FläktGroup Controller R515 Operating instructions

Type
Operating instructions
FlGro·
  
          
Operation manual
OPERATION MANUAL R515Air Curtain
General Description
Manual operation
System Control
Airflow power is adapted to site and climatic conditions
Airflow settings in 5 STEPS
0FF = No Airflow
STEP 1 = 10% Max Airflow
STEP 2 = 30 % Max Airflow
STEP 3 = 50 % Max Airflow
STEP 4 = 70 % Max Airflow
STEP 5 = 100 % Max Airflow
Manual selection of Heating system: Winter / Summer
Automatic operation
1 All right reserved
Door opens- High screening
performance is activated Door closes- After Run-Mode-
High performance stays active
After Run- time runs out
Fans switch back to step 1
(stand-by)
Inside temperature reaches
Ts level Fans switch OFF
Temperature drops below
Ts System is activated
in stand-by mode step 1
Door opens - High
screening performance
is activated again
FläktGroup
General Description
2 All right reserved
1 - PC BOARD
2 - 5 STEP Transformer
230 V /1 /50hz
Supply power cable prewired length = 2 m
3 - Remote Controller 515
Connection cable RJ 45 prewired length = 10 m
1
2
3
Location
OPERATION MANUAL R515Air Curtain
FläktGroup
PC Board
Description
OPERATION MANUAL R515Air Curtain
M
0 230 200 170 140 120
L N PE
230 V
ac
L1
N
PE
230 V
ac
AUX
up to
10 units
OUT J4 J6 J5 J16
OUT IN IN IN OUT
0-10 V
MASTER ON-OFF
CONTACT
0-10 V
ON-OFF
REPORT
Solenoid
Valve for
heating mode
Dip switch for BMS
CONTROLLER
Frost
detector
Thermostat
3 All right reserved
FläktGroup
OPERATION MANUAL R515Air Curtain
Controller
Description Control Panel R515
1 -Airflow rate indicator
STEP OFF 1-2-3-4-5
2 -Airflow settings
Upper arrow: increase airflow
Lower arrow: decrease airflow
3 - Heating LPHW settings
key on Control Panel: Selection for Winter or Summer mode
4 - Select AUTO - MODE
4 All right reserved
13
24
SW1-SW2-SW3-SW4-SW5 (see table)
FläktGroup
OPERATION MANUAL R515Air Curtain
Operation Manual
Switch codes inside R515
5 All right reserved
A. AUTOMATIC - FUNCTION DOOR CONTACT
B. AUTOMATIC - FUNCTION AMBIENT THERMOSTAT
C. AUTOMATIC - FUNCTION BMS-ON-OFF / FROST ALARM
D. SET AFTER RUN TIME DOOR
FläktGroup
OPERATION MANUAL R515Air Curtain
Configuration
6 All right reserved
Operation Manual
A. MANUAL 5- STEP AIRFLOW CONTROL SET LPHW MODE
Manual selection of airflow step 0 1-2-3-4-5
Manual selection of LPHW Heating ON-OFF
SELECT OPERATION MODE 0-10 V / DIGITAL / MEMORY
1. 0 10 V - EC / AC Fan operation
SET SWITCH SW 1 on PC-BOARD 1 to Position ON. Connect to
external signal 0-10 V (5 steps: 2 V signal / step) from BMS.
2. 230 V 5 step Fan operation
SET SWITCH SW 1 on PC BOARD 1 to Position OFF
B. AUTOMATIC OPERATION BASICS
Air Curtain automatic operation fluctuating between external signals from
door contact and ambient thermostat for optimal screening efficiency and
continuous tempering of entrance area.
DOOR CONTACT
Air Curtain switches to selected airflow step when door opens and returns
to stand-by mode (step 1) controlled by thermostat after programmed after
run time expires.
AMBIENT THERMOSTAT - STAND-BY
Air Curtain switches ON / OFF with airflow step 1 controlled by the set
ambient temperature on the thermostat.
BMS or TIMER ON / OFF INPUT
EMERGENCY CUT OFF WHEN FROST DETECTOR IS ACTIVATED
The master ON-OFF function (contact J4) can be used to switch on and off
the system as well as to operate a freezing alarm detected by the frost
detector mounted on the heating coil (will switch off the fans give an
optical alarm signal and open the solenoid valve).
FläktGroup
OPERATION MANUAL R515Air Curtain
Configuration
7 All right reserved
Automatic mode setting
1. SELECT AUTO - MODE ON SWITCH - R 515
SELECT SUMMER WINTER MODE
(if Solenoid Valve installed in Heating circuit )
2. SET AIRFLOW STEP FOR OPEN DOOR OPERATION
2.1. KEEP DOOR OPEN WHILE PROGRAMMING
2.2. SELECT WISHED AIRFLOW STEP
2.3. SELECTED STEP WILL BE SHOWN ON DISPLAY
3. SET AFTER RUN TIME WHEN DOOR CLOSES
SW1 / SW2
4. SET AMBIENT AIR TEMPERATURE
THERMOSTAT
5. DOOR OPENS - SYSTEM SWITCHES TO
PRESET AIRFLOW STEP
ACTIVATED STEP IS SHOWN ON DISPLAY
6. DOOR CLOSES - SYSTEM REMAINS IN HIGH VOLUME MODE
DURING PRESET AFTER RUN TIME - THEN SWITCHES TO STEP 1
HEATING MODE TILL IT IS ACTIVATED AGAIN
7. FROST ALARM: IF A FROST DETECTOR (CAPILLAR SENSOR
ON HEATING COIL) IS INSTALLED AND ACTIVATED DUE TO
FREEZING HAZARD SYSTEM WILL SWITCH OFF FANS,
OPEN THE SOLENOID VALVE AND WARNING LED FLASHES
FläktGroup
Linea - ZDE / ZDS
Comfort Flat
Comfort
MAINTENANCE FREE!
Clean / Vacuum
Absorbing Grill
periodically
OPERATION MANUAL R515Air Curtain
Service & Maintenance
Air outlet nozzle adjust direction
Air Inlet Maintenance
8 All right reserved
FläktGroup
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9