ENGINEERING MANUAL
INVERTER-DRIVEN MULTI-SPLIT SYSTEM
HEAT PUMP AIR CONDITIONERS
Engineering Manual
TC-17006
Technical Catalog for Outdoor Unit
< Indoor Units >
●WallMount
TIWM006B21S
TIWM008B21S
TIWM012B21S
TIWM015B21S
TIWM018B21S
TIWM024B21S
TIWM030B21S
TC-17006-rev.1
i
IMPORTANT NOTICE AND SAFETY SUMMARY
1. Introduction
2. Important Safety Instructions
Thismanualshouldbeconsideredasapermanentpartoftheairconditioningequipmentandshould
remainwiththeairconditioningequipment.
(Transportation/InstallationWork)>(RefrigerantPipingWork)>(ElectricalWiringWork)>(Ref.ChargeWork)>(Test
Run)>(User)
ThisEngineeringManualconcentratesonairconditioningunitsforuseinheatpumpandheatrecovery
systems.Readthismanualcarefullybeforeperforminginstallationsoroperations.
Signal Words
Indicatesahazardoussituationthat,ifnotavoided,couldresultindeathor
seriousinjury.
Indicatesahazardoussituationthat,ifnotavoided,couldresultinminoror
moderateinjury.
Indicatesinformationconsideredimportant,butnothazard-related
(forexample,messagesrelatingtopropertydamage).
General Precautions
Toreducetheriskofseriousinjuryordeath,readtheseinstructions
thoroughlyandfollowallwarningsorcautionsincludedinallmanualsthat
accompaniedtheproductandareattachedtotheunit.Referbacktothese
instructionsasneeded.
ThissystemshouldbeinstalledbypersonnelcertiedbyJohnsonControls,Inc.Personnelmustbe
qualiedaccordingtolocal,stateandnationalbuildingandsafetycodesandregulations.Incorrect
installationcouldcauseleaks,electricshock,reorexplosion.InareaswhereSeismic‘’Performance
requirementsarespecied,theappropriatemeasuresshouldbetakenduringinstallationtoguard
againstpossibledamageorinjurythatmightoccurinanearthquakeiftheunitisnotinstalled
correctly,injuriesmayoccurduetoafallingunit.
UseappropriatePersonalProtectiveEquipment(PPE),suchasglovesandprotectivegogglesand,
whereappropriate,haveagasmasknearby.Alsouseelectricalprotectionequipmentandtoolssuited
forelectricaloperationpurposes.Keepawetclothandareextinguishernearbyduringbrazing.Use
careinhandling,rigging,andsettingofbulkyequipment.
Whentransporting,becarefulwhenpickingup,movingandmountingtheseunits.Althoughthe
unitmaybepackedusingplasticstraps,donotusethemfortransportingtheunitfromonelocation
toanother.Donotstandonorputanymaterialontheunit.Getapartnertohelp,andbendwith
yourkneeswhenliftingtoreducestrainonyourback.Sharpedgesorthinaluminumnsontheair
conditionercancutngers,sowearprotectivegloves.
Donottouchoradjustanysafetydevicesinsidetheindoororoutdoorunits.Allsafetyfeatures,
disengagement,andinterlocksmustbeinplaceandfunctioningcorrectlybeforetheequipmentis
putintooperation.Ifthesedevicesareimproperlyadjustedortamperedwithinanyway,aserious
accidentcanoccur.Neverbypassorjump-outanysafetydeviceorswitch.
JohnsonControlswillnotassumeanyliabilityforinjuriesordamagecausedbynotfollowingsteps
outlinedordescribedinthismanual.UnauthorizedmodicationstoJohnsonControlsproductsare
prohibitedasthey…
Maycreatehazardswhichcouldresultindeath,seriousinjuryorequipmentdamage.
Willvoidproductwarranties.
Mayinvalidateproductregulatorycertications.
MayviolateOSHAstandards.
ii
TC-17006-rev.1
Takethefollowingprecautionstoreducetheriskofpropertydamage.
Preventmoisture,dust,ornoncondensablecompoundsfromenteringtherefrigerantcycleduring
installationwork.Foreignmattercoulddamageinternalcomponentsorcauseblockages.
Ifairltersarerequiredonthisunit,donotoperatetheunitwithouttheairltersetinplace.Iftheair
lterisnotinstalled,dustmayaccumulateandbreakdownmayresult.
Donotinstallthisunitinanyplacewheresilicongasescancollect.Ifthesilicongasmoleculesattach
themselvestothesurfaceoftheheatexchanger,thennedsurfaceswillrepelwater.Asaresult,any
amountofdrainagemoisturecondensatecanoverowfromthedraincondensatepanandcouldrun
insideoftheelectricalbox,possiblycausingelectricalfailures.
Wheninstallingtheunitinahospitalorotherfacilitywhereelectromagneticwavesaregenerated
fromnearbymedicaland/orelectronicdevices,beawareofnoiseandelectronicinterference
ElectromagneticInterference(EMI).DonotinstallwhereEMIwavescandirectlyradiateintothe
electricalbox,controllercable,orcontroller.Inverters,appliances,high-frequencymedicalequipment,
andradiocommunicationsequipmentmaycausetheunittomalfunction.Theoperationoftheunit
mayalsoadverselyaffectthesesamedevices.Installtheunitatleast10ft.(approximately3m)away
fromsuchdevices.
Whenawirelesscontrollerisused,locateatadistanceofatleast3.3ft.(approximately1m)between
theindoorunitandelectriclighting.Ifnot,thereceiverpartoftheunitmayhavedifcultyreceiving
operationcommands.
Donotinstalltheunitinanylocationwhereanimalsandplantscancomeintodirectcontactwiththe
outletairstream.Exposurecouldadverselyaffecttheanimalsandplants.
Donotinstalltheunitwithanydownwardslopetothesideofthedrainadapter.Ifyoudo,youmay
havecondensateowingbackwhichmaycauseleaks.
Besurethecondensatehosedischargeswaterproperly.Ifconnectedincorrectly,itmaycauseleaks.
Donotinstalltheunitinanyplacewhereoilcanseepontotheunits,suchastableorseatingareasin
restaurants,andsoforth.Fortheselocationsorsocialvenues,usespecializedunitswithoil-resistant
featuresbuiltintothem.Inaddition,useaspecializedventilationunitdesignedforrestaurantuse.
Thesespecializedoil-resistantunitscanbeorderedforsuchapplications.However,inplaceswhere
largequantitiesofoilcansplashontotheunit,suchasafactory,eventhespecializedunitscannotbe
used.Theseproductsshouldnotbeinstalledinsuchlocations.
Ifthewiredcontrollerisinstalledinalocationwhereelectromagneticradiationisgenerated,make
surethatthewiredcontrollerisshieldedandcablesaresleevedinsideconduittubing.
Ifthereisasourceofelectricalinterferencenearthepowersupply,installnoisesuppression
equipment(lter).
Duringthetestrun,checktheunit’soperationtemperature.Iftheunitisusedinanenvironment
wherethetemperatureexceedstheoperationboundary,itmaycauseseveredamage.Checkthe
operationaltemperatureboundaryinthemanual.Ifthereisnospeciedtemperature,usetheunit
withintheoperationaltemperatureboundaryof32to104°F(0to40°C).
ReadinstallationandappropriateusermanualsforconnectionwithPCorperipheraldevices.Ifa
warningwindowappearsonthePC,theproductstops,doesnotworkproperlyorworksintermittently,
immediatelystopusingtheequipment.
TC-17006-rev.1
iii
Installation Precautions
Toreducetheriskofseriousinjuryordeath,thefollowinginstallation
precautionsmustbefollowed.
Wheninstallingtheunitinto…
Awall:Makesurethewallisstrongenoughtoholdtheunit’sweight.Itmaybenecessaryto
constructastrongwoodormetalframetoprovideaddedsupport.
Aroom:Properlyinsulateanyrefrigeranttubingruninsidearoomtoprevent“sweating”thatcan
causedrippingandwaterdamagetowallandoors.
Damporunevenareas:Usearaisedconcretepadorconcreteblockstoprovideasolid,level
foundationfortheunittopreventwaterdamageandabnormalvibration.
Anareawithhighwinds:Securelyanchortheoutdoorunitdownwithboltsandametalframe.
Provideasuitablewindbafe.
Asnowyarea:Installtheoutdoorunitonaraisedplatformthatishigherthandriftingsnow.
Providesnowprotectionhood.
Iftheremotesensorsarenotusedwiththiscontroller,thendonotinstallthiscontroller…
inaroomwherethereisnothermostat.
wheretheunitisexposedtodirectsunshineordirectlight.
wheretheunitwillbeincloseproximitytoaheatsource.
wherehot/coldairfromtheoutdoors,oradraftfromelsewhere(suchasairvents,diffusersor
grilles)canaffectaircirculation.
inareaswithpooraircirculationandventilation.
Donotinstalltheunitinthefollowingplaces.Doingsocanresultinanexplosion,re,damage,
corrosion,orproductfailure.
Explosiveorammableatmosphere.
Wherere,oil,steam,orpowdercandirectlyentertheunit,suchasincloseproximityordirectly
aboveakitchenstove.
Whereoil(includingmachineryoil)maybepresent.
Wherecorrosivegasessuchaschlorine,bromine,orsuldecanaccumulate,suchasnearahot
tuborhotspring.
Wheredense,salt-ladenmistisheavy,suchasincoastalregions.
Wheretheairqualityisofhighacidity.
Whereharmfulgasescanbegeneratedfromdecomposition.
Donotpositionthecondensatepipefortheindoorunitnearanysanitarysewerswherecorrosive
gasesmaybepresent.Ifyoudo,toxicgasescanseepintobreathableairspacesandcancause
respiratoryissues.Ifthecondensatepipeisinstalledincorrectly,waterleakageanddamagetothe
ceiling,oor,furniture,orotherpossessionsmayresult.Ifcondensatepipingbecomesclogged,
moisturecanbackupandcandripfromtheindoorunit.Donotinstalltheindoorunitwheresuch
drippingcancausemoisturedamageorunevenlocations:Usearaisedconcretepadorconcrete
blockstoprovideasolid,levelfoundationfortheunittopreventwaterdamageandabnormal
vibration.
Beforeperforminganybrazingwork,besurethattherearenoammablematerialsoropenames
nearby.
Performatestruntoensurenormaloperation.Safetyguards,shields,barriers,covers,andprotective
devicesmustbeinplacewhilethecompressor/unitisoperating.Duringthetestrun,keepngersand
clothingawayfromanymovingparts.
Cleanupthesitewhennished,rememberingtocheckthatnometalscrapsorbitsofwiringhave
beenleftinsidetheunitbeinginstalled.
Duringtransportation,donotallowthebackrestoftheforkliftmakecontactwiththeunit,otherwise,
itmaycausedamagetotheheatexchangerandalsomaycauseinjurywhenstoppedorstarted
suddenly.
Removegasinsidetheclosingpipewhenthebrazingworkisperformed.Ifthebrazingllermetalis
meltedwithremaininggasinside,thepipeswillbeblownoffanditmaycauseinjury.
Besuretousenitrogengasforanairtighttest.Ifothergasessuchasoxygengas,acetylenegasor
uorocarbongasareaccidentallyused,itmaycauseexplosionorgasintoxication.
Afterinstallationworkforthesystemhasbeencompleted,explainthe“SafetyPrecautions,”theproperuse
andmaintenanceoftheunittothecustomeraccordingtotheinformationinallmanualsthatcamewiththe
system.AllmanualsandwarrantyinformationmustbegiventotheuserorleftneartheIndoorUnit.
iv
TC-17006-rev.1
Refrigerant Precautions
Toreducetheriskofseriousinjuryordeath,thefollowingrefrigerant
precautionsmustbefollowed.
Asoriginallymanufactured,thisunitcontainsrefrigerantinstalledbyJohnsonControls.Johnson
Controlsusesonlyrefrigerantsthathavebeenapprovedforuseintheunit’sintendedhomecountry
ormarket.JohnsonControlsdistributorssimilarlyareonlyauthorizedtoproviderefrigerantsthat
havebeenapprovedforuseinthecountriesormarketstheyserve.Therefrigerantusedinthisunit
isidentiedontheunit’sfaceplateand/orintheassociatedmanuals.Anyadditionsofrefrigerantinto
thisunitmustcomplywiththecountry’srequirementswithregardtorefrigerantuseandshouldbe
obtainedfromJohnsonControlsdistributors.Useofanynon-approvedrefrigerantsubstituteswillvoid
thewarrantyandwillincreasethepotentialriskofinjuryordeath.
Ifinstalledinasmallroom,takemeasurestopreventtherefrigerantfromexceedingthemaximum
allowableconcentrationintheeventthatrefrigerantgasesshouldescape.Theinstallationshould
meettherequirementsinASHRAEStandards15and34.Ifrefrigerantgashasleakedduringthe
installationwork,ventilatetheroomimmediately.
Checkthedesignpressureforthisproductis601psi(4.15MPa).Thepressureoftherefrigerant
R410Ais1.4timeshigherthanthatoftherefrigerantR22.Therefore,therefrigerantpipingfor
R410AshallbethickerthanthatforR22.Makesuretousethespeciedrefrigerantpiping.Ifnot,the
refrigerantpipingmayraptureduetoanexcessiverefrigerantpressure.Besides,payattentionto
thepipingthicknesswhenusingcopperrefrigerantpiping.Thethicknessofcopperrefrigerantpiping
differsdependingonitsmaterial.
WhenR410Aisused,therefrigerantoiltendstobeaffectedbyforeignmatterssuchasmoisture,
oxidelm,(orfat).Performtheinstallationworkwithcaretopreventmoisture,dust,ordifferent
refrigerantfromenteringtherefrigerantcycle.Foreignmattercanbeintroducedintothecycletosuch
partsastheexpansionvalvecausingoperationalissues.
Toavoidthepossibilityofdifferentrefrigerantorrefrigerantoilbeingintroducedintothecycle,the
sizesofthechargingconnectionshavebeenchangedfromR407CtypeandR22type.Itisnecessary
toverifytheappropriatetoolsareonhandbeforeperforminginstallationwork.
UserefrigerantpipesandjointswhichareapprovedforusewithR410A.
Acompressor/unitcomprisesapressurizedsystem.Neverloosenthreadedjointswhilethesystemis
underpressureandneveropenpressurizedsystemparts.
Beforeinstallationiscomplete,makesurethattherefrigerantleaktesthasbeenperformed.If
refrigerantgasesescapeintotheair,turnOFFthemainswitch,extinguishanyopenamesand
contactyourservicecontractor.Refrigerant(Fluorocarbon)forthisunitisodorless.Iftherefrigerant
shouldleakandcomeintocontactwithopenames,toxicgascouldbegenerated.Also,becausethe
uorocarbonsareheavierthanair,theysettletotheoor,whichcouldcauseasphyxiation.
Wheninstallingtheunit,andconnectingrefrigerantpiping,keepallpipingrunsasshortas
possible,andmakesuretosecurelyconnecttherefrigerantpipingbeforethecompressorstarts
operating.Iftherefrigerantpipingisnotconnectedproperlyandthecompressorstartswith
thestopvalveopened,airmaybepulledintothesystemandtherefrigerantcyclewillbecome
subjectedtoextremelyhighpressure,whichcancauseanexplosionorre.
Tightenthearenutwithatorquewrenchinthespeciedmanner.Donotapplyexcessiveforcetothe
arenutwhentightening.Ifyoudo,thearenutcancrackandrefrigerantleakagemayoccur.
Whenmaintaining,relocating,anddisposingoftheunit,dismantletherefrigerantpipingafterthe
compressorstops.
Whenpipesareremovedoutfromunderthepipingcover,aftertheinsulationworkiscompleted,
coverthegapbetweenthepipingcoverandpipeswithadditionalinsulatingmaterial(eld-supplied).
Ifthegapisnotcovered,theunitmaybedamagedifsnow,rainwaterorsmallanimalsentertheunit.
Donotapplyexcessiveforcetothestopvalvewhenopening.Ifdamaged,thestopvalvecouldcome
apartduetorefrigerantpressure.Atthetestrun,fullyopenthegasandliquidvalves,otherwise,
thesedeviceswillbedamaged.(Itisclosedbeforeshipment.)
Ifthesetupforoutdoorunitsisincorrect,itmaycauseowbackoftherefrigerantandresultinfailure
oftheoutdoorunit.
Therefrigerantsystemmaybedamagediftheslopeofthepipingconnectionkitexceeds+15
o
.
TC-17006-rev.1
v
Electrical Precautions
Takethefollowingprecautionstoreducetheriskofelectricshock,reor
explosionresultinginseriousinjuryordeath.
Highlydangerouselectricalvoltagesareusedinthissystem.Carefullyrefertothewiringdiagram
andtheseinstructionswhenwiring.Improperconnectionsandinadequategroundingcancause
seriousinjuryordeath.
Performallelectricalworkinstrictaccordancewiththisinstallationandmaintenancemanualandall
therelevantregulatorystandards.
Beforeservicing,shutoffandtagalldisconnectswitches.Neverassumeelectricalpoweris
disconnected.Alwaysverifywithameter.
Onlyuseelectricalprotectionequipmentandtoolssuitedforthisinstallation.
Insulateawiredcontrolleragainstmoistureandtemperatureextremes.
Usespeciedcablesbetweenunits.
Theinstalledairconditionermaynotfunctionnormallyinthefollowinginstances:
Ifelectricalpowerforthenewairconditionerissuppliedfromthesametransformerasthe
externalequipment*referredtobelow.
Ifthepowersupplywiringforthisexternalequipment*andthenewairconditionerunitarelocated
incloseproximitytoeachother.
externalequipment*:(Example):Alift,containercrane,rectierforelectricrailway,inverter
powerdevice,arcfurnace,electricfurnace,large-sizedinductionmotorandlarge-sized
switch.
Regardingthecasesmentionedabove,surgevoltagemaybeinductedintothepowersupply
cablesforthepackagedairconditionerduetoarapidchangeinpowerconsumptionofthedevice
andanactivationofaswitch.
Checkeldregulationsandstandardsbeforeperformingelectricalworkinordertoprotectthe
powersupplyforthenewairconditionerunit.
CommunicationcablemustbeaminimumofAWG18(0.82mm
2
),2-Conductor,StrandedCopper.
ShieldedcablemustbeusedforapplicationsandroutinginareasofhighEMIandothersourcesof
potentiallyexcessiveelectricalnoisetoreducethepotentialforcommunicationerrors.Whenshielded
cablingisapplied,properbondingandterminationofthecableshieldisrequiredasperJohnson
Controlsguidelines.Plenumandriserratingsforcommunicationcablesmustbeconsideredper
applicationandlocalcoderequirements.
Thepolarityoftheinputterminalsisimportant,sobesuretomatchthepolaritywhenusingcontacts
thathavepolarity.
Useadedicatedcircuitfortheairconditionerattheunit’sratedvoltage.
Highlydangerouselectricalvoltagesareusedinthissystem.Carefullyrefertothewiringdiagramand
theseinstructionswhenwiring.Improperconnectionsandinadequategroundingcancauseserious
injuryordeath.
Beforeinstallingthecontrollerorremotedevices,ensurethattheindoorandoutdoorunitoperation
hasbeenstopped.Further,besuretowaitatleastveminutesbeforeturningoffthemainpower
switchtotheindoororoutdoorunits.Otherwise,waterleakageorelectricalbreakdownmayresult.
DonotopentheservicecoveroraccesspaneltotheindoororoutdoorunitswithoutturningOFFthe
mainpowersupply.Beforeconnectingorservicingthecontrollerorcablestoindoororoutdoorunits,
shutoffandtagalldisconnectswitches.Neverassumeelectricalpowerisdisconnected.Alwaysverify
withameter.
ThisequipmentcanbeinstalledwithaGroundFaultCircuitBreaker(GFCI),whichisarecognized
measureforaddedprotectiontoaproperlygroundedunit.Installappropriatesizedbreakers/fuses
/overcurrentprotectionswitches,andwiringinaccordancewithlocal,stateandNECcodesand
requirements.Theequipmentinstallerisresponsibleforunderstandingandabidingbyapplicable
codesandrequirements.
vi
TC-17006-rev.1
- CONTENTS -
1. GeneralInformation(Features).................................................................................................................. 1-1
2. WallMount................................................................................................................................................. 2-1
2.1 UnitNomenclature............................................................................................................................. 2-1
2.2 Line-up.............................................................................................................................................. 2-1
2.3 GeneralData..................................................................................................................................... 2-2
2.4 DimensionalData.............................................................................................................................. 2-3
2.5 Structure............................................................................................................................................ 2-6
2.6 ComponentData............................................................................................................................... 2-8
2.7 OperationSpace............................................................................................................................... 2-9
2.8 SensibleHeatFactor(SHF).............................................................................................................. 2-9
2.9 ElectricalData................................................................................................................................... 2-10
2.10 SoundData....................................................................................................................................... 2-11
2.11 ControlSystem.................................................................................................................................. 2-13
2.11.1 RefrigerantSystem.................................................................................................................. 2-13
2.11.2 StandardOperationSequence................................................................................................ 2-14
2.11.3 SafetyandControlDeviceSetting........................................................................................... 2-17
2.11.4 WiringDiagram........................................................................................................................ 2-18
3. OptionalParts............................................................................................................................................ 3-1
3.1 LineUp.............................................................................................................................................. 3-1
3.2 StrainerKit:MSF-NP63AandMSF-NP112A.................................................................................... 3-2
3.3 Infrared(IR)ReceiverKit:CWDIRK01.............................................................................................. 3-3
3.3.1 Specications........................................................................................................................... 3-3
3.3.2 Dimensions.............................................................................................................................. 3-3
3.3.3 ApplicableModels.................................................................................................................... 3-3
3.3.4 Accessories/Options.............................................................................................................. 3-4
3.3.5 Installation................................................................................................................................ 3-4
3.3.6 ElectricalWiring....................................................................................................................... 3-7
3.3.7 SettingDIPSwitchesonIndoorUnitSide............................................................................... 3-7
3.3.8 SettingDIPSwitchonIRReceiverKitSide............................................................................. 3-8
3.3.9 IdentifyingIndoorUnitsInstalledinaSide-by-SideOperation................................................ 3-9
3.3.10 SimultaneousOperation.......................................................................................................... 3-10
3.3.11 TestRunbyWirelessController(CIR01)................................................................................. 3-12
3.3.12 AlarmIndication....................................................................................................................... 3-12
3.4 3PConnectorCable:PCC-1A........................................................................................................... 3-13
3.5 RemoteSensor:THM-R2A................................................................................................................ 3-13
3.6 Relayand3PinConnectorKit:PSC-5RA......................................................................................... 3-14
4. SelectionData............................................................................................................................................ 4-1
4.1 SelectionGuide................................................................................................................................. 4-1
4.2 CapacityTable................................................................................................................................... 4-1
4.2.1CoolingCapacity............................................................................................................................... 4-1
4.2.2HeatingCapacity............................................................................................................................... 4-2
IMPORTANTNOTICEANDSAFETYSUMMARY......................................................................................... i
1. Introduction................................................................................................................................................ i
2. ImportantSafetyInstructions..................................................................................................................... i
FEATURES
TC-17006-rev.1
1-1
VRF Air Conditioners
Johnson Controls proudly introduces new Variable Refrigerant Flow (VRF) air conditioners, a highly-efcient
and reliable air-conditioning system. Recently, increased numbers of buildings are requiring "intelligent"
facilities that include communication networks, ofce automation, and a comfortable environment. In
particular, a comfortable environment is becoming more of a year-around requirement in ofce buildings.
The VRF multi-split system air conditioner meets these requirements. The proven combination of the scroll
compressor and inverter provides the best air conditioning for small and medium ofce buildings.
VRF System
Johnson Controls has developed the VRF system with its customers in mind.
This system, allows the interconnection of indoor units for all our VRF air conditioners.
This system provides the consumer with greater exibility for installation, which means that the air-
conditioning systems will integrate better within complex facility structures.
1. General Information (Features)
Indoor Unit Type
Capacity (MBH)
6 8 12 15 18 24 30
Wall Mount
TIWM_B21S
: Available
Wide Range Line-up
Table 1.1 Indoor Unit Type List
Wall Mount Models
TIWM006B21S, TIWM008B21S, TIWM012B21S, TIWM015B21S, TIWM018B21S,
TIWM024B21S, TIWM030B21S
FEATURES
1-2
TC-17006-rev.1
Easy Maintenance and Flexible Design
(1) Face panel
The unit has been designed with a face panel and a slim body. The front panel is easy to clean and
should remain relatively dust free. It is easily removed and washed with water.
(2) Compact design width of 31-1/8 inches (790mm) (Only for TIWM006B21S and TIWM008B21S)
The compact design width of 31-1/8 inches (790mm) makes it possible to install in a narrow space.
(3) Applicable to centralized control
When each indoor unit is controlled with a wireless controller, there is no need to install a wired
controller with a centralized control system.
Easy Installation
(1) DIP switch setting without removing the front panel
Other switch settings can be performed without removing the front panel.
Open the electrical box cover and perform the eld electrical wiring work without removing the front
panel.
(2) Operation control with wireless controller
Each unit can be controlled with a wireless controller by
built-in receiver kit. A wired controller is also available
instead of a wireless operation.
A signal-receiving buzzer and indicator light signals the
wireless controller operation.
In an instance of group control with a wireless controller
(multiple units are controlled simultaneously with one
wireless controller), an optional receiver kit or wired
controller is required.
31-1/8 inches (790mm)
Electrical Box Cover
PCB for DIP Switch
Remove the DIP switch
cover to set the DIP
switches.
Open the front cover
to see the electrical box.
Remove the electrical box cover
to perform the on-site wiring work
of the terminal block.
Available Range for Wireless Controller
CS-NET
New Type
Beep
WALL MOUNT
TC-17006-rev.1
2-1
2. Wall Mount
2.1 Unit Nomenclature
Model Descriptions
Example
T I WM 006 B 2 1 S
Nomenclature Description
T = Tag in the Bag T
Indoor Unit I
Indoor Unit Type
WM = Wall Mount
WM
Capacity (MBH) 006
Refrigerant Type
B = R410A
B
Power Supply
2 = 208/230Volts - 1Phase - 60Hz
2
1 = 1st Generation 1
S = Standard Type S
2.2 Line-up
Type
Capacity
Model
RT MBH
Indoor Unit Wall Mount
0.5 6 TIWM006B21S
0.7 8 TIWM008B21S
1.0 12 TIWM012B21S
1.3 15 TIWM015B21S
1.5 18 TIWM018B21S
2.0 24 TIWM024B21S
2.5 30 TIWM030B21S
WALL MOUNT
2-2
TC-17006-rev.1
2.3 General Data
Indoor Unit Type Wall Mount
Model TIWM008B21S TIWM012B21S
Indoor Unit Power Supply AC 1Phase, 208/230V, 60Hz
Nominal Coolin
g
Ca
p
acit
y
1
Btu/h
(kW)
Nominal Heatin
g
Ca
p
acit
y
1
Btu/h
(kW)
dB
Outer Dimensions
Height in. (mm) 11-13/16 (300) 11-13/16 (300) 11-13/16 (300) 13-1/8 (333)
Width in. (mm) 31-1/8 (790) 31-1/8 (790) 35-7/16 (900) 45-1/4 (1150)
Depth in. (mm) 9-1/16 (230) 9-1/16 (230) 9-1/16 (230) 9-5/8 (245)
Net Weight lbs. (kg) 22 (10) 22 (10) 24 (11) 35 (16)
Refrigerant R410A
Indoor Fan
Airflow Rate cfm
(Hi2-Hi-Me-Lo)
(
m
3
/min.
)
External Pressure
in.W.G
(Pa)
Motor Nominal Output W
Connections
Refrigerant Piping Flare-Nut Connection (with Flare Nuts)
Liquid Line in. (mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35)
Gas Line in. (mm) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70)
Condensate Drain
OD in. (mm) 7/8 (22) 7/8 (22) 7/8 (22) 7/8 (22)
ID in. (mm) 5/8 (16) 5/8 (16) 5/8 (16) 5/8 (16)
Indoor Unit Type Wall Mount
Model
Indoor Unit Power Supply AC 1Phase, 208/230V, 60Hz
Nominal Coolin
g
Ca
p
acit
y
1
Btu/h
(kW)
Nominal Heatin
g
Ca
p
acit
y
1
Btu/h
(kW)
dB
Outer Dimensions
Height in. (mm) 13-1/8 (333) 13-1/8 (333) 13-1/8 (333)
Width in. (mm) 45-1/4 (1150) 45-1/4 (1150) 45-1/4 (1150)
Depth in. (mm) 9-5/8 (245) 9-5/8 (245) 9-5/8 (245)
Net Weight lbs. (kg) 37 (17) 37 (17) 37 (17)
Refrigerant R410A
Indoor Fan
Airflow Rate cfm
(Hi2-Hi-Me-Lo)
(
m
3
/min.
)
External Pressure
in.W.G
(Pa)
Motor Nominal Output W
Connections
Refrigerant Piping Flare-Nut Connection (with Flare Nuts)
Liquid Line in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Gas Line in. (mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)
Condensate Drain
OD in. (mm) 7/8 (22) 7/8 (22) 7/8 (22)
ID in. (mm) 5/8 (16) 5/8 (16) 5/8 (16)
VP16VP16
(5.8)
20,000
(5.3)
49-43-40-36
VP16
38
(0)
0.0
(19-17-14-12)
671-600-494-424
0.0
39-35-32-30
353-282-247-229
34,000
30,00024,000
TIWM030B21STIWM024B21S
12,000
(3.5)
13,500
(2.3)
(10-8-7-6.5)
494-388-318-265
46-40-36-33
(14-11-9-7.5)
(4.0)
VP16
(0)
38
VP16VP16 VP16
15,000
(0)
(10-8-7-6.5)
8,0006,000
(1.8)
6,700
(2.0)
39-35-32-30
Sound Pressure Level
2
(Overall A Scale)
(Hi2-Hi-Me-Lo)
TIWM006B21S
9,000
(2.6)
38
0.0
(0)
38
0.0
353-282-247-229
(0)
38
38 38
(15-14-13-10)
(22-19-17-15) (22-19-17-15)
0.0
0.0 0.0
777-671-600-530
(0)
777-671-600-530
(4.4)
(7.0) (8.8)
17,000
27,000
42-40-38-33
51-49-46-41 51-49-46-41
(5.0)
(7.9) (10.0)
TIWM015B21S
Sound Pressure Level
2
(Overall A Scale)
(Hi2-Hi-Me-Lo)
(0)
530-494-459-353
18,000
TIWM018B21S
1. Nominal capacity is based on combinations within the VRF system and the following conditions:
Cooling Operation Conditions Heating Operation Conditions
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB)
67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB)
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB)
Piping Length: 24 ft. 7-3/16 in. (7.5m) Piping Lift: 0ft. (0m)
2. Sound pressure level is based on following conditions.
3.3 ft. (1m) Front of the Unit and 3.3 ft. (1m) Below the Unit.
The above data was measured in an anechoic chamber so that reected sound should be taken into consideration in the eld.
WALL MOUNT
TC-17006-rev.1
2-3
2.4 Dimensional Data
Models: TIWM006B21S and TIWM008B21S
Opening Direction Option 1: Opening Direction Option 2:
NOTES:
1. Removal of the condensate pipe is possible from either side of the knockout holes. If using the left side, install
a condensate hose to the condensate pipe connection at the left side.
2. Make sure there is no gap at the center position of the bracket and the unit. Mount them according to the gure
above.
Unit: inch (mm)
WALL MOUNT
2-4
TC-17006-rev.1
Models: TIWM012B21S
NOTE:
Removal of the condensate pipe is possible from either side of the knockout holes. If using the left side, install a
condensate hose to the condensate pipe connection at the left side.
Opening Direction Option 1:
Unit: inch (mm)
Opening Direction Option 2:
WALL MOUNT
TC-17006-rev.1
2-5
Models: TIWM015B21S, TIWM018B21S, TIWM024B21S and TIWM030B21S
NOTE:
Removal of the condensate pipe is possible from either side of the knockout holes. If using the left side, install a
condensate hose to the condensate pipe connection at the left side.
Unit: inch (mm)
Opening Direction Option 2: Opening Direction Option 3:
Opening Direction Option 1:
Dimension
Model
a b
TIWM015B21S
1/4
(6.35)
1/2
(12.7)
TIWM018B21S
3/8
(9.52)
5/8
(15.88)
TIWM024B21S
3/8
(9.52)
5/8
(15.88)
TIWM030B21S
3/8
(9.52)
5/8
(15.88)
WALL MOUNT
2-6
TC-17006-rev.1
2.5 Structure
No. Part Name Remarks No. Part Name Remarks
1 Fan 9 Refrigerant Liquid Pipe with
f
1/4 (6.35) Flare Nut
2 Fan Motor 10 Condensate Pipe VP16 (OD
f
7/8 (22))
3 Heat Exchanger 11 Motor for Auto Swing
4 Distributor 12 Condensate Pan
5 Strainer 13 Air Filter
6 Electronic Expansion Valve 14 Air Outlet
7 Electrical Control Box 15 Air Inlet
8 Refrigerant Gas Pipe with
f
1/2 (12.7) Flare Nut 16 Receiver Part
No. Part Name Remarks No. Part Name Remarks
1 Fan 9 Refrigerant Liquid Pipe with
f
1/4 (6.35) Flare Nut
2 Fan Motor 10 Condensate Pipe VP16 (OD
f
7/8 (22))
3 Heat Exchanger 11 Motor for Auto Swing
4 Distributor 12 Condensate Pan
5 Strainer 13 Air Filter
6 Electronic Expansion Valve 14 Air Outlet
7 Electrical Control Box 15 Air Inlet
8 Refrigerant Gas Pipe with
f
1/2 (12.7) Flare Nut 16 Receiver Part
Unit: inch (mm)
Models: TIWM006B21S and TIWM008B21S
Models: TIWM012B21S
WALL MOUNT
TC-17006-rev.1
2-7
No. Part Name Remarks No. Part Name Remarks
1 Fan 9 Refrigerant Liquid Pipe with
f
b Flare Nut
2 Fan Motor 10 Condensate Pipe VP16 (OD
f
7/8 (22))
3 Heat Exchanger 11 Motor for Auto Swing
4 Distributor 12 Condensate Pan
5 Strainer 13 Air Filter
6 Electronic Expansion Valve 14 Air Outlet
7 Electrical Control Box 15 Air Inlet
8 Refrigerant Gas Pipe with
f
a Flare Nut 16 Receiver Part
Unit: inch (mm)
Models: TIWM015B21S, TIWM018B21S, TIWM024B21S and TIWM030B21S
Mark
Model
a b
TIWM015B21S 1/2 (12.7) 1/4 (6.35)
TIWM018B21S
TIWM024B21S
TIWM030B21S
5/8 (15.88) 3/8 (9.52)
WALL MOUNT
2-8
TC-17006-rev.1
2.6 Component Data
Indoor Heat Exchanger and Fan
Tube Material
Outer Diameter
ɸ in. (mm)
1/4 (7.0) 1/4 (7.0) 1/4 (7.0) 1/4 (7.0)
Rows
Number of Tube/Coil
Fin Material
Pitch in. (mm) 0.049 (1.25) 0.049 (1.25) 0.049 (1.25) 0.051 (1.3)
psi (MPa) 601 (4.15) 601 (4.15) 601 (4.15) 601 (4.15)
ft
2
(
m
2
Number/Unit
Outer Diameter
ɸ in.
(mm)
Nominal Airflow cfm
(Hi2-Hi-Me-Lo)
(
m
3
/min.
)
Starting Method
Nominal Output W
Quantity
Insulation Class
Tube Material
Outer Diameter
ɸ in. (mm)
1/4 (7.0) 1/4 (7.0) 1/4 (7.0)
Rows
Number of Tube/Coil
Fin Material
Pitch in. (mm) 0.051 (1.3) 0.051 (1.3) 0.051 (1.3)
psi (MPa) 601 (4.15) 601 (4.15) 601 (4.15)
ft
2
(
m
2
Number/Unit
Outer Diameter
ɸ in.
(mm)
Nominal Airflow cfm
(Hi2-Hi-Me-Lo)
(
m
3
/min.
)
Starting Method
Nominal Output W
Quantity
Insulation Class
TIWM015B21S
TIWM024B21S
(115)
353-282-247-229
(10-8-7-6.5)
46
52
Heat Exchanger Type
2
2
Indoor Fan Motor
38 38
11
EE
2
52
TIWM030B21S
Model
Heat Exchanger Type
22
Model
34 34
Maximum Operating Pressure
Total Face Area 76.4 90.4
(7.1) (8.4)
Number of Coil/Unit 1 1
Indoor Fan
1
1
1
(14.0)
(15.8)
1
Maximum Operating Pressure
Total Face Area
150.7
170.1
Indoor Fan Motor
4-1/8
530-494-459-353
TIWM018B21S
52
2
Copper Tube
Multi-Pass Cross Finned Tube
Multi-Blade Centrifugal Fan
1
(15.8)
170.1
Aluminum
1
Indoor Fan
1
Number of Coil/Unit
(105)
777-671-600-530
(22-19-17-15)
38
1
4-1/8
4-1/8
170.1
(15.8)
1
4-1/2
(115)
1
4-1/2 4-1/2
(115)
494-388-318-265
(14-11-9-7.5)
E
1
(15-14-13-10)
(105)
38
1
(105)(105)
4-1/8
DC Motor
TIWM006B21S TIWM012B21S
353-282-247-229
(10-8-7-6.5)
38
1
E
Aluminum
Copper Tube
Multi-Pass Cross Finned Tube
Multi-Blade Centrifugal Fan
Drip-Proof Type Enclosure
DC Motor
TIWM008B21S
2
34
76.4
(7.1)
1
1
E
1
38
E
1
38
Drip-Proof Type Enclosure
(22-19-17-15)
777-671-600-530
(19-17-14-12)
671-600-494-424
E
WALL MOUNT
TC-17006-rev.1
2-9
Models: TIWM006B21S, TIWM008B21S, TIWM012B21S, TIWM015B21S, TIWM018B21S,
TIWM024B21S and TIWM030B21S
2.7 Operation Space
2.8 Sensible Heat Factor (SHF)
Model SHF *
TIWM006B21S 0.73
TIWM008B21S 0.73
TIWM012B21S 0.74
TIWM015B21S 0.75
TIWM018B21S 0.73
TIWM024B21S 0.73
TIWM030B21S 0.73
* SHF is based on combinations within the VRF system and the following conditions:
Cooling Operation Conditions
Indoor Air Inlet Temperature: 80
o
F DB (26.7
o
C DB)
67
o
F WB (19.4
o
C WB)
Outdoor Air Inlet Temperature: 95
o
F DB (35.0
o
C DB)
Piping Length: 24 ft. 7-3/16 in. (7.5m)
Piping Lift: 0 ft. (0m)
* The above gure shows TIWM006B21S and TIWM008B21S units.
Model a b
TIWM006B21S
TIWM008B21S
TIWM012B21S
5-7/8 (150) 3-15/16 (100)
TIWM015B21S
TIWM018B21S
TIWM024B21S
TIWM030B21S
3-15/16 (100) 7-7/8 (200)
Min.
a
Min.
b
Min.
94-1/2
(2400)
Min.
3-15/16
(100)
Floor
Unit: inch (mm)
WALL MOUNT
2-10
TC-17006-rev.1
2.9 Electrical Data
Model
Unit Main Power Applicable Voltage Power Supply
Indoor
Fan Motor
Unit
VOL PH HZ Maximum Minimum MCA MFA OPT FLA
TIWM006B21S
208/230 1 60 253 188
0.3 15 0.038 0.2
TIWM008B21S 0.3 15 0.038 0.2
TIWM012B21S 0.5 15 0.038 0.4
TIWM015B21S 0.4 15 0.038 0.3
TIWM018B21S 0.6 15 0.038 0.5
TIWM024B21S 0.7 15 0.038 0.6
TIWM030B21S 0.7 15 0.038 0.6
VOL: Rated Unit Power Supply Voltage (V)
PH: Phase
HZ: Frequency (Hz)
MCA: Minimum Circuit Ampacity (A)
MFA: Maximum Fuse Ampacity (A)
OPT: Rated Motor Output (kW)
FLA: Full Load Ampacity (A)
NOTE:
Power supply voltage should be satised with the following.
Supply Voltage: Rated Voltage within ±10%
Starting Voltage: Rated Voltage within -15%
Operating Voltage: Rated Voltage within ±10%
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

York VRF Wall Mount Indoor Unit User manual

Category
Split-system air conditioners
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI