ICP PAPC24GA1 Owner's manual

Type
Owner's manual
Installation Instructions
I DIRECT DRIVE BLOWER
PA95/PAPC
PA55/PAPA SERI ES
SINGLEPACKAGEAIRCONDITIONERS
ELECTRICCOOL/
ELECTRICHEAT(OPTIONAL)c
TABLEOFCONTENTS
1. Safety Labeling and Signal Words .......................... 2
Danger,Warningand Caution .................................... 2
2. Safe Installation Requirements ....................... 2
3. Locating The Unit .................................. 2
Clearances ............................................... 2
Dimensions................................................... 2
MinimumClearancesto CombustibleConstruction..................... 3
Installation ................................................... 3
InstallingDuctCollars ........................................ 3
CondensateDrain ............................................. 4
4. Electrical Wiring .................................... 4
Ground Connections........................................... 4
LineVoltageWiring ............................................. 4
Unit Disconnect ............................................... 4
Converting230V Unitsto 208V .................................... 4
LowVoltageWiring ............................................ 4
ThermostatConnections......................................... 5
FieldInstalledEquipment ........................................ 5
5. Electric Heat Installation ............................. 6
GeneralInformation ................................ 6
AdjustingTherrnostatAnticipator ................................. 6
UmitControls .............................................. 6
TimeDelayOperation ................................... 6
Staging .................................................. 6
InstallHeater ................................................. 6
HeaterWiring ........................................... 6
Grounding ................................................ 6
InstallingWiring .......................................... 7
Unit DisconnectBreaker ......................................... 8
RainShieldInstallation ......................................... 8
6. Air Distribution System .............................. 9
Ductwork .................................................... 9
DuctworkInsulation ............................................ 9
DuctwotkConnections.......................................... 9
Fi_ers .............................. 9
7. Start-up Procedures ............................... 10
FinalElectricalCheck ................ 10
CirculaUngAirBlower .......................................... 10
Determining8_owerSpeed.......... 10
Steed Taos ............................ 10
Cooling andAuxiliaryElectric Strip Heat ............................ tO
CheckBeforeStarting ...................... 10
CirculatingAir Blower ..................... 11
Cooling ................................................... 11
AuxiliaryHeating ......................... 11
TemperatureRiseCheck ..................... 11
Sequenceof Operation ......................................... tt
CoolingMode:Energized(R,G,Yt_ De-energized_N/At................ 11
8. Operation .......................................... 11
Scroll Acti-Cycle Timer(WhereApplicable}.......................... 11
TurningTheUnit Off ....................... 12
ThermostatFan SwitchOperation................................. 12
AdjustingRoomTemperatures ...... 12
13. Maintenance .................................. 12
MonthlyMaintenanceandInspectionChecks ........................ 12
Air Filters ................................................ 12
CoolingSeasonChecks(Monthly)................................. 12
CondenserCoil ........................................... 12
CondensateDrain............................................ 12
AnnualMaintenanceand Inspection ............................... 12
Condense"FanMotor ......................................... 12
CirculatingAir Blower ......................................... 12
Printed in U.S.A. 426 011001 02
2/20/96
1. Safetv Labelinq and Siflnal Words
Danger,Warningand Caution
ThesignalwordsDANGER,WARNINGandCAUTIONareusedtoidentifylevelsofhaz-
ard seriousness.The signalword DANGERis onlyusedon productlabelsto signifyan
immediatehazard.The signalwordsWARNINGandCAUTIONwillbeused onproduct
labelsandthroughoutthis manualandothermanualsthatmayapplyto theproduct.
2. Safe Installation Requirem ents
CAUTION
Do NOToperate unit in acorrosive atmosphere containing chlorine,
fluorine, or any other corrosive chemicals.
Installation or repairs made by unqualified persons can result
in hazards to you and others. Installation MUST conform with
local building codes or, in the absence of local codes, with the
National Electrical Code NFPA70-1990 or current edition.
The information contained in this manual is intended for use
by a qualified service technician familiar with safety proce-
dures and equipped with the proper tools and test instru-
ments.
Failure to carefully read and follow all instructions in this
manual can result in unit malfunction, property damage, per-
sonal injury and/or death.
Seal supply and return air ducts.
Check to see that filters are installed correctly and are the proper
type and size.
NOTE:Itisthepersonalresponsibilityandobligationofthecustomertocontactaqualified
installerto ensurethattheinstallationisadequateandconformsto governingcodesand
ordinances.
3. Locatinq & Installinq The Unit
The unitis designedfor outdoorinstallationonly.Placethe unit ona platformatground
level. The unitmay beinstalledon a concreteslabof 48" (1219mm)x48" (1219mm)
dimensions. Cementblockson a 3" sand footing willalso work. The slabor blocks
SHOULDNOTbein contactwith any partofthe structure. Checklocalcodescovering
zoning,noise,platforms,etc..
Ifpracticalavoidlocatingnexttofreshair intakes,ventorbedroomwindows. Noisemay
carryintotheopeningsanddisturbpeopleinside.
Avoid installationsunderroofoverhangswithoutguttering. Waterdrainingfromthe roof
ontotheunitcouldproduceexcessivenoise,and maycauseicetobuilduponcoil orfan.
Placementoftheunitshouldbeinawelldrainedareaortheunit MUSTbesupportedhigh
enoughso runoffwillnotenterthe unit.
Do notlocateunitwhereheat,lint orexhaustfumeswill bedischargedon unit (asfrom
dryervents.)
Clearances
Minimum clearances,as specifiedin FIGURE 1, MUSTbe maintainedfrom adjacent
structuresto provideadequateaircirculationand roomfor service personnel.
While minimumclearancesare acceptablefor safetyreasons,theymay notallowade-
quateaircirculationaroundtheunitforproperoperation.Wheneverpossible,it isdesirable
toallowadditionalclearance,especiallyaroundthecondenserinletanddischargeopen-
ings.
Do NOTinstalltheunitin arecessedor confinedareathatwillpermitdischargedairfrom
thecondensertorecirculatetothe condenserinlet.
Dimensions
NOTE: DUCT COLLARS ATTACHED TO SUPPLY AND RETURN MUST BE REVERSED AT INSTALLATION. SEE INSTRUCTIONS ON PAGE 3.
ALL DIMENSIONS IN iNCHES ROUND SHAPED FLANGE WiLL
ACCOMMODATE 12" DIA.
SUPPLY DUCT
t
26.5
COIL
ACCESS
PANEL
ROUND FLANGE
WILL
ACCOMMODATE
14_ DIA.
RETURN DUCT
T m
10
\ 41
CONDENSATE DRAIN
CONECTION
* ELECTRICAL ACCESS FOR LINE VOLTAGE POWER SUPPLY-ONE FOR UNIT, ONE FOR HEATER
** FOR LOW VOLTAGE WIRING
DIA HOLE**
_/4 DIA.*
_/4 DIA.*
3/4
Minimum Clearances to Combustible Construction
SERVICE ACCESS CLEARANCES
Blower Access Panel Side .......................... 30" (762mm)
Electrical Access Panel Side ........................ 30" (762mm)
OPERATIONAL CLEARANCES
Combustible Base
(Wood or Class A, B or C
roof covering material) ......................... 0"
Supply and Return Air Ducts ................................. 0"
Duct Connection Side
Clearance between Overhang
and Top of Unit ..................... 48" (1219mm)
Clearance around Condenser Coil area to wall or shrubs ........ 10"
I
FIGURE 1
I Minimum Clearances and Access Panels
I
Overhang
Evaporator 48" Minimum Overhang Clearance
Access Panel
f 10"around
condenser
coil area
6" Blower/Electrical
Access Panel
Cover Plate
Installation
CAUTION
The unit must be installed as level as possible, with a maximau
slope no greater than 1/8" per foot (10mm per meter). For side to side
leveling, the condensate drain side of the unit MUST always be lower
to provide proper drainage.
The unit MUST be situated in such away as to provide safe access
for servicing.
The platform may be made of either concrete or pressure treated
wood and MUST be level and strong enough to support the unit's
weight.
Position platform separate from the building's foundation.
install in a well-drained area, with the top surface of the platform
high enough above grade level to allow installation of a conden-
sate drain trap. See FIGURE4
FIGURE 2 Blower Compartment
Installing Duct Collars
Ductcollarsaresuppliedwiththe unitand areattachedtothesupplyandreturnopenings
withthe flanges totheinsideandmustbereversedbeforeunit'sinstallation.
1.Remove the screws from the collars and reverse them so the flange
isto the outside.
2. Make sure when pushing the collars into place that the "V" flange of
the collars seats into the supply and return holes securely.
3. Re-install screw in each collar so it goes through both of the holes in
the collar end. It does not matter how the ends of the collar overlap
in order to accomplish this.
FIGURE 3 I Duct Collar Installation I
CondensateDrain
Thecondensatedrainoutletisa 314" (19.1mm)threadedfemalePVCconnectionlocated
atthebottom oftheunittothe leftoftheevaporatoraccesspanel.
Thecirculatingblowerandthe condenserfancreateanegativepressureontheconden-
satedrain linethatwillpreventthe condensatefromdrainingproperlywithouta trap.To
combatthisnegativepressure,afieldsuppliedcondensatetrapthatwillallowastanding
columnofwaterofatleast2" (50.8mm)MUSTbeinstalled.Theoutletofthetrapmustbeat
least1"belowthe unitdrainconnection.Install the trapas nearto theunitaspossible
for properdrainage.
A3/4" (19.1mm)drainlineMUSTbeinstalledif requiredby localcodesor iflocationofunit
requiresit. Runthe drainlineto anopen drainor othersuitabledisposalpoint.
FIGURE 4
3/4" (19.1mm)
Threaded Female
PVC Fitting
Condensate Drain Information *
1"
(25.4mm)
3/4" (19.1mm)
Drain Line
33/4 ""
(82.5mm) 2" (50.8mm)
_,_kv * Condensate trap MUST be installed.
4. Electrical Wirinq
Electrical shock hazard.
Disconnect power at fuse box or service panel before making
any electrical connections.
Unit MUST be grounded to electrical service panel.
Failure to follow this warning can result in property damage,
personal injury, and/or death.
NOTE:All electricalworkMUSTconformwith therequirementsof localcodesandordi-
nancesand in theUnitedStateswith NationalElectricalCodeANSI/NFPA70-1990 (or
currentedition). Providelinevoltagepowersupplyfrom aseparatefused circuitwitha
disconnectswitch(whenrequired)locatedwithinsightoftheunit.Supplyvoltage,amper-
age,fuseanddisconnectswitchsizesMUSTconformwithlocalcodesandordinances.
WiringMUSTbe protectedfrompossiblemechanicaldamageandMUSTNOTinterfere
with removalofaccesspanels,filters, etc.
AllexposedlinevoltageconnectionsMUSTbemadethroughliquidtightconduittoprevent
waterfromenteringthe unitthroughtheelectricalaccess..
Ground Connections
Agroundlugisinstalledonthecontrolplate(orelectricheatmountingplate)forthe ground
connection.Use acopperconductorofthe appropriatesizefromtheunitto a grounded
connectionintheelectricalservicepanelortoa properlydrivenandelectricallygrounded
groundrod.
Line Voltage Wiring
DoNOTcompletelinevoltageconnectionsuntilunitispermanentlygrounded.Alllinevolt-
ageconnectionsandthegroundconnectionMUSTbemadewithcopper wire.
Connectionsfor linevoltagearemadeontheunitelectricalcontrolplate(seeFIGURE7).
For access,removethe Blower/Electricalaccesspanel.
Refertoapplicablewiringdiagram andFIGURE6.Completethelineserviceconnections
tothe contactor'L'terminalson theelectricalcontrolplate.Checkallscrewterminalsto
ensuretheyare tight.
NOTE:IfanElectricHeatAccessoryisinstalled,refertotheElectricHeatAccessorysec-
tion of thismanualto determinelinevoltageconnections.The ElectricHeatAccessory
mountsinsidethe unitin theheaterbox.Fieldsuppliedlinevoltage wiresfor theElectric
HeatAccessory(separatefromthefieldsuppliedlinevoltagewirestothe unit)connectto
theappropriatecircuitbreaker(ifused)in theElectricHeatAccessory.
Unit Disconnect
ADisconnectSwitchKitisavailablethatinstallsinsidetheunitoraseperatecircuitbreaker
maybeinstalledtocontrolthe unit.Refertoinstructionsfollowingheaterinstallationsec*
tion.
Converting 230V Units to 208V
Toconvert230V unitsto208V:
1.Turn electric power OFF.
2. Remove the blower/electrical access panel.
3. Locate the 24V control transformer.
4. Remove wire from the terminal labeled "240V" on the 24V control
transformer and reconnect it to the 208V terminal of the 24V control
transformer.
5. Replace the electrical/compressor access panel.
Low Voltage Wiring
For access,removethe electricalcontrol/bloweraccesspanel.
Refertotheconnectionwiringdiagramforthe applicablemodelandtotheinstructionsin-
cludedwith thethermostat.
Routelow voltagewiresthroughthe portlocatedonthe rearpaneland upto the control
box.
NOTE:IfanElectricHeatAccessoryisinstalled,seetheElectricHeatAccessoryInstalla-
tion Sectionof thismanualfor lowvoltage connections.
ThermostatConnections
Thelocationofthethermostathasanimportanteffectontheoperationofthe unit.Seethe
thermostatinstructionsfor properconnection.See FIGURE5for LowVoltageWireHar-
nessConnections
Field Installed Equipment
Wiringtobedoneinthefieldbetweenthe unitandotherdevices,or betweenseparatede-
viceswhicharefieldinstalledandlocated,MUSTNOTexceedthetemperaturelimitations
fortypeT wireandMUSTbeinstalledaccordingtothemanufacturer'sinstructionsforthe
devices.
J Electronic Thermostat Low Voltage Wiring
FIGURE 5 Harness Connection Diagram
Typical Thermostat Subbase
[,q [?] [R,]
I I I I I
I I I I I
, = = , (when used)
I I I I I
i i , , [W'h
[Blue] [Green] [Red] [Yellow] ite]
Com Fan 24V Comp Elect.
(when Cool Heat
used) Acces.
Unit Low Voltage Wiring Harness.
FIGURE 6 J Typical Connections at Unit
"F_'I
I
II
II
aCT I '
I I
I I
I
I
USE CO PPER CONDUCTORS ONLY
208/Z30V 60HZ 7PH
I
I
I
I
I
] I
J
F _ 3 1
'1 K_ I I\ I
' -_ I I'l'' I_
I BL I J GND L__ R__/_R
I
L=BL
THERMOSTAT
OONNEOTION£
FIGURE 7 J Control Box Configuration
Blower
Relay or
Sequencer
Transformer
\
Anti-Cycle Time
(If Used)
Capacitor
Ground lug,
Contactor
Component Wire
Opening
Control Box
Line Volt Wire Entrance
Low Volt
5. Electric Heat Installation
General Information
Adjusting Thermostat Anticipator
Set theheatanticipatorofthe thermostattothe propervalue.See instructionsprovided
with thethermostatbeforemakingthisadjustment.
ModelNumber AnticipatorSettin_l
AMMK05AHBIA .18
AMM F,U/API_tA ,;Jb
.._IVl IVli% I U,_,I'ID/P_ .,.lt_
^_AHV4c^t _ntA ,_
A_A_I _OI'_AWRIA _A
Limit Controls
Thelimitcontrolsaremountedonthefaceofthe heaterandarewiredintothesupplywires
toeachelement. Ifthereis notenoughairflowthroughtheheater,thelimitwillopenand
breakthe powercircuit. The limitwillreset whenthe electricaccessorycoolsdown.
Time Delay Operation
TheheaterelementsareswitchedON andOFFthroughoneormorecontrolswhichoper-
atethroughthe lowvoltagethermostatcircuit.
Thesecontrolsconsistofanumberoftimedelaysdependingonthespecificheatermodel.
Anelectricheataccessoryhas 1,2or 3ofthesecontrols.Thefirsttimedelayisactivated
whenthethermostatcontactsclose.Approximately1to20secondslatertheindoorblower
andthefirst heaterbankareenergized.Approximately70secondsafterthefirst heater
bankisenergizedtheremainingtime delaysandheaterbanksareenergized.
Staging
Some electric utilities require staging on electric heaters larger than 6 kilo-
watts. Therefore, the heater elements are turned on in 5 or 10 kW incre-
ments under control of the sequencers.
Ifstaging based on heat loss or demand is required, the use of accessory
outdoor thermostats is recommended. The heat sequencer wiring isde-
signed to be staged by breaking the 24V "Common" Leg (normally brown
or gray). Outdoor thermostats available through your wholesale supplier
allow the control of two or four stages of electrical heat.
Some indoor electronic thermostats may provide for multiple stages of
electric heat. When this type thermostat isused, it may be necessary to
break the 24V "Hot" leg of the sequencer (as fed from the "W' circuit at the
thermostat). This will require field modification of the control wiring and
should only be done by an experienced controls technician or electrician.
Install Heater
1. Shut OFF electric power at unit disconnect switch or service panel.
2. Remove the blower access panel from unit.
NOTE: Installation of field wiring and conduit for heaters to the
unit prior to installing the heater will simplify wiring of heaters.
3. From inside the blower compartment, remove the six screws on the
heater cover plate and save the screws. Discard the heater cover
plate.
The screws will be used later to mount the electric heat accessory
and its cover.
4. Remove the cardboard wrapper from the heater's elements.
5. Insert the heater into the heater/blower box. Exercise caution to
prevent damage to heater elements.
6.Secure heater to heater/blower box with four of the six screws re-
moved in Step 3.
FIGURE 8 Typical Electric Heat Accessory
Breaker- Style Heater rle
FIGURE 9 Installing The Electric Heat Accessory
Heater Wiring
Grounding
Permanentlygroundthe electricheataccessoryinaccordancewithlocalcodesandordi-
nancesandintheUnitedStateswithNationalElectricalCodeANSIINFPA70-1990orcur-
rent edition. Use a copper conductorof the appropriate sizefrom the electric heat
accessorytothe groundlug onthecircuitbreakerpanelas shownin FIGURE10.
Installing Wiring
Whenanelectricheataccessoryis installed,twoseparatefieldpowersuppliesMUSTbe
provided- one or more forthe electricheataccessoryandone for theunit.
1.Shut OFF electric power at unit disconnect or service panel.
2.Installtheappropriatefieldsuppliedconduitfittingintotheheater
knockoutlocatedin the rear panel of the unit. The knockout is sized
11/4" in diameter.
NOTE: Check FIGURE 11 for heater/speed combinations that are
unacceptable.
3.Connect field installed copper ground wire(s) to the ground lug(s) on
the heater mounting plate. On models with more than one circuit, a
separate copper ground wire MUST be connected to a separate
ground lug for each circuit.
4. Route the field supplied line voltage wires for the heater to the line
side of the electric heat accessory's circuit breaker(s) or high voltage
wiring harness. Leave approximately 8" of excess wire so the break-
er or wiring harness may be moved to service. Make line voltage
connections to L3-L6 as appropriate. NOTE: If heaters without
breakers are used, route field wires to inside of unit and attach to
heater wires tagged L3-L6 as appropriate using supplied wire nuts.
5.Connect the black wire with terminal from the heater wire harness to
the loose black wire at the unit blower or appropriate speed tap if
lower speed is desired in electric heat mode.
FIGURE 10 1
6 Connect the red wire with terminal in the heater wire harness to the
loose red wire from the unit sequencer.
7.Connect the white wire from the heater wire harness to the white wire
from the thermostat at the field supplied low volt wire harness in the
control box.
8.Connect the grey and brown wires from the heater wire harness to
the blue wire from the unit 24V common. NOTE: If outdoor thermo-
stats are used for staging electric heat, connect the grey and brown
wires according to the thermostat instructions. See "Staging" in
Electrical Wiring Section of this Manual.
After completing installation of the heater, install the breaker rain shield on
the blower access panel according to the following instructions on page 8.
Ifusing a pigtail style heater, proceed to Start-Up Procedures for Auxiliary
Electric Strip Heat on page 10.
Typical Wiring Installation ( Breaker Style Heater Shown-Pigtail style also available)
Access hole for
low voltage
wires
Unit Line Volt-
age Wires
Knockout for unit
field supplied line
voltage wires
Ground
Lug
Heater
Ground Lug
Unit blower heat-
ing speed tap
leads
FIGURE 11 Accessory Electric Heater Electrical Data
MaximumOverourrent
HEATER Nominal Heating Supply Heater MininumCircuit ProtectiveDevice
MODEL UsedWith SupplyVoltage KWRating BTUH CircuitNo. Amps Ampacity (Amps)
AMMK05AHA 2-5 TON 240-1-60 4.8 t6,382 L3_L4 20.0 25.0 30
AMMK05AHB 208-1-60 3.6 t2,287 L3- L4 17.3 21.6 25
AMMK07AHA 2-5 TON 240-1-60 7.5 25,598 L3-L4 3t.2 39.1 45
AMMK07AHB 208-1-60 5.6 19,113 L3-L4 26.9 33.6 40
AMMK10AHA 2-5 TON 240-1-60 9.6 32,765 L3- L4 40.0 50.0 60
AMMK10AHB 208-1-60 7.2 24,574 L5- L6 34.6 43.3 50
L3- L4 40.0 50.0 60
AMMK15AHB 21/2-5 TON 240-1-60 14.4 49,t47 L5- L6 20.0 25.0 30
L3- L4 34.6 43.3 50
208-1-60 10.8 36,860 L5- L6 17.3 21.6 25
L3- L4 40.0 50.0 60
AMMK20AHB 21/2-5 TON 240-1-60 19.2 65,530 L5- L6 40.0 50.0 60
L3- L4 34.6 43.3 50
208-1-60 14.4 49,t47 L5- L6 34.6 43.3 50
FIGURE 12 Accessory Electric Heater Heating Data
*TemperatureRise °F @ CFM
Heater
Model
AMMK05AHA
AMMK05AHB
AMMK07AHA
AMMK07AHB
AMMK10AHA
AMMK10AHB
AMMK15AHB*
AMMK20AHB**
UseWith
NC: 2-5 TON
NC: 2-5 TON
NC: 2-5 TON
21/2-5 TON
21/2-5 TON
SupplyVoltage KWHating
240-1-60 4.8
208-1-60 3.6
240-1-60 7.5
208-1-60 5.6
240-1-60 9.6
208-1-60 7.2
240-1-60 14.4
208-1-60 10.6
240-1-60 19.2
208-1-60 14.4
TotalHeating
BTUH 600 800
16,832 25.3 t9.0
12,287 19.0 t4.2
25,596 39.5 29.6
19,113 29.5 22.t
32,765 50.6 37.9
24,574 37.9 28.4
49,147 --- 56.9
36.860 56.9 42.7
65,530 ......
49,147 --- 56.9
1000 1200 1400 1600 1800 2000 2200
15.2 12.6 10.6 9.5 8.4 7.6 ---
11.4 9.5 8.1 7.1 6.3 5.7 ---
23.7 19.8 16.9 14.8 13.2 11.9 10.8
17.7 14.7 12.6 11.1 9.8 8.8 8.0
30.3 25.3 21.7 19.0 16.9 15.2 13.8
22.8 19.0 16.3 14.2 12.6 11.4 10.3
45.5 37.9 32.5 28.4 25.3 22.8 20.7
34.1 28.4 24.4 2t.3 19.0 17.1 15.5
- - - 50.6 43.3 37.9 33.7 30.3 27.6
45.5 37.9 32.5 28.4 25.3 22.8 20.7
* 15KWHEATERNOTTO BE OPERATEDON LOWTAPFOR2 1/2 TONNC ANDHP.
** 20KWHEATERNOTTOBE OPERATEDON LOWORMEDIUMLOWTAPFOR3AND3 1/2NC ANDHP.
Unit Disconnect Breaker
FIGURE 13 l Installing Circuit Breaker
SpringClipReleaseTab
Rain Shield Installation
FIGURE 14 I Installing The Rain Shield
1
CLOSED CELL FOAM PAD
1/8" THICK 3 3/8' X 71/16"
IN SIZE, ADHESIVE BACKED.
INSIDE
CIRCUIT BREAKER COVER.
BREAKER
HEATER PLUGS
RAIN SHIELD
1.Removeallscrewsfromthecoverplateon Blower/ElectricalAccessPanel.
Ifaseperateunitdisconnectbreaker/switchisrequireditcan beinstalledinsidetheunitin 2. InstalladhesivebackedgasketonBlower/ElectricalAccessPanel.
theheateraccessoryorasa singleinstallationbyusingtheDisconnectSwitchKit.Asep
eratepowersupplycircuitmustbeprovidedforthe unit. 3. Installlowerframeofrainshield with4 screws.
1.Toinstallthecircuitbreakerorswitch,insertthebottomfootofthebreakerintolower
mountingholeontheheaterpanelwiththebreakerat aslightangleoutfromthe 4. Installrainshieldhingedcoverwith4 screws.
panel.
2.Pushbreakerin towardspanelandlift upslightlyso breakerfits intothetopmount-
ingholeandsnaps(locks)inposition.
Breakershavealockingspringcliptoholdthem inposition.Toremovebreakerliftupon
thereleasetabon topofthebreakerand pullout and downslightly.
FIGURE 15 Accessory Electric Heater Heating Data
5. Installcircuitbreakerfillerplates(2eachperunusedbreakerslot.)
6. Re-installBlower/ElectricalAccessPanel.
NOTE: VERIFYALLAPPROPRIATESEALSARE iN PLACE.SEE FIGURE14.
Breaker Amps Part Number Application
25 1082008 PA9524, PA5524, PAPA24, PAPC24
30 1082009 PA9530, PA5530, PAPA30, PAPC30
35 1082010 PA5536, PAPA36
40 1082011 PA9536, PAPC36
45 1082012 PA9542, PAPC42
50 1082013 PA5542, PA5548, PAPA42, PAPA48
60 1082014 PA9548, PAPC48
60 Switch 1082042 Fits AII- Disconnect Switch Only (No Over Current Protection)
AMMO01 DSA DISCONNECT SWITCH KIT (includes 60A switch & rain shield) BREAKER FOR UNIT ONLY.
FOR "NO HEAT" or PIGTAIL STYLE HEATER APPLICATION ONLY.
6. Air Distribution System
Forairflowdata(blowerperformancedata,blowerspeedtapsettings,etc.)seetheTechni-
calDataSheetattachedto theunit..
Ductwork
Ductwork Insulation
Itisrecommendedthatductworkinstalledoutdoorshaveaminimumof2" (51mm)offiber-
glassinsulationandbecoveredby aweatherproofvapor barrierthatisprotectedagainst
damage.Caulkingandflashings,or othermeansadequatetoprovideapermanentweath-
er seal,must beused.
Itisrecemmendedthatductworkinstalledin atticsorotherareasexposedtooutdoortem-
peratureshaveaminimumof2" (51ram)fiberglassinsulationandhaveanindoortypeva-
por barrier.
Ductwork Connections
Theuseofflexible,non-combustibleconnectorsbetweenmaintrunkductsand supply
andreturnairplenumsis recommendedto minimizevibrationtransmission.
NOTE: Connectsupplyandreturnairplenumsto unitin amannerthatwillallowthetopof
theunittoberemovedwithoutremovingplenums.PlenumsMUSTbeindividuallysealed
to unitcasing.DuctsMUSTbeterminatedinsidestructure.
Filters
AllreturnairMUSTpassthrough afieldsuppliedfilterbeforeenteringtheunit.Ifused,an
electronicair cleanerMUSTbe installedin the return air ductwork. Minimum recom-
mendedfilter areasare listed inFIGURE16and arebasedon a velocityof300 ftfmin
(12m/s) for disposablefiltersand500ff/min(2.54m/s)for washablehighvelocityfilters.
CAUTION
NOTE:Thetotal heatgain ofthestructuretobeconditionedas expressedintotal Btuihr
shouldbe calculatedby manufacturer'smethodor in accordancewith"A.S.H.R.A.E
Guide"or"ManualJ - LoadCalculations"publishedbytheAirConditioningContractorsof
America.Thetotal heatgaincalculatedshouldbeequaltoor lessthan the coolingcapac-
ityoutput basedon D.O.E.test procedures,steadystate efficiencytimesinput.
Ductwork,supplyregisters,and returnairgrillesMUSTbedesignedand sizedto handle
theunit'scoolingairvolume requirements,tftheunitis connectedtoanexistingsystem,
theductworkMUSTbecheckedtomakesureitisadequate.Extrarunsorlargerductsizes
mayhaveto beinstalled.
Maximumrecemmendedvelocityintrunkductsis1000feetperminute(5.08m/s).Velocity
in branchesshouldnotexceed800feet perminute(4.06m/s).RefertotheTechnicaIData
Labelontheunit forunit airvolumerequirementsandsystemsizingrecommendations.
NOTE:Ductworksizingaffectstemperatureriseandcoolingtemperaturedifferential.Be
suretoproperlysizeductworktothecapacityandairflowcharacteristicsofyour unit.Fail-
uretodoso canaffectlimitcontrols,compressors,motors,andothercomponentsandwill
leadto prematurefailure ofcomponents. Thiswillalsoadverselyaffectday to dayunit
performance.
FlexibleDuctKitsareavailablefromyoursuppliertoeffectpropersizingandinstallationto
MobileHomesandother standardconstruction..
Refertounitratingplatefor properElectricHeatAccessorysizingandsee the Tempera-
tureRiseChecksectionintheElectricHeatAccessorylnstallaUonSectionofthismanuaL Do NOT operate the unit without all filters in place.
FIGURE 16 Recommended Filter Sizes
NOTE: Somefiltersaremarkedwithanarrowtoindicatethe properdirectionofairflowthroughthefilter. The airflow directionwillbetowardstheblowermotor.Makesurefilter i
installedcorrectly.
2
21/2
3
31/2
4
5
Nominal Tons
Air Conditioning
Nominal Air Flow
Cubic Feet
per Minute
700-900
900-1100
t100-1300
1300-1500
1500-1700
1900-2100
Recommended Filter Sizes
Sq. In. Surface Arep/Nominal Size
Disposable Filters
400 or 20 x 25
487 or 20 x 30
576 or 14 x 25 (2Req.)
665 or 16 x 25 (2Req.)
753 or 20 x 25 (2 Rea.'_
960 or 20 x 30 (2 Req.'l
Cleanable Filters
246 or 15 x 20
30t or 14x25
356 or 16 x 25
411 or 20 x25
466 or 20 x 25
575 or 24 x 25
7. Start-up Procedures
Electrical shock hazard.
Use extreme care during all of the following checks and pro-
cedures.
Make sure electric power is turned OFF as instructed in ap-
propriate steps.
Failure to follow this warning can result in property damage,
personal injury, and/or death.
Final Electrical Check
Makeafinalwiringchecktobesuresystemiscorrectlywired.Inspectfieldinstalledwiring
andtheroutingtoensurethatrubbingorchafingduetovibrationwillnotoccur.
NOTE:WiringMUSTbe installedso it is protectedfrompossiblemechanicaldamage.
Circulating Air Blower
DeterminingBlowerSpeed
1.Turn electric power OFF.
2. From the system design, determine the total external static pressure
(ESP) for the supply ducts, return ducts and registers, diffusers,
grilles, dampers, heaters and filters.
3.To your system ESP determined in Step 2, add 0.05 In. W.C. for a
wet coil.
4. From the system design, determine the desired cooling airflow in
cubic feet per minute (CFM).
5. Locate the unit's Blower Performance Data table on the tech data
label for the unit's voltage. (The tech data sheet is attached to the
evaporator access panel on the unit.) From the table, determine the
speed tap required to achieve the desired airflow.
&See next section, Speed Taps, to set the blower motor speed termi-
nal block (speed taps) to the cooling speed determined in the pre-
vious steps.
I
FIGURE 18 I Blower Motor
Speed Taps
I
BIow'er Speed Tap Block
Auxiliary E_ectric Heat B
Wire (if used)
connects here
BE SURE TO CHECK BLOWER MOTOR SPEED DATA ON THE
UNITS TECHNICAL DATA LABEL LOCATED ON THE UNIT.
NOTE: Electric heater blower wire may be attached to any "Appropriate"
speed tap See FIGURE 11notes. The yellow lead MUST always be con-
nected to the speed tap block at the common quick connect terminal. The
terminal is identified as COM.
Refer to FIGURE 18 and the appropriate unit wiring diagram included in
this manual. Wire the black wire to the required speed tap terminal to
achieve required airflow determined in Step 5.
Cooling and Auxiliary Electric Strip Heat
On Air Conditioning units with electric heat, the heat strip may be operated
on a lower blower speed than cooling (Refer to Heater Chart FIGURE 11)
See FIGURE 15 for connection location.
Check Before Starting
SpeedTaps
AfterdeterminingtherequiredCFMandspeedtapdatafromthetechdatasheet,followthe
stepsbelowtochangespeedsifnecessary.
FIGURE 17 [ Blower Speed Tap Settings
10 SEER 2 TON MED
10 SEER 21/2 TON MED
10 SEER 3 TON LOW
10 SEER 31/2 TON MED HI
10 SEER 4 TON LOW
10 SEER 5 TON HI
12 SEER 2 TON MED
12 SEER 21/2 TON MED
12 SEER 3 TON LOW
12 SEER 31/2 TON MED HI
12 SEER 4 TON LOW
1. Check that the blower motor speed terminal block is set to the prop-
er cooling speed. Refer to the unit wiring diagram and the various
airflow tables in this manual.
2. Check to see that clean, properly sized field supplied air filters are
installed in the return air duct.
3. Inspect the inside of the unit to be sure that all wires are in place and
all tools, etc. are removed.
4. Replace all service access panels.
Checktheunit'soperationasoutlinedinthefollowinginstructions.Ifanyunusualsparking,
odorsornoisesareencountered,shutOFFelectricpowerimmediately.Recheckforwiring
errors,orobstructionsin ornearblower motors.
CirculatingAir Blower
1.Be sure electric power is OFF.
2.Set thermostat Heat-Cool selector to OFF.
10
3.SetthermostatfanswitchtoAUTO.
4.TurnelectricpowerON.Nothingshouldstartrunning.
5.SetthermostatfanswitchtoON.Thecirculatingairblowershould
comeONaftera30seconddelay.
Atemperaturerisegreaterthan60°F(33.3°C)isnotrecommended.(Thisappliestoelec-
tricheatonly).
1.To check the temperature rise through the unit, place thermometers
in the supply and return air ducts as close to the unit as possible.
2.Open ALL registers and duct dampers.
6. Reset thermostat fan switch to AUTO. The circulating air blower
should go OFF after a 30 second delay. Nothing should be running.
Cooling
1. Be sure that electric power is OFF.
2. Set thermostat Heat-Cool select to COOL.
3. Adjust thermostat setting to below room temperature.
4. Turn electric power ON. During power application check the follow-
ing:
a. Contactor- Contactsclosing
b. Compressor- ON
c. Condenserfanmotor- ON
d. Circulatingair blower- ON (afterdelay)
5.Switch the thermostat to OFF, check the following:
a. Contactorcontactsopening.
b. Compressor- OFF
c. Condenserfanmotor- OFF
d. Circulatingblower - OFF(afterdelay)
6.Turn electric power OFF
AuxiliaryHeating
NOTE: Repeatcirculatingairblowerprocedureaboveif AuxiliaryElectricHeatis being
installedafterunit hasbeen installedandcheckedout.
3.Set thermostat Heat-Cool selector to HEAT.
4.Set the thermostat temperature setting as high as it will go.
5.Turn electric power ON.
6.Operate unit AT LEAST 5 minutes, then check temperature rise.
NOTE: The maximum outlet air temperature for all models is 200°F
(93.35C). Maximum temperature rise for electric heat is 60°F (33.35C)
7.Set thermostat to normal temperature setting.
8.Turn electric power OFF.
9 Change blower speed tap if 60°F (33.3°C)TemperatureRisewasexceeded
andrepeat.
10.Be sure to seal all holes in ducts if any were created during this
process.
Sequence of Operation
CoolingMode:Energized(R,G,YI) De-energized(N/A)
(a) When high and low voltage is initially applied to unit:
(f)On a call for cooling ......... :
The compressor and condenser fan will energize. The evaporator
blower motor will have a delay on and will energize after 30 seconds.
Temperature Rise Check
Temperaturerise isthe differencebetweenthesupplyandreturnairtemperatures.The
temperatureriseshouldbe-+2°F (1.1°C)ofthetemperatureriseshownin FIGURE12.
NOTE:The temperaturerisecan beadjustedby changingtheheatingspeedtapat the
unit'sblowerterminalblock.Referto theunit'sInstallationInstructionsfor airflowinforma-
tion.
(2)When the cooling setpoint has been satisfied ......... :
The compressor and condenser fan will de-energize immediately.
The evaporator blower motor will have a delay off and will de-ener-
gize after 30 seconds.
if temperature rise is excessive, verify proper airflow through the unit. if
temperature rise is inadequate, check for proper electrical supply to the
heater and verify correct airflow.
8. Operation
Electrical shock hazard.
Turn OFF electric power supply at disconnect switch or ser-
vice panel before removing any access or service panel from
unit.
Failure to follow this warning can result in property damage,
personal injury, and/or death.
izespressurethroughoutthesystemandpreventspossiblereverserotationofthescroll
compressor.
CAUTION
Do NOT operate unit on cooling when the outdoor temperature is be-
low 60°F. This is necessary to prevent possible damage to the com-
pressor.
TurningThe Unit Off
Scroll Anti-Cycle Timer (Where Applicable)
Single phaseunitswithscrollcompressorscan be equippedwithan anti-cycle device
whichdelaysthestart ofthecompressorinthe eventofa powerinterruption.Thisequal-
1.Set the thermostat selector switch to OFF and set the fan switch to
AUTO. To restart, set thermostat selector switch to COOL or HEAT
and set thermostat to temperature desired.
2.To shut the unit down completely, turn electric high voltage power
OFF
tl
Thermostat Fan Switch Operation
WiththethermostatfanswitchintheONposition,thecirculatingairblowerwillruncontinu-
ouslyatthespeed usedfor cooling.
Withthethermostatfan switchintheAUTOposition,thecirculatingairblowerwillonlyrun
duringeach cooling or heatingcycle.
9. Maintenance
Adjusting RoomTemperatures
Ifthetemperaturein individualroomsisnotas desired,balancethesystembyadjusting
thedampetsinthebranchducts.Adjustalittleatatimeandwaitadayaftereachchangeto
judgetheeffect.Oncethedampersareadjustedfornormalweatherconditions,itisbestto
leavethemthatway.Compensatefortemporaryweatherchanges byadjustingthether-
mostatsetting.
Monthly Maintenance and Inspection Checks
CondenserFanMotor
Air Filters
CAUTION
Do NOT operate unit without air filters.
Inspectfiltersat leastmonthlyand replaceorcleanas required.Washablefiltersmaybe
cleanedby soakingin milddetergentand rinsingwithcoldwater.Replacefilterswiththe
arrowsonthe sidepointingin the directionof airflow.Dirtyfiltersarethe mostcommon
causeofinadequateheatingor coolingperformance,andof compressorfailures.
Cooling Season Checks (Monthly)
CondenserCoil
Keepthecondenserinletandoutletareacleanandfreeofleaves,grassclippingsorother
debris.Grassshouldbekeptshortinfrontofthecondenserairinlet.ShrubberyMUSTbe
trimmedbackso it is nocloserthan 30inches (762mm)to unit panelsand10 inches
(254mm)to coil inlet.
Thecondenserandevaporatorcoilsshouldbecleanedbyusing anon-acid typecleaner
toavoidremovingpaintorothertypeofcoatingonthecoi!.Alwaysturnoffelectricalpower
totheunit duringserviceandmaintenance.
CondensateDrain
Periodiccleaningofthecondensatedrain&trapmayberequired.Inspectdrainageofcon-
densateafteratleast15minutesof continuousoperationin coolingmode duringhumid
conditions.
CAUTION
Do NOT use 3in I oil, penetrating oil, WD40 or similar oilsto oil motor
bearings.
Motors used inthis product are considered permanently lubricated for up
to 5 years. Ifoil ports are provided on the motor, oilthecendenserfanmotorand
evaporatorblowermotorafterfiveyearsof operationandeveryfiveyearsthereafter.
UseSAE10W30motoroil.Tooil,removetheholeplugsfromthemotorendbellsandadd
severaldropsofoilwitha squeezetype,flexibletubeoiler.Replaceholeplugsafteroiling.
Do NOToveroil.
Cleanthesurroundingareaandthecondenserandevaporatorcoils.Usecautiontoavoid
damagetocoil fins.Usea non-acidtype ofcleanerONLY.
CirculatingAir Blower
Toaccessorremovetheblowermotorusethefollowingsteps.
1.Turn electric power OFF
2. Remove the blower access panel.
3. Unplug the wires connected to the speed tap block if necessary, not-
ing the location of each wire for re-installation.
4.Slide entire housing toward you.
Annual Maintenance and Inspection
Electrical shock hazard.
Turn OFF electric power supply at disconnect switch or service
panel before removing any access or service panel from unit.
Failure to follow this warning can result in property damage,
personal injury, and/or death.
The annualinspectionMUSTincludelubricationandcleaningas requiredtoensureeffi-
cientoperationofthe unit.To simplifyaccess,removeallaccesspanels.
&Visually inspect the blower wheel for accumulations of dirt or lint.
Clean the compartment and the blower wheel. If accumulation is
excessive on blower wheel, or does not easily remove, it may be
necessary to remove and disassemble the blower assembly for prop-
er cleaning.
&Oil blower motor if needed.
CAUTION
Do NOT use 3in I oil, penetrating oil, WD40 or similar oilsto oil motor
bearings.
OiltheblowermotorbyaddingseveraldropsofSAE10W30toeachmotorbearing.The
blowermotorshouldbeoiledafterfiveyearsof operationandeveryfiveyearsthereafter.
7.When finished, reassemble in reverse order.
12
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12