OPERATION MANUAL R510Air Curtain
General Description
Manual operation
System Control
Airflow power is adapted to site and climatic conditions
Aiflow settings in 5 STEPS
0FF = No Airflow
STEP 1 = 10% Max Airflow
STEP 2 = 30 % Max Airflow
STEP 3 = 50 % Max Airflow
STEP 4 = 70 % Max Airflow
STEP 5 = 100 % Max Airflow
Manual selection of Heating system : Winter / Summer
Automatic operation
PN R510_13_10 1 All right reserved
System Control
Air Curtain operation controlled by external signal from
door contact or ambient thermostat
If Set point temperature is not reached or the door is
opened, Air Curtain runs with programmed airflow.
When Set point temperature is reached or the door is
closed, Air Curtain returns to stand-by mode after “After
Running Time” expires.
Stand-by: Step 0 Stand-by: Step 1
General Description
2 All right reserved
1 - PC BOARD
2 - 5 STEP Transformer
230 V /1 /50hz
Supply power cable prewired length = 2 m
3 - Remote Controller 510
Connection cable RJ 45 prewired length = 10 m
1
2
3
Location
OPERATION MANUAL R510Air Curtain
PN R510_13_10
PC Board
Description
OPERATION MANUAL R510Air Curtain
M
0 230 200 170 140 120
L N PE
230 V
ac
L1
N
PE
230 V
ac
AUX
up to
10 units
OUT J4 J6 J5 J16
OUT IN IN IN OUT
0-10 V
MASTER ON-OFF
CONTACT
0-10 V
ON-OFF
REPORT
Solenoid
Valve for
heating mode
Dip switch for BMS
Wireless Remote
Control RC 50
CONTROLLER
3 All right reserved
PN R510_13_10
OPERATION MANUAL R510Air Curtain
Controllers
Description Control Panel R510 and Remote Controller RC50 (Wireless)
1 -Airflow rate indicator
STEP OFF 1-2-3-4-5
2 -Airflow settings
P1 key : increase airflow
P2 key : decrease airflow
3 - Heating LPHW settings
P3 key on Control Panel : Selection for Winter or Summer mode
P3 key on Remote Controller : ON for Winter mode, OFF for
Summer mode
4 All right reserved
12
3
2
Remote controller RC50
(Wireless)
Control Panel R510
3
PN R510_13_10
Airflow adjustment
Set up Airflow level by pressing P1 & P2 arrows keys
Heating mode
Press ON key to activate heating mode
OPERATION MANUAL R510Air Curtain
Manual Operation
Control Panel Controller R510
5 All right reserved
Remote Controller RC50
PN R510_13_10
Airflow adjustment
Set up Airflow level by pressing P1 & P2 arrows
keys
0FF = No Airflow
1 = 10% Max Airflow
2 = 30%
3 = 50%
4 = 70%
5 = 100%
Airflow rate level is indicating on LED control
Heating mode
Press arrow key and select Cloud to set heating mode
OPERATION MANUAL R510Air Curtain
Automatic Mode Setting
Configuration
6 All right reserved
Procedure
Connect Door Contact or Thermostat to J6 connector on Microprocessor PC Board
Open Controller R510 to set up Standby mode
Dip switch on OFF position : No airflow after “Running Time”
Dip switch on ON position : Minimum Airflow (STEP1) after “Running Time”
PN R510_13_10
OPERATION MANUAL R510Air Curtain
Automatic Mode Setting
Configuration
7 All right reserved
PN R510_13_10
Procedure
Open the door or select max Set point on thermostat.
On Control Panel R510, select the desired airflow (SETP 1 -2-3-4-5) by pressing arrows
keys P1 & P2
Airflow rate is indicated on the LED display
To confirm, press and hold arrows keys P1 & P2 simultaneously for 5 seconds minimum
When LEDS flashes, your selection is entered in the microprocessor
OPERATION MANUAL R510Air Curtain
Automatic Mode Setting
Configuration
8 All right reserved
Procedure
Set “Running Time” by pressing arrows keys P1 and P2
Step 5 75 sec
Step 4 60 sec
Step 3 45 sec
Step 2 30 sec
Step 1 15 sec
Press and hold Winter / Summer arrow key for 3 seconds to confirm your selection
Important
After 20 seconds, if “Running Time” has not been validated,
programming is cancelled
PN R510_13_10
OPERATION MANUAL R510Air Curtain
BMS Configuration
9 All right reserved
By default, microprocessor is set on OFF Position
Configuration
Procedure
Set DIP Switch on ON position
J5 connector is now activated for BMS
5 steps controls : 2 V signal / step
PN R510_13_10
Linea - ZDE / ZDS
Comfort Flat
Comfort
MAINTENANCE FREE !
Clean / Vacuum
Absorbing Grill
periodically
OPERATION MANUAL R510Air Curtain
Service & Maintenance
Air outlet nozzle adjust direction
Air Inlet Maintenance
10 All right reserved
PN R510_13_10
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11

FläktGroup Control Panel 510 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI