Megger INGVAR User manual

Category
Multimeters
Type
User manual
WWW.MEGGER.COM
User’s Manual
Art No. ZP-BH05E Doc. BH0654BE V02 2011
INGVAR
Primary Current Injection Test System
INGVAR
Primary Current Injection Test System
Megger Sweden AB
Eldarvägen 4
Box 2970
SE-187 29 TÄBY
Sweden
T +46 8 510 195 00
F +46 8 510 195 95
seinfo@megger.com
www.megger.com
NOTICE OF COPYRIGHT & PROPRIETARY RIGHTS
© 2011, Megger Sweden AB. All rights reserved.
The contents of this manual are the property of Megger Sweden AB. No part of this work may be reproduced or transmitted in any form or
by any means, except as permitted in written license agreement with Megger Sweden AB. Megger Sweden AB has made every reasonable
attempt to ensure the completeness and accuracy of this document. However, the information contained in this manual is subject to change
without notice, and does not represent a commitment on the part of Megger Sweden AB. Any attached hardware schematics and technical
descriptions, or software listings that disclose source code, are for informational purposes only. Reproduction in whole or in part to create
working hardware or software for other than Megger Sweden AB products is strictly prohibited, except as permitted by written license
agreement with Megger Sweden AB.
TRADEMARK NOTICES
Megger® and Programma® are trademarks registered in the U.S. and other countries. All other brand and product names mentioned in this
document are trademarks or registered trademarks of their respective companies.
Megger Sweden AB is certified according to ISO 9001 and 14001.
User’s Manual
BH0654BE ZP-BH05E
3
4 ZP-BH05E BH0654BE
Contents
1 Safety ..................................................... 6
1.1 General ........................................................6
Symbols on the instrument .......................................... 6
Precaution levels ......................................................... 6
1.2 Safety instructions ........................................6
2 Introduction ......................................... 10
2.1 General ......................................................10
Current generation ................................................... 10
The measurement section contains/provides .............. 10
2.2 Fields of application ...................................11
2.3 Reservations ...............................................11
3 Panels ................................................... 12
3.1 Control Unit panel .....................................12
3.3 Cables .......................................................15
Standard cables ......................................................... 15
Optional cables ......................................................... 16
4 Display ................................................. 18
4.1 The display .................................................18
Directional indicators ................................................. 18
When special applications are activated ..................... 18
5 Menu options ...................................... 20
5.1 General ......................................................20
5.2 AMMETER, V/A METER and SYSTEM menu
options ....................................................20
How to set values ...................................................... 20
A-METER 1 ................................................................ 20
V/A METER ................................................................ 21
SYSTEM .................................................................... 21
5.3 MEMORY and APPLICATION menu
options ...................................................22
Setting values ............................................................ 22
MEMORY .................................................................. 22
APPLICATION ............................................................ 23
6 How to install INGVAR ........................ 24
6.1 Safety ........................................................24
6.2 Connecting the test object and the Current
Unit to each other ...................................24
6.3 Series connection .......................................25
6.4 Parallel connection .....................................25
6.5 Connecting the Current Unit to the Control
Unit .........................................................26
6.6 Grounding INGVAR ....................................26
6.7 Connecting INGVAR to the mains ..............27
Mains voltage ........................................................... 27
Mains cable and connectors ...................................... 27
6.8 Current cables and conductors ...................27
Available cable sets ................................................... 27
Standard multi-cable sets .................................28
Multi-cable sets with customised length ................... 28
Calculate the impedance ........................................... 29
6.9 How to arrange the cable sets ....................30
Minimising impedance in cables ................................ 30
6.10 How to arrange bars ................................32
6.11 FAQ .........................................................32
7 How to use INGVAR ............................ 34
7.1 How to generate current ............................34
7.2 Rules of thumb when generating current ...35
7.3 Setting the desired current .........................35
Low currents ............................................................. 35
High currents ............................................................ 35
Generating briefly ..................................................... 35
7.4 Setting times for limited-time generation
(MAX TIME) .............................................36
7.5 Continuous current generation ..................36
7.6 Setting stop conditions ..............................37
7.7 Getting maximum current from INGVAR ....37
7.8 Generating low currents ............................38
7.9 Generating pulse trains ..............................38
7.10 Holding (freezing) measured values ..........39
7.11 Measuring phase angle and polarity .........39
Measuring current ..................................................... 39
Measuring voltage .................................................... 39
7.12 Measuring Z, P, R, X, S, Q and power factor
(cos ϕ) .....................................................40
7.13 Reading maximum current at an
operation ................................................41
7.14 Measuring operating limits .......................41
Method 1: Normal injection –gradually increase in cur-
rent. .......................................................................... 41
Method 2: Manually controlled momentary injection . 42
Method 3: Limited-time generation ........................... 42
7.15 Measuring tripping/operation times .........43
7.16 Instantaneous trip unit measurement .......43
7.17 Test circuit impedance ..............................44
Introduction .............................................................. 44
Test circuit impedance limits the current .................... 44
Impedance of the test object ..................................... 44
7.18 Selecting output configuration and
cables / conductors ..................................45
Current output – Series or Parallel ............................. 45
BH0654BE ZP-BH05E
5
Rules of thumb ......................................................... 46
8 Application examples ......................... 48
8.1 Testing a low-voltage circuit breaker...........48
Measuring the tripping limit (normal generation) ....... 48
Measuring the tripping time ...................................... 48
Instantaneous trip unit measurement ........................ 48
Measure the instantaneous trip time ......................... 49
8.2 Testing the ratio of a current transformer ...49
Example .................................................................... 49
8.3 Measuring the polarity of a current trans-
former .....................................................50
8.4 Testing a direct acting automatic recloser ...51
Time test ................................................................... 51
8.5 Testing a sectionalizer ................................52
9 Troubleshooting .................................. 54
General ..................................................................... 54
Measurement errors .................................................. 54
10 Calibration ......................................... 56
10.1 General ....................................................56
10.2 Calibration of offset .................................56
10.3 Calibration of scale factor, ammeter 1 ......57
Scale factor, range LOW ............................................ 57
Scale factor, range HIGH ........................................... 57
10.4 Scale factor for the I/30-function ..............57
10.5 Calibration of scale factor, ammeter 2 ......58
Scale factor, range 0 – 2 A ........................................ 58
Scale factor, range 0 – 20 A ...................................... 58
10.6 Calibration of scale factor, voltmeter ........58
Scale factor, range 0 – 0.2 V...................................... 58
Scale factor, ranges 0 – 2 V, 0 – 20 V and 0 – 200 V .. 58
10.7 Resetting to preset (standardized) calibra-
tion values ...............................................59
Performing a reset ..................................................... 59
11 Specifications .................................... 60
Extended specifications ....................................61
Stop input ................................................................. 61
Appendix 1 ............................................. 62
A1.1 Transferring test data to a PC or a printer 62
A1.2 Setting up the connection .......................62
How to connect via Win XP hyper terminal ......63
How to connect via Win 2000 Hyper Terminal .. 64
A1.3 Transfers in ”NORMAL USE” ....................65
Example of transfered data: ...................................... 65
A1.4 Transfers in applications ”TEST RECLOSER”
and ”SECTIONALIZER” ............................66
Example of transferred data: ..................................... 66
How to connect via Win 7 Hyper Terminal ........ 66
Index ....................................................... 68
6 ZP-BH05E BH0654BE
1 SAFETY
1
Safety
1.1 General
Always follow the local safety regulations that apply
to work with high-voltage equipment.
Make certain that all personnel who work with
INGVAR have been trained in its use and that all ap-
plicable safety precautions are taken.
Read and comply with the following instructions as
well as the warnings and instructions on the ING-
VAR control panel.
Symbols on the instrument
Caution, refer to accompanying docu-
ments.
Caution, risk of electric shock.
Protective conductor terminal.
WEEE, Waste Electrical and Electronic
Equipment. Please utilize your local
WEEE collection facilities in the dispo-
sition of this product and otherwise
observe all applicable requirements.
Precaution levels
The manual uses two precaution levels, WARNING
and Important. The messages will be in the following
formats:
WARNING
Means you may risk possible bodily harm
and damage to the test object and/or test
equipment.
Important
Means you risk damage to the test object
and/or the test equipment.
1.2 Safety instructions
You must also read and follow the additional safety
precautions in each appropriate section of the manu-
al.
1. Read / Follow / Retain all instructions
All safety and operating instructions must be read
before using INGVAR.
All safety and operating instructions for INGVAR must
be followed.
All safety and operating instructions must be retained
for future reference.
2. Connecting
Always ground INGVAR
Before connecting INGVAR, turn off its master ON/
OFF switch.
When changing the connections make sure that
current not can be generated accidently. Disconnect
the mains supply or switch the miniature breaker F1
to the 0-position.
Do not use within measurement categories II, III and
IV.
Use caution when working near bare conductors or
bus bars. Accidental contact with a conductor may
cause electrical shock. At dry locations use caution
when working with voltages that exceed 33 V AC
and 46 V peak or 70 V DC, such signals pose a shock
hazard. At wet locations, use caution when working
with voltages that exceed 16 V AC and 22V peak or
35 V DC. Follow the local safety regulations.
Before connecting INGVAR to a circuit breaker,
make certain that the circuit breaker is closed and
grounded on one side.
When testing current transformer. Dangerous
voltages can appear in the secondary circuits if they
are open.
Unplug INGVAR from the mains supply when it is left
unattended or not in use.
BH0654BE ZP-BH05E
7
1 SAFETY
3. Grounding (Earthing)
INGVAR can be used only in electrical systems with
single Ground. User must verify before connecting
this unit to power, that High Voltage Ground and
Low Voltage Protective Ground create a single
protective ground with no measurable voltage
potential existing between these ground systems.
If a voltage potential is found between the ground
systems please consult local safety regulations.
Always use a grounded mains cable to connect the
Control Unit to the mains. Always ground INGVAR
using a separate ground cable.
4. Mains cord protective conductor
INGVAR is equipped with a power cord with integral
safety ground pin.
The equipment must be connected to a grounded
mains outlet.
Do not defeat the safety ground in any manner.
5. Separate ground wire
The INGVAR case must also be grounded by the
separate protective ground wire with connection
to the Protective Conductor Terminal on top of the
INGVAR. Check the continuity of the protective
ground wire before each use. Make sure the
connector is fastened properly to the INGVAR
Protective Conductor Terminal. Make sure the
connection point at the ground system is fastened
properly. Route the wire so that it is unlikely to be
walked on or that it may loosen accidentally by
someone or something moving near it.
The protective ground wire must not be loosened
while any input connector is attached to the contacts
of a high voltage circuit breaker or another device
being subject to inductive or capacitive coupled
interference from surrounding high voltage wires.
6. Placement
INGVAR must be situated away from any heat
sources such as radiators, heat registers, stoves, or
other products that produce heat.
Do not place the INGVAR in areas with excessive
dust, mechanical vibration or shock
Do not use INGVAR near water.
Do not expose the INGVAR to rain or moisture.
Do not touch the plug with wet hands. Doing so may
result in electrical shock.
7. Use
Do not use the instrument for any purpose other
than indicated by the manufacturer.
Do not use any accessories/cables not recommended
by the INGVAR manufacturer as they may cause
hazards.
8. EMC Warning
INGVAR can generate radio frequency energy. If not
installed and used in accordance with this manual
it may cause interference to radio communications.
INGVAR has been tested and found to comply with
the limits for measurement equipment designed
to provide reasonable protection against such
interference when used in an industrial environment.
Operation of INGVAR in a commercial or residential
area is likely to cause interference, at which case,
the user, at his own expense, will be required to take
whatever measures that may be required to correct
the interference.
9. Cables
Use only approved mains detachable cable set with
INGVAR. Main supply cables shall be rated for the
maximum current for the equipment and the cable
shall meet the requirements of IEC 60227 or IEC
60245. Mains supply cables certified or approved
by a recognized testing authority are regarded as
meeting this requirement.
To conform to the CE requirements for high
frequency radiation, shielded cables or cables with
added ferrite filters must be used for connection to
the inputs/outputs.
Connecting cables must be routed so that they are
not likely to be walked on nor pinched by items
placed upon or against them. Do not pull on or tie
them. Pay particular attention to the connectors.
To disconnect a cable, unlock the retainer (in case of
an XLR connector), grasp the connector firmly and
pull.
If an input- or output cable becomes damaged, stop
using it. Use of a damaged cable may result in fire or
electric shock.
8 ZP-BH05E BH0654BE
1 SAFETY
10. Power sources
Only connect INGVAR to an outlet protected with
max 16 A overcurrent protection.
Make certain that mains outlet and its fuses and all
cables/wiring have sufficient current-carrying capacity,
i.e. suitable ratings.
Use an easily accessible power outlet. This will ensure
that you can disconnect the power quickly in case of
a problem.
Never connect INGVAR to a mains voltage other than
that specified on the data plates (nameplate) on the
Control Unit and the Current Unit.
The plug to the mains inlet is not to be used as
disconnecting device.
The mains connector or the mains switch are to be
used as disconnecting device.
11. Inputs and outputs
Do not apply voltage to the outputs.
Do not connect the “AMMETER 2” and VOLTMETER
inputs at the same time.
The voltages and currents that are generated by
INGVAR can cause serious injury.
Dangerous voltages can develop at exposed
connectors if the equipment malfunctions.
The current output terminals and connecting points
can be hot after generation of high current.
12. Ventilation
Slots and openings in the instrument are provided for
ventilation. They ensure reliable operations, keeping
it from overheating. These openings must not be
blocked nor covered during operation.
13. Lightning
For added protection for INGVAR during a lightning
storm unplug it from the AC outlet and from all
cables connected to the inputs. This will prevent
damage to the INGVAR due to lightning and power
supply surges.
Never touch the plug and power cord if it begins to
thunder. Touching them may result in electric shock
14. Cleaning
Unplug INGVAR before cleaning
Do not use liquid cleaners or aerosol cleaners.
Use only a damp cloth for cleaning.
Stubborn stains may be removed with a cloth lightly
dampened with a mild detergent solution.
15. Damage
Do not use INGVAR if the test leads appear damaged.
Do not continue using a damaged INGVAR. Using a
damaged INGVAR may result in fire or electric shock.
Do not touch a damaged LCD panel directly with
bare hands. The liquid crystal, which leaks from the
panel, is poisonous if it enters the eyes or mouth. If
any part of the skin or body comes in direct contact
with the panel, please wash thoroughly. If some
physical symptoms result, please consult your doctor.
16. Damage requiring service
Unplug INGVAR from all connections and refer
servicing to qualified service personnel under the
following conditions:
• When any connector is damaged, including mains
plug.
• If liquid has been spilled into INGVAR.
• If INGVAR has been exposed to rain or moisture.
• If the INGVAR does not operate normally (following
the operating instructions).
• If the INGVAR has been dropped or damaged in any
way.
•When INGVAR exhibits a distinct change in
performance.
•If INGVAR begins to emit smoke, smells like
something is burning or makes strange noise.
17. Servicing
Do not attempt to service INGVAR yourself; opening
or removing covers can expose you to dangerous
voltage and other hazards.
Please refer all servicing to qualified service
personnel.
If you attempt to service INGVAR yourself the
warranty is no longer valid.
18. Returning
If, for some reason, you need to return INGVAR,
please use either the original transport box or one of
equivalent strength
BH0654BE ZP-BH05E
9
1 SAFETY
10 ZP-BH05E BH0654BE
2 INTRODUCTION
2
Introduction
2.1 General
INGVAR is intended for use in high-voltage substa-
tions and industrial environments, for laboratories and
testing purposes. INGVAR consists of a Control Unit
equipped with a control panel and a Current Unit. The
units are portable and easy to connect.
INGVAR is designed to generate short-duration cur-
rent, and is protected from overheating. Under special
circumstances, INGVAR can generate up to 5,000
amperes.
The Control Unit controls the current output (gen-
eration) from the Current Unit and is equipped with
sophisticated measurement facilities. The Control Unit
can sense the phase angle and adapt subsequent gen-
eration operations so that they all start at the current’s
zero-cross-over points. This ensures minimized DC
offset in connection with starting.
Current generation
Current can be generated in many ways:
Continuously.
During a preset maximum time.
As long as you press a button.
Until an external signal activates the stop input.
At a lower current (I/30) to avoid unnecessary heating
of the object being tested while the current is being
adjusted.
In pulses (both pulse duration and between-pulse pause
are user-definable).
The measurement section
contains/provides
Timer.
Digital ammeter (true RMS).
An additional channel for measuring a voltage or a
second current.
Direct display of the turns ratio of a current transformer.
Provisions for measuring phase angle Z, P, R, X, S, Q and
power factor (cos ϕ).
Currents and voltages expressed (if so desired) as
percentages of nominal values.
Fast-acting hold function. Measured values can be frozen
in response to a signal arriving at the stop input and/or
when the current is interrupted.
In addition to its normal working mode, there are spe-
cial INGVAR settings supporting the following types of
testing:
Testing of direct acting automatic reclosers.
Testing of sectionalizers.
Even though INGVAR features outstanding versatility,
it is very easy to use because:
You can start generation whenever desired.
You can repeat a measurement by simply pressing a
button. It is not necessary to clear the display first.
You can save different settings for INGVAR in ten different
memories.
BH0654BE ZP-BH05E
11
2 INTRODUCTION
2.2 Fields of application
INGVAR is primarily intended for:
Testing of protective relay equipment (primary injection
testing).
Testing of breakers with overcurrent tripping.
Conducting ratio tests on current transformers.
Conducting polarity tests on current transformers.
Other fields of application include:
Tests requiring high currents.
Testing direct-acting automatic reclosers.
Testing sectionalizers.
Testing ground grids.
2.3 Reservations
When set at maximum current, INGVAR is designed
only for temporary (short-duration) current genera-
tion. Do not use INGVAR for long-term generation at
full current. See the product specifications in chapter
11.
12 ZP-BH05E BH0654BE
3 PANELS
3
Panels
3.1 Control Unit panel
More detailed descriptions of the display and the
menu options appear in chapter 4 ”Display” and
chapter 5 ”Menu options”.
1. Mains inlet, 3 pin CEE connector (16 A)
2.
Display, This block contains the display which
presents times, currents or voltages as well as
messages and menus. Chapter 4 ”Display”
describes the display and its functions in greater
detail.
3.
Grounding (earth) terminal
4.
F2 and F3, fuses (T3.15AL 250V).
5.
EMERGENCY STOP
6.
I/30, enables to make the settings at a reduced
current, only 1/30 of the real test current. The
settings are approximate and work best for linear
loads.
7.
Current adjust knob to set (adjust) the generated
current.
Adjustment is sensitive to the turning speed.
OPERATE lamp indicates current generation
Green, yellow and red LEDs indicate percentage of
current generated for a specific load.
8. Miniature circuit breaker (F1) connected to the
current generation circuitry. It can be operated
manually and used as a disconnector to prevent
unintentional generation
9.
METERS
V
Voltmeter
A
Ammeter 2
For making the connections needed to measure a
voltage or a second current. This is useful when (for
example) you want to measure phase angles, polarity
or the turns ratio of a current transformer. You can
make your settings using the "V/A METER" menu
option in the MENU block.
An indicator lamp lights up to indicate whether you
have activated the Voltmeter or the A-meter 2.
WARNING
Do not connect the
A
AMMETER2 and
V
VOLT-
METER inputs at the same time.
Indicator lamps. Indicate whether ammeter 2 or
the voltmeter is enabled.
10. CURRENT UNIT, Multiconnector for interconnection
of current and control units.
11.
USB type B
1
2
6
7 9
151413
12
11
5
16
18
1083 4
19
17
BH0654BE ZP-BH05E
13
3 PANELS
12. ON/OFF switch
13.
HOLD
Press button to freeze (hold) the measured values.
When the lamp in the button glows steadily it
indicates that the Hold-function is active. Freezing
takes place:
a) when the stop condition is met
or
b) when generation is shut off, whereupon the
lamp in the button starts to flash.
The frozen value disappears as soon as you start a
new generation or press the RESET button.
RESET
Press to clear (reset) the values shown on the
display.
14.
Select/set knob Turn knob to make settings in the
display.
15. MENU, select special functions and change the set-
tings for the measuring instruments.
Press the button to get the desired menu option. Use
the Select/set knob to select a function or alter a
value. Change generation range, 0 to 66% or 33 to
100%, by turning left / right.
A
Select the range for "A-METER 1", measuring
the generated current), and specify whether the
measured values are to be expressed:
a) in amperes
b) as percentages of nominal current
c) as ratios.
V
A
Choose between using the voltmeter or the
ammeter 2 (A-METER 2, measures a second
current), select their ranges and how the values
should be expressed. You can also set the system
to measure the turns ratio of a current transformer.
SYS
Here you specify:
a) the time unit to be used by the timer
b) the amount of delay for the automatic shutoff
in accordance with the preset stop condition. In
addition you can select the language that will be
used in the display and make the desired entries
for calibration.
MEM
Recall or save settings for INGVAR in 10 memories.
APPL
Here you set INGVAR for the following
applications:
a) Normal use.
b) Testing of a direct acting automatic recloser.
c) Testing of a sectionalizer.
d) Generation of a pulse train.
ESC
Press to cancel and/or go back to the previous
level.
Also used to activate R, Z, X, ϕ (phase angle), P, S,
Q and power factor (cos ϕ) measurements or to
read the maximum current during an operation.
Press to confirm your choice and/or proceed to the
next level.
16. ON
TIME
Starts current generation. When generation starts
the timer is instantaneously reset and restarted.
MOM
Current generation starts and continues as long as
you press the button.
17.
Temperature alarm, is lit if the temperature rises
too high and INGVAR risks becoming overheated
14 ZP-BH05E BH0654BE
3 PANELS
18. OFF, stops current generation
STOP INPUT, here you enter the stop condition.
When this condition is met, the current generation
and timer stops. The measured value can be frozen
(held).
AUTO
, activates the automatic shutoff-function. ING-
VAR will automatically stop generating current after
a specified period of time. Press the button until the
MAX TIME lamp lights up, and enter the maximum
generation time using the Select/set knob in the
MENU block
This button can also be used to activate the auto-
matic shutoff when a stop condition is met. Press the
button until the STOP INPUT lamp lights up, and
enter the desired stop condition in the STOP INPUT
block.
INT Internal detection. Hold/Stop takes place when
the current is interrupted by the object being
tested.
Voltage
mode
The input
responds to
application or
interruption of
voltage
The input
responds to
application of
voltage
The input
responds to
interruption
of voltage.
Contact
mode
The input
responds to
the opening
or closing of a
contact
The input
responds to
closing of a
contact.
The input
responds to
opening of a
contact.
The status lamp adjacent to the connection sockets
is lit:
In the voltage mode — if voltage is present.
In the contact mode — if the contact is closed.
When the preset stop condition is met the LATCH
lamp is lit. Resetting takes place automatically when
you start a new generation or when you press the
RESET
button.
See chapter 7 for stop condition settings.
19. OUTPUT SETTING, indicates how the Current Unit
output is configured – parallel or serial.
BH0654BE ZP-BH05E
15
3 PANELS
3.2 Current Unit panel
1
42 3 5 6
1
CONTROL UNIT, input terminal for connection to
INGVAR Control Unit
2
OUTPUT, current output
Terminals for parallel or serial configuration
3
4
Sensor for the output configuration (parallel/serial)
5
OUTPUT, current output
Terminals for parallel or serial configuration
6
3.3 Cables
Standard cables
Interconnection cable
Cable, 3 m (10 ft) for connection of the Control Unit to the
Current Unit.
16 ZP-BH05E BH0654BE
3 PANELS
Current cables
Standard current cable set, 2 x 2 m (6.5 ft) , 120 mm
2
Grounding cable
Cable for protective grounding, 5 m (16 ft), 16 mm
2
Mains cable
Mains cable, 3 m (10 ft), 240 V / 16 A
Optional cables
Interconnection cable, 5 m (16 ft) GA-12705
Interconnection cable, 10 m (33 ft) GA-12710
Current cable set 2 x 0.5 m (1.6 ft) 3 x 120 mm
2
with end-bars.
GA-12305
BH0654BE ZP-BH05E
17
2 INTRODUCTION
18 ZP-BH05E BH0654BE
4 DISPLAY
4
Display
4.1 The display
Presents measured values.
Presents INGVAR´s settings.
Guides you by providing helpful messages, warnings and
prompts.
Helps you scroll through menu options by displaying
directional indicators.
The display is divided into 4 areas. Normal use:
Time
Ammeter 1 Ammeter 2 / voltmeter
Example:
1.234 s
750 A 3.123 V
By pressing the
ESC
button; Z, ϕ (phase angle) & Z, P,
R, X, S, Q, power factor (cos ϕ) or max I
1)
will appear
in the upper area of the display.
1)
Max I is the highest current value that was gener-
ated (minimum time 100 ms) during the injection.
Example:
4.164 mW Z
750 A 3.123 V
O.F.” (Overflow) in an area means that the value is
too high.
- - - ” in a field means that it is impossible to present
a value. The reason can be too low measurement
signal or that it is impossible to calculate a value.
If you press
the measured values will be dumped
via the USB port, see appendix 1 for details.
Directional indicators
The directional indicators that appear on the display
show which direction you can scroll using the Select/
set knob
. There are three types of directional markers:
You can scroll upwards
You can scroll downwards
You can scroll both up and down
When special applications are
activated
When a special application is activated this is indicated
in the upper right corner.
Example:
Application ”TEST RECLOSER
1.234 s RECL.
750 A
See further the descriptions of the application modes,
chapter 8 ”Application examples”.
BH0654BE ZP-BH05E
19
4 DISPLAY
20 ZP-BH05E BH0654BE
5 MENU OPTIONS
5.1 General
This chapter explains the menu options available in
the MENU block on the control panel and the settings
that you can make there. All settings appear on the
display.
You can only select a menu option while INGVAR is in
the OFF state (i.e. not generating).
There are three ways to exit from a menu option:
A] Press the button of the most recently selected
menu option a second time.
B] Press
TIME
C] Press
RESET
5.2 AMMETER, V/A METER
and SYSTEM menu options
You can set INGVAR’s first ammeter ("A-METER 1") in
the "AMMETER" menu option. In the "V/A METER"
menu option you can set INGVAR’s second amme-
ter ("A-METER 2") and INGVAR’s voltmeter. In the
"SYSTEM" menu option you can set the timer, select
the desired language for use on the display, and make
certain other settings. The menu options are described
in detail below.
How to set values
An example of how the display can appear for the
"AMMETER" menu option appears below. The top
line (the menu heading) shows what is to be set. The
second line (right-justified) shows the actual setting.
You can use the Select/set knob to scroll through
the different menu headings. The directional indica-
tors show the direction or directions in which you can
scroll.
Example:
RANGE
Auto
You can scroll upwards.
Select the desired menu heading ("RANGE" for ex-
ample) and press . The value will appear between
flashing arrow-heads < >:
RANGE
< Auto >
You can now change the setting (to the low ampere
range for example) using the Select/set knob.
Press
to confirm your choice.
You can press the
ESC
button to leave the field with-
out changing it or to return to the previous level.
A-METER 1
In this menu option you can make settings for ING-
VAR’s intern ammeter ("A-METER 1"). You can select
the range and the unit in which the reading is to be
5
Menu options
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72