S6BQ SERIES - COMMERCIAL SPLIT SYSTEM TWO STAGE AIR CONDITIONER
NOTES
FIELD CONTROL WIRING
350 FEET #14 GA.
250 FEET #16 GA.
150 FEET #18 GA.
LENGTH WIRE SIZE
TOTAL WIRE MINIMUM RECOMMENDED
FIELD WIRING
FACTORY WIRING
10131340
T2
T3
T1
TEST
CYCLE TIMER
ANTI-SHORT
1. DISCONNECT ALL POWER BEFORE SERVICING.
2. FOR SUPPLY CONNECTIONS, USE COPPER
CONDUCTORS ONLY.
3. LINE AND BLOWER MOTOR BRANCH CIRCUIT
WIRE SHOULD BE OF A SIZE TO PREVENT
VOLTAGE DROP BEYOND FIVE PERCENT OF
SUPPLY LINE VOLTAGE.
4. CAUTION: IF ANY OF THE ORIGINAL WIRES
SUPPLIED WITH THE APPLIANCE MUST BE
REPLACED, IT MUST BE REPLACED WITH
WIRING MATERIAL HAVING A TEMPERATURE
RATING OF AT LEAST 105° C.
5. ALL MOTORS MARKED IOL HAVE INTERNAL
LINE BREAK.
6. FOR AMPACITIES AND OVERCURRENT
PROTECTION, SEE UNIT RATING PLATE.
7. FURNACE/AIR HANDLER W/FACTORY EQUIPPED
24V CONTROL CIRCUIT TRANSFORMERS
SHOULD BE MODIFIED/REWIRED TO ONLY USE
24V TRANSFORMER FROM OUTDOOR SECTION.
SEE INSTALLATION INSTRUCTIONS FOR
TYPICAL MODIFICATIONS.
8. TRANSFORMER PRIMARY CONNECTION WILL
MATCH UNIT RATED VOLTAGE.
9. FOR 208V OPERATION REMOVE WHITE WIRE
FROM 230V TAP AND PLACE ON 208V TAP.
10. USE #18 GA. WIRE FOR 24 VOLT CONTROL
WIRING ON UNIT.
11. ALL 24 VAC LOW VOLTAGE CONNECTIONS TO
UNIT MUST BE CLASS 2.
WIRING CODE
BLACK - BK
BROWN - BR
RED - RD
ORANGE - OR
YELLOW - YE
GREEN - GN
BLUE - BL
WHITE - WH
  • Page 1 1