application Functions
3-163
3.25 Parameters 30-** Special Features
3-167
3.26 Parameters 31-** Bypass Option
3-167
3.27 Parameters 35-** Sensor Input Option
3-168
4 Parameter Lists
4-1
4.1 Parameter Options
4-1
4.1.1 Default settings 4-1
4.1.2 Operation/Display 0-** 4-2
4.1.3 Load/Motor 1-** 4-3
4.1.4 Brakes 2-** 4-4
4.1.5 Reference / Ramps 3-** 4-5
4.1.6 Limits / Warnings 4-** 4-6
4.1.7 Digital In/Out 5-** 4-7
4.1.8 Analog In/Out 6-** 4-8
4.1.9 Comm. and Options 8-** 4-9
4.1.10 Profibus 9-** 4-10
4.1.11 CAN Fieldbus 10-** 4-11
4.1.12 Smart Logic 13-** 4-11
4.1.13 Special Functions 14-** 4-12
4.1.14 Adj. Freq. Drive Information 15-** 4-12
4.1.15 Data Readouts 16-** 4-14
Contents
VLT
®
AQUA Drive Programming Guide
MG20O622 - VLT
®
is a registered Danfoss trademark
4.1.16 Data Readouts 2 18-** 4-15
4.1.17 Adj. Freq. Drive Closed-loop 20-** 4-16
4.1.18 Ext. Closed-loop 21-** 4-17
4.1.19 Application Functions 22-** 4-18
4.1.20 Timed Actions 23-** 4-19
4.1.21 24-** Application Functions 2 4-19
4.1.22 Cascade Controller 25-** 4-20
4.1.23 Analog I/O Option MCB 109 26-** 4-21
4.1.25 Water Application Functions 29-** 4-23
4.1.26 Special Features 30-** 4-23
4.1.27 Bypass Option 31-** 4-24
4.1.28 Sensor Input Option 35-** 4-24
5 Troubleshooting
5-1
5.1.1 Warnings/Alarm Messages 5-1
6 Index
6-1
Contents
VLT
®
AQUA Drive Programming Guide
MG20O622 - VLT
®
is a registered Danfoss trademark
Contents
VLT
®
AQUA Drive Programming Guide
MG20O622 - VLT
®
is a registered Danfoss trademark
1 Introduction
Programming Guide
Software version: 1.9x
This Programming Guide can be used for all FC 200 adjustable
frequency drives with software version 1.9x.
The software version number can be seen from 15-43 Software
Version.
Table 1.1
1.1.1 Approvals
Table 1.2
1.1.2
Symbols
Symbols used in this guide.
NOTICE!
Indicates something to be noted by the reader.
CAUTION
Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury or
equipment damage.
WARNING
Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
*
Indicates default setting
Table 1.3
1.1.3
Abbreviations
Alternating current AC
American wire gauge AWG
Ampere/AMP A
Automatic Motor Adaptation AMA
Current limit I
LIM
Degrees Celsius
°C
Direct current DC
Drive Dependent D-TYPE
Electro Magnetic Compatibility EMC
Electronic Thermal Relay ETR
Adjustable frequency drive FC
Gram g
Hertz Hz
Horsepower hp
Kilohertz kHz
Local Control Panel LCP
Meter m
Millihenry Inductance mH
Milliampere mA
Millisecond ms
Minute min
Motion Control Tool MCT
Nanofarad nF
Newton Meters Nm
Nominal motor current I
M,N
Nominal motor frequency f
M,N
Nominal motor power P
M,N
Nominal motor voltage U
M,N
Permanent Magnet motor PM motor
Protective Extra Low Voltage PELV
Printed Circuit Board PCB
Rated Inverter Output Current I
INV
Revolutions Per Minute RPM
Regenerative terminals Regen
Second sec.
Synchronous Motor Speed n
s
Torque limit T
LIM
Volts V
The maximum output current I
VLT,MAX
The rated output current supplied by the
adjustable frequency drive
I
VLT,N
Table 1.4
Introduction
VLT
®
AQUA Drive Programming Guide
MG20O622 - VLT
®
is a registered Danfoss trademark 1-1
1 1
1.1.4 Definitions
Adjustable frequency drive:
I
VLT,MAX
Maximum output current.
I
VLT,N
Rated output current supplied by the adjustable frequency
drive.
U
VLT, MAX
Maximum output voltage.
Input:
Control command
Start and stop the connected motor with LCP and digital
inputs.
Functions are divided into two groups.
Functions in group 1 have higher priority than functions in
group 2.
Group 1 Reset, Coasting stop, Reset and Coasting stop,
Quick stop, DC braking, Stop and the [OFF] key.
Group 2 Start, Pulse start, Reversing, Start reversing, Jog
and Freeze output
Table 1.5
Motor:
Motor Running
Torque generated on output shaft and speed from zero
rpm to max. speed on motor.
f
JOG
Motor frequency when the jog function is activated (via
digital terminals).
f
M
Motor frequency.
f
MAX
Maximum motor frequency.
f
MIN
Minimum motor frequency.
f
M,N
Rated motor frequency (nameplate data).
I
M
Motor current (actual).
I
M,N
Rated motor current (nameplate data).
n
M,N
Rated motor speed (nameplate data).
n
s
Synchronous motor speed
n
s
=
2 ×
par
. 1 23 × 60
s
par
. 1 39
P
M,N
Rated motor power (nameplate data in kW or HP).
T
M,N
Rated torque (motor).
U
M
Instantaneous motor voltage.
U
M,N
Rated motor voltage (nameplate data).
Break-away torque
175ZA078.10
Pull-out
rpm
Torque
Figure 1.1
η
VLT
The efficiency of the adjustable frequency drive is defined
as the ratio between the power output and the power
input.
Start-disable command
A stop command belonging to the group 1 control
commands - see this group.
Stop command
See Control commands.
References:
Analog Reference
A signal transmitted to the analog inputs 53 or 54, can be
voltage or current.
Binary Reference
A signal transmitted to the serial communication port.
Introduction
VLT
®
AQUA Drive Programming Guide
1-2 MG20O622 - VLT
®
is a registered Danfoss trademark
11
Preset Reference
A defined preset reference to be set from -100% to +100%
of the reference range. Selection of eight preset references
via the digital terminals.
Pulse Reference
A pulse frequency signal transmitted to the digital inputs
(terminal 29 or 33).
RefMAX
Determines the relationship between the reference input
at 100% full scale value (typically 10 V, 20 mA) and the
resulting reference. The maximum reference value set in
3-03 Maximum Reference.
RefMIN
Determines the relationship between the reference input
at 0% value (typically 0 V, 0 mA, 4 mA) and the resulting
reference. The minimum reference value set in
3-02 Minimum Reference.
Miscellaneous:
Analog Inputs
The analog inputs are used for controlling various
functions of the adjustable frequency drive.
There are two types of analog inputs:
Current input, 0–20 mA and 4–20 mA
Voltage input, 0–10 V DC
Analog Outputs
The analog outputs can supply a signal of 0–20 mA, 4–20
mA.
Automatic Motor Adaptation, AMA
AMA algorithm determines the electrical parameters for
the connected motor at standstill.
Brake Resistor
The brake resistor is a module capable of absorbing the
braking energy generated in regenerative braking. This
regenerative braking energy increases the intermediate
circuit voltage and a brake chopper ensures that the
power is transmitted to the brake resistor.
CT Characteristics
Constant torque characteristics used for all applications
such as conveyor belts, displacement pumps and cranes.
Digital Inputs
The digital inputs can be used for controlling various
adjustable frequency drive functions.
Digital Outputs
The adjustable frequency drive features two solid state
outputs that can supply a 24 V DC (max. 40 mA) signal.
DSP
Digital Signal Processor.
ETR
Electronic Thermal Relay is a thermal load calculation
based on present load and time. Its purpose is to estimate
the motor temperature.
Initializing
If initialization is carried out (14-22 Operation Mode), the
adjustable frequency drive returns to the default setting.
Intermittent Duty Cycle
An intermittent duty rating refers to a sequence of duty
cycles. Each cycle consists of an on-load and an off-load
period. The operation can be either periodic duty or non-
periodic duty.
LCP
The Local Control Panel makes up a complete interface for
control and programming of the adjustable frequency
drive. The control panel is detachable and can be installed
up to 10 ft [3 m] from the adjustable frequency drive, i.e.,
in a front panel by means of the installation kit option.
lsb
Least significant bit.
msb
Most significant bit.
MCM
Short for Mille Circular Mil, an American measuring unit for
cable cross-sections. 1 MCM = 0.5067 mm
2
.
Online/Offline Parameters
Changes to online parameters are activated immediately
after the data value is changed. Changes to offline
parameters are not activated before [OK] is entered on the
LCP.
Process PID
The PID control maintains the desired speed, flow,
pressure, temperature, etc., by adjusting the output
frequency to match the varying load.
PCD
Process Control Data
Power Cycle
Switch off line power until display (LCP) is dark then turn
power on again.
RCD
Residual Current Device.
Set-up
Parameter settings can be saved in four set-ups. Change
between the four parameter set-ups, and edit one set-up,
while another set-up is active.
SFAVM
Switching pattern called Stator Flux oriented Asynchronous
Vector Modulation (14-00 Switching Pattern).
Slip Compensation
The adjustable frequency drive compensates for the motor
slip by giving the frequency a supplement that follows the
measured motor load, keeping the motor speed almost
constant.
Introduction
VLT
®
AQUA Drive Programming Guide
MG20O622 - VLT
®
is a registered Danfoss trademark 1-3
1 1
Smart Logic Control (SLC)
The SLC is a sequence of user-defined actions executed
when the associated user-defined events are evaluated as
true by the Smart Logic Controller. (Parameter group 13-**
Smart Logic Control (SLC).
STW
Status Word
Adjustable Frequency Drive Standard Bus
Includes RS-485 bus with FC protocol or MC protocol. See
8-30 Protocol.
Thermistor
A temperature-dependent resistor placed where the
temperature is to be monitored (adjustable frequency drive
or motor).
Trip
A state entered in fault situations, e.g., if the adjustable
frequency drive is subject to an overtemperature or when
the adjustable frequency drive is protecting the motor,
process or mechanism. Restart is prevented until the cause
of the fault has disappeared and the trip state is canceled
by activating reset or, in some cases, by being
programmed to reset automatically. Trip may not be used
for personal safety.
Trip Locked
A state entered in fault situations when the adjustable
frequency drive is protecting itself and requiring physical
intervention, e.g., if the adjustable frequency drive is
subject to a short circuit on the output. A locked trip can
only be canceled by cutting off line power, removing the
cause of the fault, and reconnecting the adjustable
frequency drive. Restart is prevented until the trip state is
canceled by activating reset or, in some cases, by being
programmed to reset automatically. Trip may not be used
for personal safety.
VT Characteristics
Variable torque characteristics used for pumps and fans.
VVC
plus
If compared with standard voltage/frequency ratio control,
Voltage Vector Control (VVC
plus
) improves the dynamics
and the stability, both when the speed reference is
changed and in relation to the load torque.
60° AVM
Switching pattern called 60°
Asynchronous Vector
Modulation (14-00 Switching Pattern).
Power Factor
The power factor is the relation between I
1
and I
RMS
.
Power
factor
=
3
x
U
x
I
1
cos
ϕ
3
x
U
x
I
RMS
The power factor for 3-phase control:
=
I
1
x
cos
ϕ1
I
RMS
=
I
1
I
RMS
since
cos
ϕ1 = 1
The power factor indicates to which extent the adjustable
frequency drive imposes a load on the line power supply.
The lower the power factor, the higher the I
RMS
for the
same kW [hp] performance.
I
RMS
=
I
1
2
+
I
5
2
+
I
7
2
+ .. +
I
n
2
In addition, a high power factor indicates that the different
harmonic currents are low.
The built-in DC coils produce a high power factor, which
minimizes the imposed load on the line power supply.
WARNING
The voltage of the adjustable frequency drive is dangerous
whenever connected to line power. Incorrect installation of
the motor, adjustable frequency drive or serial communi-
cation bus may cause death, serious personal injury or
damage to the equipment. Consequently, the instructions
in this manual, as well as national and local rules and
safety regulations, must be complied with.
Safety Regulations
1. Disconnect the line power supply before carrying
out repair work. Make sure that the line power
supply has been disconnected and that the
necessary time has elapsed before removing
motor and line power supply plugs.
2. The [Off] key on the LCP does not disconnect the
line power supply and consequently it must not
be used as a safety switch.
3. The equipment must be properly grounded, the
user must be protected against supply voltage
and the motor must be protected against
overload in accordance with applicable national
and local regulations.
4. The ground leakage current exceeds 3.5 mA.
5. Protection against motor overload: If this function
is desired, set 1-90 Motor Thermal Protection for
example to data value ETR trip 1 or data value
ETR warning 1.
6. Do not remove the plugs for the motor and line
power supply while the adjustable frequency
Introduction
VLT
®
AQUA Drive Programming Guide
1-4 MG20O622 - VLT
®
is a registered Danfoss trademark
11
drive is connected to line power. Make sure that
the line power supply has been disconnected and
that the necessary time has elapsed before
removing motor and line power plugs.
7. Note that the adjustable frequency drive has
more voltage sources than L1, L2 and L3, when
load sharing (linking of DC intermediate circuit)
or external 24 V DC are installed. Make sure that
all voltage sources have been disconnected and
that the necessary time has elapsed before
commencing repair work.
Warning against unintended start
1. The motor can be brought to a stop with digital
commands, bus commands, references or a local
stop, while the adjustable frequency drive is
connected to line power. If personal safety
considerations (e.g., risk of personal injury caused
by contact with moving machine parts following
an unintentional start) make it necessary to
ensure that no unintended start occurs, these
stop functions are not sufficient. In such cases,
the line power supply must be disconnected or
the Safe Stop function must be activated.
2. The motor may start while setting the
parameters. If this means that personal safety
may be compromised (e.g., personal injury caused
by contact with moving machine parts), motor
starting must be prevented, for instance by use
of the Safe Stop function or secure disconnection
of the motor connection.
3. A motor that has been stopped with the line
power supply connected, may start if faults occur
in the electronics of the adjustable frequency
drive, through temporary overload or if a fault in
the power supply grid or motor connection is
remedied. If unintended start must be prevented
for personal safety reasons (e.g., risk of injury
caused by contact with moving machine parts),
the normal stop functions of the adjustable
frequency drive are not sufficient. In such cases,
the line power supply must be disconnected or
the Safe Stop function must be activated.
NOTICE!
When using the Safe Stop function, always follow the
instructions in the section Safe Stop of the VLT
®
AQUA
Drive Design Guide, MG20N.
4. Control signals from, or internally within, the
adjustable frequency drive may in rare cases be
activated in error, be delayed or fail to occur
entirely. When used in situations where safety is
critical.
WARNING
High Voltage
Touching the electrical parts may be fatal - even after the
equipment has been disconnected from line power.
Also make sure that other voltage inputs have been
disconnected, such as external 24 V DC, load sharing
(linkage of DC intermediate circuit), as well as the motor
connection for kinetic backup.
Systems where adjustable frequency drives are installed
must, if necessary, be equipped with additional monitoring
and protective devices according to the valid safety
regulations, e.g., law on mechanical tools, regulations for
the prevention of accidents, etc. Modifying the adjustable
frequency drives with the operating software is allowed.
NOTICE!
Hazardous situations shall be identified by the machine
builder/integrator who is responsible for taking necessary
preventive means into consideration. Additional
monitoring and protective devices may be included, always
according to valid national safety regulations, e.g., law on
mechanical tools, regulations for the prevention of
accidents.
Protection Mode
Once a hardware limit on motor current or DC link voltage
is exceeded, the adjustable frequency drive will enter
“Protection mode”. “Protection mode” is a change of the
PWM modulation strategy and a low switching frequency
to minimize losses. This continues 10 s after the last fault
and increases the reliability and the robustness of the
adjustable frequency drive while re-establishing full control
of the motor.
Introduction
VLT
®
AQUA Drive Programming Guide
MG20O622 - VLT
®
is a registered Danfoss trademark 1-5
1 1
1.1.5 Electrical Wiring - Control Cables
Figure 1.2 Diagram showing all electrical terminals without options.
Terminal 37 is the input to be used for Safe Stop. For instructions on Safe Stop installation, please refer to the section Safe Stop Instal-
lation of the Design Guide.
In rare cases, and depending on the installation, very long
control cables and analog signals may result in 50/60 Hz
ground loops due to noise from line power supply cables.
If this occurs, it may be necessary to break the shield or
insert a 100 nF capacitor between shield and chassis.
The digital and analog inputs and outputs must be
connected separately to the common inputs (terminal 20,
55, 39) of the adjustable frequency drive to avoid ground
currents from both groups affecting other groups. For
example, switching on the digital input may disturb the
analog input signal.
Introduction
VLT
®
AQUA Drive Programming Guide
1-6 MG20O622 - VLT
®
is a registered Danfoss trademark
11
Input polarity of control terminals
12 13 18 19 27 29 32 33 20 37
+24 V DC
0 VDC
130BT106.10
PNP (Source)
Digital input wiring
Figure 1.3
NPN (Sink)
Digital input wiring
12 13 18 19 27 29 32 33 20 37
+24 V DC
0 VDC
130BT107.11
Figure 1.4
NOTICE!
Control cables must be shielded/armored.
See section on grounding of shielded/armored control
cables in the VLT
®
AQUA Drive Design Guide, MG20N for the
correct termination of control cables.
130BA681.10
Figure 1.5
1.1.6
Start/Stop
Terminal 18 = 5-10 Terminal 18 Digital Input [8] Start
Terminal 27 = 5-12 Terminal 27 Digital Input [0] No
operation (Default coast inverse)
Terminal 37 = Safe stop (where available)
Figure 1.6
Introduction
VLT
®
AQUA Drive Programming Guide
MG20O622 - VLT
®
is a registered Danfoss trademark 1-7
1 1
1.1.7 Pulse Start/Stop
Terminal 18 = 5-10 Terminal 18 Digital Input [9] Latched
start
Terminal 27= 5-12 Terminal 27 Digital Input [6] Stop inverse
Terminal 37 = Safe stop (where available)
Figure 1.7
1.1.8
Speed Up/Down
Terminals 29/32 = Speed up/down
Terminal 18 = 5-10 Terminal 18 Digital Input [9]
Start (default)
Terminal 27 = 5-12 Terminal 27 Digital Input [19]
Freeze reference
Terminal 29 = 5-13 Terminal 29 Digital Input [21]
Speed up
Terminal 32 = 5-14 Terminal 32 Digital Input [22]
Slow
Terminal 29 only in FC x02 (x=series type).
12
18
27
29
32
37
+24V
Par. 5-10
Par. 5-12
Par. 5-13
Par. 5-14
130BA021.12
Figure 1.8
1.1.9
Potentiometer Reference
Voltage reference via a potentiometer
Reference Source 1 = [1] Analog input 53 (default)
Terminal 53, Low Voltage = 0 V
Terminal 53, High Voltage = 10 V
Terminal 53, Low Ref./Feedback = 0 RPM
Terminal 53, High Ref./Feedback = 1500 RPM
Switch S201 = OFF (U)
130BA154.11
Speed RPM
P 6-15
Ref. voltage
P 6-11 10 V
1 k
+10 V/30 mA
Figure 1.9
Introduction
VLT
®
AQUA Drive Programming Guide
1-8 MG20O622 - VLT
®
is a registered Danfoss trademark
11
2 How to Program
2.1 The Graphical and Numerical Local
Control Panel
The easiest programming of the adjustable frequency drive
is performed by the Graphical LCP (LCP 102). It is necessary
to consult the adjustable frequency drive Design Guide
when using the Numeric Local Control Panel (LCP 101). For
further information on how to use the Numeric Local
Control Panel (LCP 101), see 2.3 How to Program on the
Numerical LCP.
2.2 How to Program on the Graphical LCP
The control panel is divided into four functional groups
1. Graphical display with Status lines.
2. Menu keys and LEDs - changing parameters and
switching between display functions.
3. Navigation keys and LEDs (LEDs).
4. Operation keys and LEDs.
All data is displayed in a graphical LCP display, which can
show up to five items of operating data while displaying
[Status].
Display lines
a. Status line: Status messages displaying icons and
graphic.
b. Line 1-2: Operator data lines displaying data
defined or chosen by the user. By pressing
[Status], up to one extra line can be added.
c. Status line: Status messages displaying text.
Auto
on
Reset
Hand
on
O
Status
Quick
Menu
Main
Menu
Alarm
Log
Back
Cancel
Info
OK
Status
1(0)
1234rpm 10,4A 43,5Hz
Run OK
43,5Hz
On
Alarm
Warn.
130BA018.13
1
2
3
4
b
a
c
Figure 2.1
How to Program
VLT
®
AQUA Drive Programming Guide
MG20O622 - VLT
®
is a registered Danfoss trademark 2-1
2 2
2.2.1 The LCP Display
The LCP display has back light and a total of 6 alpha-
numeric lines. The display lines show the direction of
rotation (arrow), the chosen set-up as well as the
programming set-up. The display is divided into three
sections.
Top section shows up to two measurements in normal
operating status.
The top line in the Middle section shows up to five
measurements with related unit, regardless of status
(except in the case of alarm/warning).
Bottom section always shows the state of the adjustable
frequency drive in status mode.
Top section
Middle section
Bottom section
Status
43 RPM
1.4 Hz
Auto Remote Running
! Pwr.card temp (W29)
2.9%
5.44 A 25.3 kW
1(1)
130BP074.10
!
Figure 2.2
The Active set-up (selected as the Active Set-up in
0-10 Active Set-up) is shown. When programming another
set-up than the Active Set-up, the number of the
programmed set-up appears to the right.
Display Contrast Adjustment
Press [Status] and [
] for darker display
Press [Status] and [
] for brighter display
Most parameter set-ups can be changed immediately via
the LCP, unless a password has been created via 0-60 Main
Menu Password or via 0-65 Personal Menu Password.
LEDs
If certain threshold values are exceeded, the alarm and/or
warning LED lights up. A status and alarm text appear on
the LCP.
The ON LED is activated when the adjustable frequency
drive receives line voltage, or via a DC bus terminal or 24
V external supply. At the same time, the backlight is on.
Green LED/On: Control section is working.
Yellow LED/Warn.: Indicates a warning.
Flashing Red LED/Alarm: Indicates an alarm.
On
Warn.
Alarm
130BP044.10
Figure 2.3
LCP Keys
The control keys are divided into functions. The keys
below the display and LEDs are used for parameter set-up,
including choice of display indication during normal
operation:
130BP045.10
Status
Quick
Menu
Main
Menu
Alarm
Log
Figure 2.4
[Status] indicates the status of the adjustable frequency
drive and/or the motor. Choose between three different
readouts by pressing [Status]: 5 line readouts, 4 line
readouts or Smart Logic Control.
Press [Status] to select Display mode or for changing back
to Display mode from either Quick Menu mode, Main
Menu mode or Alarm mode. Also press [Status] to toggle
single or double readout mode.
[Quick Menu]
Allows quick set-up of the adjustable frequency drive. The
most common functions can be programmed here.
The [Quick Menu] consists of:
- Q1: My Personal Menu
- Q2: Quick Setup
- Q3: Function Set-ups
- Q5: Changes Made
- Q6: Loggings
How to Program
VLT
®
AQUA Drive Programming Guide
2-2 MG20O622 - VLT
®
is a registered Danfoss trademark
22
The Function Set-up provides quick and easy access to all
parameters required for the majority of water and
wastewater applications including variable torque, constant
torque pumps, dosing pumps, well pumps, booster pumps,
mixer pumps, aeration blowers and other pump and fan
applications. Amongst other features, it also includes
parameters for selecting which variables to display on the
LCP, digital preset speeds, scaling of analog references,
closed-loop single zone and multi-zone applications and
specific functions related to water and wastewater
applications.
The Quick Menu parameters can be accessed immediately
unless a password has been created via 0-60 Main Menu
Password, 0-61 Access to Main Menu w/o Password,
0-65 Personal Menu Password or 0-66 Access to Personal
Menu w/o Password.
It is possible to switch directly between Quick Menu mode
and Main Menu mode.
[Main Menu]
is used for programming all parameters.
The Main Menu parameters can be accessed immediately
unless a password has been created via 0-60 Main Menu
Password, 0-61 Access to Main Menu w/o Password,
0-65 Personal Menu Password or 0-66 Access to Personal
Menu w/o Password. For the majority of water and
wastewater applications it is not necessary to access the
Main Menu parameters. The Quick Menu, Quick Setup and
Function Set-ups provide the simplest and quickest access
to the typical required parameters.
It is possible to switch directly between Main Menu mode
and Quick Menu mode.
Parameter shortcut can be carried out by pressing down
[Main Menu] for 3 s. The parameter shortcut allows direct
access to any parameter.
[Alarm Log]
displays an alarm list of the five latest alarms (numbered
A1-A5). To obtain additional details about an alarm, use
the navigation keys to navigate to the alarm number and
press [OK]. Right before entering the alarm mode
information about the condition of the adjustable
frequency drive is provided.
Auto
on
Reset
Hand
on
O
Status
Quick
Menu
Main
Menu
Alarm
Log
Back
Cancel
Info
OK
On
Alarm
Warn.
130BA027.10
Figure 2.5
[Back] goes to the previous step or layer in the navigation
structure.
[Cancel] annuls the latest change or command as long as
the display has not been changed.
[Info] supplies information about a command, parameter,
or function in any display window. [Info] provides detailed
information whenever help is needed.
Exit info mode by pressing either [Info], [Back], or [Cancel].
Navigation Keys
The four navigation keys are used to navigate between the
different choices available in [Quick Menu], [Main Menu]
and [Alarm Log]. Use the keys to move the cursor.
[OK] is used for choosing a parameter marked by the
cursor and for enabling the change of a parameter.
Local Control Key for local control are found at the bottom
of the LCP.
[Hand On] enables control of the adjustable frequency
drive via the LCP. [Hand on] also starts the motor, and it is
now possible to enter the motor speed data using the
navigation keys. The key can be selected as Enable [1] or
Disable [0] via 0-40 [Hand on] Key on LCP
External stop signals activated by means of control signals
or a serial bus will override a “start” command via the LCP.
How to Program
VLT
®
AQUA Drive Programming Guide
MG20O622 - VLT
®
is a registered Danfoss trademark 2-3
2 2
The following control signals will still be active when
[Hand on] is activated
[Hand On] - [Off] - [Auto On]
Reset
Coasting stop inverse
Reversing
Set-up select bit 0 - Set-up select bit 1
Stop command from serial communication
DC brake
[Off] stops the connected motor. The key can be selected
as [1] Enable or [0] Disable via 0-41 [Off] Key on LCP. If no
external stop function is selected and the [Off] key is
inactive the motor can only be stopped by disconnecting
the voltage.
[Auto On] enables the adjustable frequency drive to be
controlled via the control terminals and/or serial communi-
cation. When a start signal is applied on the control
terminals and/or the bus, the adjustable frequency drive
will start. The key can be selected as [1] Enable or [0]
Disable via 0-42 [Auto on] Key on LCP.
NOTICE!
An active HAND-OFF-AUTO signal via the digital inputs has
higher priority than the control keys [Hand on] [Auto on].
[Reset] is used for resetting the adjustable frequency drive
after an alarm (trip). It can be selected as [1] Enable or [0]
Disable via 0-43 [Reset] Key on LCP.
The parameter shortcut can be carried out by holding
down the [Main Menu] key for three seconds. The
parameter shortcut allows direct access to any parameter.
2.2.2
Quick Transfer of Parameter Settings
between Multiple Adjustable
Frequency Drives
Once the set-up of an adjustable frequency drive is
complete, store the data in the LCP or on a PC via MCT 10
Set-up Software Tool.
Data storage in LCP
1.
Go to 0-50 LCP Copy
2. Press [OK]
3. Select “All to LCP”
4. Press [OK]
All the parameter settings are now being stored in the LCP
as indicated by the progress bar. When 100% is reached,
press [OK].
NOTICE!
Stop the motor before performing this operation.
Connect the LCP to another adjustable frequency drive
and copy the parameter settings to this adjustable
frequency drive as well.
Data transfer from LCP to adjustable frequency drive
1.
Go to 0-50 LCP Copy
2. Press [OK]
3. Select “All from LCP”.
4. Press [OK]
The parameter settings stored in the LCP are now
transferred to the adjustable frequency drive as indicated
by the progress bar. When 100% is reached, press [OK].
NOTICE!
Stop the motor before performing this operation.
2.2.3 Display Mode
In normal operation, up to 5 different operating variables
can be indicated continuously in the middle section: 1.1,
1.2, and 1.3 as well as 2 and 3.
2.2.4
Display Mode - Selection of Readouts
It is possible to toggle between three status readout
screens by pressing [Status].
Operating variables with different formatting are shown in
each status screen - see examples below.
Several values or measurements can be linked to each of
the displayed operating variables. The values/
measurements to be displayed can be defined via
0-20 Display Line 1.1 Small, 0-21 Display Line 1.2 Small,
0-22 Display Line 1.3 Small, 0-23 Display Line 2 Large, and
0-24 Display Line 3 Large, which can be accessed via [QUICK
MENU], “Q3 Function Set-ups”, “Q3-1 General Settings”,
“Q3-13 Display Settings”.
Each readout parameter selected in 0-20 Display Line 1.1
Small to 0-24 Display Line 3 Large has its own scale and
digits after a possible decimal point. The larger the
numeric value for a parameter, the fewer digits displayed
after the decimal point.
How to Program
VLT
®
AQUA Drive Programming Guide
2-4 MG20O622 - VLT
®
is a registered Danfoss trademark
22
Ex.: Current readout 5.25 A; 15.2A 105A.
See parameter group 0-2* LCP Display for further details.
Status screen I
This readout state is standard after start-up or initialization.
Press [Info] to obtain information about the measurement
links to the displayed operating variables (1.1, 1.2, 1.3, 2
and 3).
See the operating variables shown in the screen below.
1.1
2
3
1.3
1.2
130BP041.10
799 RPM
Auto Remote Ramping
1 (1)
36.4 kW7.83 A
0.000
53.2%
Status
Figure 2.6
Status screen II
See the operating variables (1.1, 1.2, 1.3 and 2) shown in
the screen below.
In the example, Speed, Motor current, Motor power and
Frequency are selected as variables in the first and second.
1.1
1.2
2
1.3
130BP062.10
207RPM
Auto Remote Running
1 (1)
24.4 kW5.25A
6.9Hz
Status
Figure 2.7
Status screen III
This state displays the event and action of the Smart Logic
Control. For further information, see 3.12 Parameters 13-**
Smart Logic Control.
130BP063.10
778 RPM
Auto Remote Running
1 (1)
4.0 kW0.86 A
State: 0 o 0 (o)
When: -
Do: -
Status
Figure 2.8
2.2.5 Parameter Set-Up, General
Information
The adjustable frequency drive can be used for practically
all assignments, which is why the number of parameters is
quite large. The adjustable frequency drive offers a choice
between two programming modes - a Main Menu and a
Quick Menu mode.
The former provides access to all parameters. The latter
takes the user through a few parameters making it
possible to program the majority of water/waste water
applications.
Regardless of the mode of programming, parameter can
be changes in both Main Menu mode and in Quick Menu
mode.
2.2.6
Quick Menu Key Functions
Pressing [Quick Menus]
The list indicates the different areas contained in the Quick
menu.
Figure 2.9
How to Program
VLT
®
AQUA Drive Programming Guide
MG20O622 - VLT
®
is a registered Danfoss trademark 2-5
2 2
Select My Personal Menu to display the chosen personal
parameters. These parameters are selected in 0-25 My
Personal Menu. Up to 20 different parameters can be
added in this menu.
Select Quick Set-up to go through a limited amount of
parameters to get the motor running almost optimally. The
default setting for the other parameters considers the
desired control functions and the configuration of signal
inputs/outputs (control terminals).
Parameters are selected by using the arrow keys. The
parameters in Table 2.1 are accessible in the Quick Set-up.
Parameter Unit
0-01 Language
1-20 Motor Power [kW] [kW]
1-22 Motor Voltage [V]
1-23 Motor Frequency [Hz]
1-24 Motor Current [A]
1-25 Motor Nominal Speed [rpm]
3-41 Ramp 1 Ramp-up Time [sec]
3-42 Ramp 1 Ramp-down Time [sec]
1-29 Automatic Motor
Adaptation (AMA)
[1] Enable complete AMA
Table 2.1 Parameters in Quick Set-up
Select Changes made to get information about:
the last 10 changes. Use the [
] [
] keys to scroll
between the last ten changed parameters.
the changes made since default setting.
input assignments
Select Loggings to get information about the display line
readouts. The information is shown as graphs.
It is possible to store up to 120 samples in the memory for
later reference.
How to Program
VLT
®
AQUA Drive Programming Guide
2-6 MG20O622 - VLT
®
is a registered Danfoss trademark
22
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230

Danfoss VLT AQUA Drive FC 202 Programming Guide

Type
Programming Guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI