COMMON TERM USED WITH METER READINGS
VOLTAGE: The potential between phase and neutral or phase to phase. This can be 120 to 480 volts depending
upon the model selected.
AMPERE: A unit of electrical current, which will flow through a resistance of 1 ohm by 1 volt.
WATTS: A unit of active power, which is defined as the rate at which energy is delivered to a circuit. This is the
power expanded when a current of one Ampere flows through a resistance of one ohm.
kW: A common abbreviation for 1000 watts.
KW DEMAND: A measurement of energy (kW) or (KVA) over a choice of a time interval in 15 or 30 minutes,
which is most common. A thumb rule method is to count kWh in 15 minutes and multiply by four. Multiply by two
if the demand interval is 30 minutes.
ROLLING OR SLIDING WINDOW: A demand interval that moves in time through a sub-interval. One
example would be a 15-minute demand interval could comprise of 15 one-minute sub-intervals. The first 1-minute
sub-interval will slide into the next measuring period, dropping the last sub-interval. This is the method used in this
meter, and by many utility companies.
WATT-HOUR: A unit of electric energy that measures one watt in one hour. There are one thousand-watt hours in
one-kilowatt hour.
HERTZ: A practical unit measuring the number of positive and negative values occurring in one second. Sixty Hz
is typical in the US and fifty is used in Europe.
VOLT-AMPERE: A unit of volts and current that flows because of the voltage. Volt-ampere and kilowatts are the
same at unity power factor. In an AC circuit with power factor other than unity the VA equal the square root of watts
squared plus reactive volt-amperes squared. The greater the VA over kW is reflected by poor power factor.
KVA: A common abbreviation for 1000 volt-amperes.
POWER FACTOR: The ratio of active power (kW) to apparent power (KVA). Power Factor (PF) can be corrected
by capacitors or synchronies motors.
THD and D (TOTAL HARMONIC DISTORTION and Distortion):
Lets defined linear and non-liner loads. From a simple and practical point of view, a linear load is that, when
supplied by a sinusoidal voltage, absorbs also a sinusoidal current. On the contrary, a non-linear load will absorb a
non-sinusoidal current for the same supply voltage, although such current is habitually of periodical type.
Representative examples are Static power converters, AC to DC power supplies, Discharge lamp lighting, Arc
furnaces, electric welding machines, Transformers, Iron core reactors, etc.
The Distortion can be measured in two different ways, giving parameters known as “d” and “THD”. THD rate is
referred to the total R.M.S. value where as d is obtained by multiplying a fundamental voltage by a series of currents
with frequencies multiple of the fundamental frequency.
Expected distortion rates commonly found in power systems are 5% and below in voltage and 30% and lower in
current. Higher readings do not necessarily mean a faulty facility but should be looked at for a potential problem.
PULSE OUTPUTS: Each pulse represents a predetermined increment of power or other quantities. Relay 1 in this
meter is factory programmed for 1 pulse equals 1 kWh.
ALARM RELAY: Relay 2 may be field programmed to indicate high levels of energy or powers. The relay can
operate in conjunction with local indicators i e, horn or light.
8.