EMS FireCell Radio Network Communicator Quick start guide

Category
Fire protection
Type
Quick start guide
Radio Network Communicator
POWER
NETWORK FAULT
FAULT
POWER
FAU LT
SYSTEM
FAULT
FIRE
Fire Alarm Control
Radio Hub
Slave Control Panel
230V AC
Radio Network
Communicator
(RNC)
POWER
FAU LT
SYSTEM
FAULT
FIRE
Fire Alarm Control
Radio Hub
Master Control Panel
230V AC
Radio Network
Communicator
(RNC)
Radio Network Communicator
POWER
NETWORK FAULT
FAULT
RNC Quick Start Guide Iss 7 - TSD106 AJM
www.emsgroup.co.uk
QUICK START GUIDE
RADIO NETWORK COMMUNICATOR (RNC)
For Syncro/Syncro AS
Step 1 Identify RNC Locations:
If a radio survey has already been carried out, the survey will detail the recommended
location of the Radio Network Communicators (RNCs) and also any aerial positions if
required.
600mm away from metal*
*300mm is a worst case
minimum requirement
2m away
from other
electrical
equipment
2m away
from other
electrical
equipment
2m away
from other
electrical
equipment
Syncro AS Control PanelSyncro Control Panel
RNC
Remote High Gain Aerial
When connecting an RNC to a Syncro 2 or 4 loop Panel, the recommended distance
between metal objects from the aerial is 600mm. The recommended distance to any
other electrical equipment is 2m.
When connecting an RNC to a Syncro AS 1 or 2 Loop Panel, the same rules apply as
set out above. In addition, a high gain aerial must also be tted and sited a minimum
distance of 5m from the RNC.
Aerial and RNC seperated by 5m
Never site aerial
within 5m of the
RNC when
connected to a
Syncro AS Panel.
RNC
FIRE
Fire Alarm Control
POWER
FAULT
SYSTEM
FAULT
FIRE
Fire Alarm Control
2m
minimum
distance
Plastic conduit should
be used. Panel earth
faults will be shown if
metal conduit is used.
POWER
FAULT
SYSTEM
FAULT
Never site RNC
within 2m of the
panel or Radio
Hub.
Fire in zone
Fire
Power On
Pre-Alarm
Fire
Routing On
On Test
Buzzer
Silenced
Delay
Active
More
Events
General
Disablement
General
Fault
Power
Fault
System
Fault
Sounder
Fault/Disabled
Fire Routing
Fault/Disabled
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1
2
3
4
?
Re-Sound
Alarm
Silence Alarm
(Acknowledge)
Silence
Buzzer
Lamp
Test
Reset Evacuate Function
Exit
Enter
More
Fires
More
Events
Enable
Fire Alarm Control
FIRE
Fire Alarm Control
©2018 EMS Ltd. All rights reserved Page 2 of 4 TSD106 Iss 7 13/09/2018 AJM
Step 2 Identify Cable Entry Location:
Open the unit to show the inner PCB. The cable entries can now be made. See entry
points below:
NETWORK
FAU LT
FAU LT
POWER
RESET
UP
ENTER
DOWN
BACK
POWER IN
24V DC
- +
RS485
IN
+ -
RS485
OUT
+ -
NETWORK
FAU LT
FAU LT
POWER
RESET
UP
ENTER
DOWN
BACK
POWER IN
24Vdc
- +
RS485
IN
+ -
RS485
OUT
+ -
NO CABLE
ACCESS AT
TOP OF UNIT
ALL CABLES TO BE ROUTED NEATLY AT THE BOTTOM OF THE BOX, AND NOT OVER THE PCB BOARD
Step 3 Fix The RNC To The wall:
The unit can now be xed to the wall. The RNCs xing positions are as below:
Step 4 RNC To Control Panel Wiring:
The cable must be passed through the entry points provided. Connections are
detailed below:
Please Note: Care must be taken to ensure that the all connections are made
correctly before applying power to the unit. Damage may occur if cables are
incorrectly connected.
RS485 BUS & POWER CONNECTIONS
NET IN
NET IN
NET OUT
NET OUT
AUX 24V
AUX 24V
RS485 OUT
RS485 OUT
RS485 IN
RS485 IN
POWER IN
POWER IN
+
-
+
-
+
-
+
-
+
-
+
-
CONTROL
PANEL
REMOTE NETWORK
COMMUNICATOR
POWER IN
24Vdc
RS485
IN
RS485
OUT
AUX
24V
+ - + -
-
+
- +
NET
OUT
NET
IN
+
- + -
To
Control
Panel
To
Control
Panel
©2018 EMS Ltd. All rights reserved Page 3 of 4 TSD106 Iss 7 13/09/2018 AJM
NETWORK
FAU LT
FAU LT
POWER
RESET
UP
ENTER
DOWN
BACK
Fixing Position 1
Fixing Position 2
Fixing Position 3
Fixing Position 4
Syncro/Syncro AS Control Panel
Step 5 RNC Conguration:
Setting up of the RNC is carried out by completing the following:
MASTER PANELS RNC SLAVE PANELS RNC
STEP A: At the Control Panel, Set
Network Card Address to 1. See ‘Network
Card Setup.
STEP B: At the RNC, ‘Set Node Number to
1 via menu.
From front Screen> Node Setup> Set
Node Number
NOTE: The Network Card & the RNC
Addresses must match.
STEP C: Set Site ID via menu.
From front Screen> Node Setup> Set
Site ID
NOTE: Site id is taken from this RNC’s
ident label.
STEP A: At the Control Panel, Set
Network Card Address between 2 & 16.
See ‘Network Card Setup.
STEP B: At the RNC, ‘Set Node Number
between 2 & 16 via menu.
From front Screen> Node Setup> Set
Node Number
NOTE: The Network Card & the RNC
addresses must match.
STEP C: Set Site ID via menu.
From front Screen> Node Setup> Set
Site ID
NOTE: Site id must match Master Panel
RNCs ident.
Once steps A to C have been carried out at all RNCs go to step D.
Step D: From the Master Panels RNC menu a Congure System action must be
performed From front Screen> Node Setup> Congure System
ON
1
2
3
4
5 6 7 8
ON
OFF
Where the above switch is
set to address number 1
NETWORK CARD SETUP
Step 6 Signal Checks:
Once congured, all RNCs will require a signal level check to ensure they are at an
adequate level. The level received must be 30dB or greater.
From front Screen> Node Status> Signal Level
SWITCH NUMBERS
1
2
3
4
5
6
7
8
ADDRESS
1 =
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
2 =
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
3 =
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
4 =
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
5 =
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
6 =
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
7 =
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
8 =
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
9 =
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
10 =
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
11 =
ON
ON
OFF
ON
OFF
OFF
OFF
OFF
12 =
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
13 =
ON
OFF
ON
ON
OFF
OFF
OFF
OFF
14 =
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
15 =
ON
ON
ON
ON
OFF
OFF
OFF
OFF
16 =
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
The information contained within this literature is correct at time of publishing. EMS reserves the right to change any information regarding products as part of its continual development
enhancing new technology and reliability. EMS advises that any product literature issue numbers are checked with its head oce prior to any formal specication being written.
enquiries@emsgroup.co.uk
www.emsgroup.co.uk
+44 (0) 1227 369570
©2018 EMS Ltd. All rights reserved Page 4 of 4 TSD106 Iss 7 13/09/2018 AJM