SETUP (see Chapter 4 for full instructions)
Setups can be performed directly on the front panel or via
PComTest/PAS295 communication software - see Chapter 4 for details.
Performing Basic and Communications Setup
Press CH
SELECT ENTER
Press to activate middle window; press ▲▼ to scroll to option.
SELECT
Press to activate lower window; press ▲▼ to scroll to value.
SELECT
Press to save selected value.
Basic and Communications Setup Options (∗ default setting)
Code Parameter Options Description
ConF Wiring mode 3OP2 3-wire open delta using 2 CTs
4Ln3
∗
4-wire Wye using 3 PTs
3dir2 3-wire direct connection using 2 CTs
4LL3 4-wire Wye using 3 PTs
3OP3 3-wire open delta using 3 CTs
3Ln3 4-wire Wye using 2 PTs
3LL3 4-wire Wye using 2 PTs
Pt PT ratio 1.0∗ - 6,500.0 Phase potential transformer ratio
Ct CT primary current 1-50,000A
(5∗) Primary rating of the phase current
transformer
d.P Power demand
period 1, 2, 5, 10, 15*,
20, 30, 60, E Length of demand period for power
demand calculations, in minutes.
E = external synch.
n.dp Number of power
demand periods 1-15
(1*) No. of demand periods to be averaged
for sliding window demands. 1 = block
interval
A.dP Ampere/Volt
demand period 0-1800 s
(900*) Length of demand period for
volt/ampere demand calculations.
0 = measuring peak current
buF Buffer size 8∗,16,32 No. of measurements for RMS sliding
averaging
Freq Nominal frequency 50, 60 Hz
(25 Hz option) Nominal power utility frequency
LoAd Maximum demand
load current 1-50,000A
(0∗) Maximum demand load current used in
TDD calculations 0 = CT primary
current
rSt Reset diS, En ∗ Protects all reset functions if disabled
Prot Communications
protocol ASCII∗, rtu,
dnP3, Prnt ASCII, Modbus RTU or DNP3.0
protocol, or printer mode
rS Interface standard 232*, 422, 485 RS-232 or RS-422 or RS-485 interface
Addr Address ASCII: 0∗-99, Modbus: 1∗-247, DNP3.0: 0∗-255
bAud Baud rate 110, 300, 600, 1200, 2400, 4800, 9600*, 19200 bps
ENTER
bASc
4L-n
ConF Port
ASCII
Prot
men
option
value