CAMDEN CX-PS300UL is a power supply and charger designed for use with fire alarm systems. It provides a total of 3-amp nominal continuous supply current at 12/24V DC outputs and can accommodate one or two 12 Ah lead acid rechargeable batteries. The CX-PS300UL includes a built-in dedicated charger for sealed lead acid or gel cell type batteries, with a maximum charging current of 1.5 Amps. It also features automatic switch over to standby battery upon AC failure or below V, battery presence detection within 10 seconds, and a temperature compensated battery charger.

CAMDEN CX-PS300UL is a power supply and charger designed for use with fire alarm systems. It provides a total of 3-amp nominal continuous supply current at 12/24V DC outputs and can accommodate one or two 12 Ah lead acid rechargeable batteries. The CX-PS300UL includes a built-in dedicated charger for sealed lead acid or gel cell type batteries, with a maximum charging current of 1.5 Amps. It also features automatic switch over to standby battery upon AC failure or below V, battery presence detection within 10 seconds, and a temperature compensated battery charger.

Page 1 of 9
CX-PS300UL
POWER SUPPLY / CHARGER
INSTALLATION INSTRUCTIONS
Electrified Locks, Relays and Timers
1. DESCRIPTION
The CX-PS300UL series of power supply/charger supplies a total of 3-amp nominal continuous supply current @ 12/24V DC outputs.
It is installed in a large sheet steel enclosure capable of accommodating one or two 12 Ah lead acid rechargeable batteries. The
camden CX-PS300UL has been evaluated for ULC-S533, UL294 and ULC-60839-11-1. This power supply is not intended to power re
notication appliances (Horns, Strobes & Bells).
2. GENERAL SPECIFICATIONS
1. Input = 120 240V AC 50-60Hz, 1.4 Amp maximum.
2. Output 3 Amps continuous supply current PF 0.6 a t nominal 12/24 V DC.
3. Built-in dedicated charger for sealed lead acid or gel cell type batteries.
4. Maximum battery charging current 1.5Amps (not part of the max output current rating).
5. Automatic switch over to stand-by battery upon AC failure or below V .
6. Battery presence detection within 10 seconds.
7. Temperature Compensated Battery Charger. (EN54-4 only,not UL evaluated)
8. Battery Charger Monitor.
9. Battery load test every 48hr.
10. Battery test result indication.
11. Battery Reversal protection.
12. Low Battery indication at 11.40/22.80 Volts.
13. Low Battery disconnect at 10/20.2 Volts.
14. Low Battery, Battery disconnect, No Battery presence, battery charger trouble reporting. (See FAULT TABLE)
15. AC input indication by Green LED. (LED on when AC is present).
16. AC Fault CMOS Relay contact for AC failure
17. LEDs display on enclosure door (Green, Yellow, Blue).
18. DC output indication by Blue LED, on board and enclosure.
19. Overload and short circuit protection on DC output.
20. Battery charging leads included.
21. Board Dimension: 195mm x 110mm
22. Enclosure Dimension: 338 x 448 x 110mm (HP346 for 12Ah Battery)
Page 2 of 9
CX-PS300UL POWER SUPPLY / CHARGER
INSTALLATION INSTRUCTIONS
3. TECHNICAL SPECIFICATION:
Output Voltage
Output Amperage
Ripple
12/24 V DC Regulated. ClassE, unsupervised
3 Amp
50mVp-pmax
Charging Current
Battery Charging Voltage
1.5A Max, and not part of
max output rating
13.8V/27.6V Nominal
Operating Temperature 0 ˚C to 49 ˚C
4. PERFORMANCE RATINGS
UL294 Performance Levels:
Model
Product
Type
Line Security Destructive
Attack
Endurance
Standby Power
CX-PS300UL Power Supply I I IV III (when used with 12Ah
battery)
CAN/ULC-60839-11-1 Performance Grades:
Model Product Type
Grade
Grade Achievement
CX-PS300UL Power Supply
3 (when used with 12 Ah
battery)
Connect AC & battery
trouble relay outputs to
a grade 3 control unit, to
achieve Grade 3.
5 . LED INDICATIONS
1. Green LED- AC indicator
a. On when AC present.
b. The AC fail Relay activates (opens) within 60 seconds after AC failure.
2. BlueLED– DC Power indicator
a. Powered directly from the power supply DC output and indicates output is present.
3. YellowLED– Battery Charging and Fault indicator
a. The Yellow LED ashing indicates the battery is charging and is also used to indicate
various Fault conditions. See the Fault Condition and Indication table for details.
4. RedLED– Battery/ Charger test Indiicator for Pass or Failure.
a. The Red LED indicates a Battery test Failure or a Battery charger failure in conjunction with
the Yellow LED to indicate other Fault Conditions. See the Fault Conditions and Indication
table for details.
3 of 9
CX-PS300UL POWER SUPPLY / CHARGER
INSTALLATION INSTRUCTIONS
6. RELAY / OUTPUTS:
Output Output Type Description
AC FAIL NORMALLY CLOSED
OPEN = FAULT
TRIPS WITHIN 60 SEC. AFTER AC FAILS CMOS
RELAY RATING: 30V DC, 60 mA, 16 Ω
BATTERY FAIL NORMALLY CLOSED
OPEN = FAULT
BATTERY
PROBLEM
CMOS RELAY RATING: 30V DC, 60mA ,16 Ω
7. FAULT CONDITION & INDICATIONS:
FAULT LED-G LED-Y LED-R BATT
RELAY AC RELAY LED-B
BATTERY
REVERSED OR
NOT
CONNECTED
ON OPEN
BATTERY LOW ON OPEN
BATTERY
DISCONNECTED ON OPEN
BATTERY
TEST FAIL
ON
5 RAPID FLASHES
STOP 1 SECOND
REPEAT UNTIL
BATTERY IS
REPLACED
OPEN
BATTERY TEST OK OFF
3 FLASHES
1 SEC ON/OFF
CHARGER FAIL
10 RAPID
FLASHES
2 SECONDS
STOP AND
REPEAT
UNTIL OK
OPEN
AC FAIL OFF
OPEN
WITHIN
60 SEC
DC FAIL /
OVERLOAD
OFF
Page 4 of 9
CX-PS300UL POWER SUPPLY / CHARGER
INSTALLATION INSTRUCTIONS
8. BATTERY OPERATING VALUES
Parameter Output Description
Battery Disconnect voltage 10/20.2V
When AC is o, the battery is disconnected when the battery
voltage drops below this value.
The battery is only reconnected when the AC is restored.
Minimum battery voltage to
pass battery test
11.50V
23.0V
Red LED should ash for 1 sec ON/OFF during 2 minutes
testing. 5 rapid ashes and 1 second pause indicates
battery failure. In such case replace battery.
Low Battery Voltage
Warning
11.40V
22.80V
If the out put voltage drops below this value, a voltage low
warning is generated. See Fault Conditions and Indication table.
9. INSTALLATION INSTRUCTIONS
This power supply should be installed in compliance with National Electrical Code, NFPA70 as well NFPA72 National Fire
Alarm Code, CSA C22.1, Safety Standard for Electrical Installations, Canadian Electrical Code, Part I, CAN/ULC-S524, and
all applicable Local Codes. Installation to be performed by suitably qualied personnel. The power supply shall not be
installed in the fail secure mode unless permitted by the local authority having jurisdiction, and shall not interfere with
the operation of Listed panic hardware.
NOTE: Connect the Mains AC input 120/240V AC as shows in the installation diagram. Entry knocks out on the left of the
enclosure. Keep low voltage wiring away from the AC wiring.
1. Mount the power supply in the desired location using the 4 mounting holes. NOTE: For use in indoor protected area with
controlled environment only. Do not install power supply on exterior doors.
2. With the main power disconnected, connect the LEDs to the AC input terminal block, respecting the wiring phase and polarity
: Ground/Earth=Green/Yellow, Neutral = Blue (White), Live =Black (Brown). This equipment must be connected to the 120-240
Volt Mains via a readily dedicated accessible external disconnect device with maximum 15 Amp branch protection. Select the
operating output DC voltage 12/24 with the jumper SW1. SW1 ON = 12V DC, SW1 OFF = 24V DC.
3. Do not connect the battery at this time.
4. Switch ON the AC power supply and with that Green LED will turn ON indicating AC is present and the AC Fault Relay will be
energized “ON” (closed). When the AC is o, the AC Fault Relay will drop open within 60 seconds (Factory set) activating the
CMOS output “AC Fail”. Connect this output to relevant monitoring devices.
5. Verify the DC output voltage. It should be13.20V DC or 26.40V DC (max). Blue DC LED will turn ON indicating DC output is OK.
6. Yellow LED will only turn on along with open BAT FAULT CMOS relay to indicate the Battery is not attached or connected with
reversed polarity.
7. Connect the Battery or Batteries with respective polarity. Note: Battery should not be connected if the AC is not present rst.
8. If the battery is connected with the correct polarities, the Yellow LED will turn OFF (See Fault Conditions and Indications Table).
Within one minute the Battery Fault Relay will restore and the Yellow LED will ash once every 2 seconds.
9. If the battery is connected with reverse polarity, the Yellow LED will remain ON. (See the Table Fault). The CMOS relay will be
open indicating Battery Fault. Connect this output to relevant monitoring devices.
10. Connect the devices to be powered to the output terminals marked “Vo- Vo+”.
11. See below Fig 1 & Fig 2. for installation of PD4ECB, PD8ECB, MOM8ECB and ACM4ECB need 2 EOLR Resistors (2K2) provided.
12. If Tamper Switch is required, use part # TSW1-02 or TWS2-02 (Refer Fig 3).
13. Use 2K2 EOLR (End Of Line Resistor) Part #EORL-PWX2K2.
14. Connect the fault relays to FACP or ACP for trouble indication.
15. Secure the enclosure with the screw or with the Key Lock (if provided).
5 of 9
CX-PS300UL POWER SUPPLY / CHARGER
INSTALLATION INSTRUCTIONS
10. ACM4ECB
DESCRIPTION:
The ACM4ECB is a distribution controller to be used with card Access Control, Egress Doors. It provides 12/24V DC through 4 outputs
rated 2.0A (max. 3A total) each with electronic over-current protection set at 2.5A. The 4 outputs will switch ON or OFF security
devices such as Magnetic Locks, Door Strikes, etc. It is connected to FACP or ACP via NO or NC congurable contact input using 2K2
EOLR (Part #EORL-PWX2K2). It also has an input for Reversed Polarity triggering. The ACM4ECB has 2 Dry Contact “Form C” relay
outputs, one is to indicate output status, and another to indicate DC failure on any of the 4 outputs, due to overcurrent or short.
Installation:
1. Output Connections
There are 4 selectable outputs suitable for FAIL safe cong and FAIL secure cong.
a) For FAIL safe operation, connect the positive (+) lead of the device to normally closed (NC) and the negative lead to COM ”Neg”,
connector CN1 to CN4. DC power is present in normal condition and switched OFF when the re alarm from FACP or ACP or Reverse
Polarity input is triggered. FAIL Safe operation devices such as, Magnetic Lock should be connected to this output as show in Fig. 2.
b) For FAIL secure operation, connect the positive(+) lead to Normally Open (NO) instead of normally closed (NC). DC power is not
present in normal condition and will switch ON when the FACP or ACP or Reverse Polarity input is triggered. FAIL secure operation
devices such as Door Strikes should be connected to this output.
2. Fire Alarm and Access Control Interface
Normally Open (NO), Normally Closed (NC) input or Polarity Reverse (Rev. Volt.) input are available to trigger the ACM4ECB
operation. Connect the positive(+) and Negative(-) from the FACP or ACP to the REV. VOLT terminals observing the polarity, (polarity
is referenced in alarm condition) or connect the NO or NC from the FACP or ACP output to the “Fire Trigger“ terminals. Install
PWX2K2 2k2 (EOLR) resistor at the FACP or ACP as show in Fig. 1. Note: No ELOR on Rev. Pol.
3.Engineering RESET/REX Input
This option is avaliable when the Jumper JL is removed (JL OFF). This will cause the ACM4ECB to latch upon receiving Input from the
FACP or ACP with this option in place and when the FIRE/ACP TRIGGER resets.
JL ON will cause the unit to follow the FIRE/ACP TIGGER. Install PWX2K2 2.2K (EOLR) resistor at the Key Switch or Push Button to
perform this operation.
4. Relay Output
a) DC Fail: When one or more of the 8 outputs fail due to over current or short circuit condition, the DC fail Relay will open. Connect
this output to monitoring device. (28V DC, 300mA)
b) Status Output: When the FACP or ACP input activates this will cause the dry contact Relay Form “C” to change state (de-energize).
Connect this output to monitoring device. (28V DC, 300mA)
5. ACM4ECB LED INDICATION
L1 to L4 are the Output RED LEDs, when ON they indicate DC is present (enable), and the Output relays are energized.
When OFF, they represent Relay is de-energized and the output is OFF, NO DC present (disable). LD1 to LD4 are Yellow LEDs. They
indicates overload or short on the output. The output current limit is set @ 2.5Amp, rated at max 2.0Amp. L9 Green LED is normally
OFF. It will switch on upon receiving an alarm from the FACP/ACP. This LED will stay ON following the status of the FACP/ACP input. If
JL was removed, this LED will stay ON until the manual RESET circuit resets.
6. Access Control Panel (ACP)Trigger input.
There are 4 inputs split between CN10 and CN11, each with four terminals, two IN and two GND. Activation of the inputs is achieved
by shorting IN and GND terminals of the respective inputs.
7. FACP/ACP Input Programming
Selectable Output to be Irrelevant on Fire Activation to have the output relay activation follow the FACP or ACP input place the DIP
switch corresponding to desired relay to the “OFF” position. In the “ON position, the correspondent output relay will not be aected
by the FACP,ACP or Rev. Pol input.
Page 6 of 9
CX-PS300UL POWER SUPPLY / CHARGER
INSTALLATION INSTRUCTIONS
8. Isolated Output Conguration
If any of the outputs requires to be solated DRY CONTACT, remove the respective Jumper J1 through J4 to achieve this conguration,
Form “C”, (C NO NC) available to connectors CN1 through CN4. This connection is now isolated from the internal power source. Relay
Rating: 28V DC, 2A. PF 0.6
7 of 9
CX-PS300UL POWER SUPPLY / CHARGER
INSTALLATION INSTRUCTIONS
-
-
+
+
BATTERY 2
BATTERY CONNECTION NON POWER LIMITED
PWX2K2 EOL RESISTOR
QQ4
QQ3
QQ2
QQ1
SWITCH
DIP
JJ2
JJ1
&
REMOTE
RESET/REX
R/POL
-
+
FIRE TRIG.
OFF 3 2 1 4
ON
SWITCH RELEVANT
FOR FIRE CONTROL
NO
NC
C
C
NO NC
NO
CNC
+
+-
-
ACM4ECB
FIRE
INPUT
EARTH
GND
POWER CONTROL STATUS
C NO NC
DC TRBL
POSITION TO OFF
C
NO NC NC
NO
CC
NO NC
C
NO NC
POWERPLEX
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4
NC C NO COM (Neg) NC C NO COM (Neg) NC C NO COM (Neg) NC C NO COM (Neg)
IN GND IN GND IN GND IN GND
INPUTINPUT
INPUT
INPUT
1
2
3
4
L1 J1 L2 J2 L3 J3 L4 J4
D17
C10
C13
JR
CASCADE
L9
JL
LATCH
MODE
K6
K9
K1 K2 K3 K4
LY1 LY2 LY3 LY4
EARTH
GND
TO MONITOR POINT
RT2
L4
C5
C4
CN3
CN2
CN6 CN7
D6
D16
Q12
D17
C11
C47
IC9
T1
L8
Q12
Q11
C66
C37
LED-B
D25
C54 Q18
IC13
IC12
C6
L6
L5
C8
D5A
D5
Q3A
Q3
D3
L9
C7
L1
L2
CY2
CY3
K1
CY6
L3
Q1
R1
NTC
OUTPUT
D.C.
BATT.
TEMP
FAIL
BATTERY
+
+
GND NL
BATTERY
- +
- +
SW1
12/24
PANEL LED LED-Y LED-R
LB
LED9
T4A/250Vac
NTC
LED-G
CX2
DB1
Q30
CX1
L1A
MOV
F1
PROGRAM
VR1
Q1
D2
C3
AC
FAIL
C2
C1
CY5
DX300
ELECTRIC DOOR STRIKE
INSTALL 2K2 EOLR AT FACP
ACP/FACP
2K2
EOLR
KEY SWICTH
MAGNETIC
LOCK
PWX2K2
EOL RESISTOR
POWERPLEX ELECTRONICS INC.
DX-200W-PCB
TAMPER
SWITCH
N/C TAMPER OUT
CONNECTOR
HPVM3 ASSY
TOP LEVER
DATE OF MFG
CABINET GROUND
AWG 14
EARTH
GROUND
STUD
15
AC INPUT
120 - 240 VAC
50-60Hz 1.4A
G N L
NOTE: PLEASE REFER TO CX-PS300 INSTALLATION MANUAL, PART NO:40-82B302 REV:01
CX-PS300UL
REGULATED POWER SUPPLY CHARGER
UL/ ULC LISTED AS FOLLOWS:
UL294, C A N / ULC60839-11-1,C A N / ULC-S533
POWER SUPPLY FOR ACCESS CONTROL SYSTEM
For use in Indoor
Dry controlled
Environment
G N L
(NEC AND CEC CLASS 2 CIRCUIT, 60950 LPS CIRCUIT)
3 2 3
3
LOAD (A)
3
LOAD (A)
[V]
24V
12V
12AH BATTERY 17.2AH BATTERY
STANDBY OPERATION
[HOURS]
TIME
VOLTAGE
OUTPUT STANDBY OPERATION
[HOURS]
TIME
2
2
2
EOLR
2K2
FACP/ACP
C
NO
NC
N/O CONFIG.
EOLR
2K2
NC
NO
C
N/C CONFIG.
2K2
EOLR
KEY SWITCH
N/C CONFIG.
FACP/ACP
FAIL SAFE CONFIG FAIL SECURE CONFIGURATION
KEEP POWER LIMITED WIRING FROM NON POWER LIMITED WIRING AT LEAST 0.25" INCH APART
FOR WIRING SIZE USE 22 TO 14AWG
ACCESS CONTROL
POWER
SUPPLY CHARGER
12/24 VDC 3.0Amp
CN1 CN2 CN3 CN4
CN10 CN11
RESET
EACH OUTPUT RATED AT 2.0AMP, Maximum 3 Amp Total
AMP BATTERY12 / 17.2
AMP BATTERY12 / 17.2
ULC-S533, UL 294
21A6
TESTED FOR:
ULC-60839-11 -1
SECURITY
SIGNALING
I.T.E. POWER SUPPLY
E220695
Battery capacity for loss of primary power
at least (see table below) hours for:
SECURITY EQUIPMENT
12 VOLT 12 VOLT
battery jumper
BATTERY 1
AWG14
LED’S PANEL
B AT
A C
GRN
DC
DOOR
PANEL GROUND STUD
YEL
BLU
UL294, CAN/ULC-60839-11-1:
Grade 3"
SPECIAL LOCKING
ARRANGMENT
FIRE PROTECTIVE
This Product must be installed in compliance
with National Electrical CodeNFPA70,
and all applicable codes. CSA C22.1,
Safety Standard for Electrical Installations,
Canadian Electrical Code.
REG# T188047 1-02
REG# T188047 1-01
Canada
Industry
REG# T1880471-03
Fig. 1
TO FIRE INPUT
TERMINAL
TO REVERSED
POLARITY TERMINAL
STATUS
OUTPUT
2K2
EOLR
N/O CONFIGURATION
TO REMOTE RESET
FIRE ALARM MARSHAL OPTION
REMOVE JL
TO LACHT OUPUT
UNTIL REMOTE ACTIVATE
GND
EARTH
LY4
LY3
LY2
LY1
K4
K3
K2
K1
K9
K6
MODE
LATCH
JL
L9
CASCADE
JR
C13
C10
D17
J4L4
J3L3
J2
L2
J1
L1
4321
INPUT INPUT INPUT INPUT
IN GND
IN GND
IN GND
IN GND
NC C NO COM
NC C NO COMNC C NO COMNC C NO COM
OUTPUT 4 (Neg)
OUTPUT 3 (Neg)OUTPUT 2 (Neg)OUTPUT 1 (Neg)
POWERPLEX
NC
NO
C
NC
NO
C
C
NO NCNC
NO
C
POSITION TO OFF
TRBL
NCNOC
STATUS
CONTROL
POWER
GND
EARTH
INPUT
FIRE
ACM4ECB
--
++NC
CNO
NCNO
C
C
NC
NO
FOR FIRE CONTROL
SWITCH RELEVANT
ON
1 2 3 4
OFF
FIRE TRIG. +
-
R/POL
RESET/REX
REMOTE
&
JJ1
JJ2
DIP
SWITCH
KEY PAD
C
NO
NC
ACCESS CONTROL
PANEL
RELAY OUTPUT
UL N/0 PUSH BUTTON
OUTPUT 1 AND 4 ARE DESABLE TO THE ACP/FACP
OUPUT 2 AND 3 ARE ENABLE TO ACP/FACP
POWER FAIL
OUTPUT FAIL
CONNECT TO
MONITORING
TO AUXLIARY UL LISTED
POWER SUPPLY
NOTE:
IN THIS CONFIGUARTION
J4 MUST BE REMOVED
FOR ISOLATED CONTACT
CONNECTED TO DX300
KEY SWICTH
EOLR
2K2
MAGNETIC
LOCK
ELCTRIC DOOR
STRIKE
MAGNETIC
LOCK
USE UL LISTED EOL RESISTOR
USE ONLY UL LISTED EOL RESISTOR
PART NO: PX3007 REV:01
FIG 2
TYPICAL APPLICATION WIRING DIAGRAM
2 OR MORE CX-PS300 CONNECTED IN CASCADE
SECURE SAFE
CONFIGURATION
16
FAIL SAFE
CONFIGURATION
1 2 3
4 5 6
7 8 9
* # 0
2
LY4
LY3
K4
K3
K9
K6
MODE
LATCH
JL
L9
CASCADE
JR
C13
C10
D17
J4L4
J3L3
J2
NC C NO COM
NC C NO COM
OUTPUT 4 (Neg)
OUTPUT 3 (Neg)
POWERPLEX
NC
NO
C
C
NO NC
POSITION TO OFF
DC TRBL
C ON CN
STATUS
CONTROL
POWER
GND
EARTH
INPUT
FIRE
ACM4ECB
--
++NC
CNO
NCNO
C
C
NC
NO
FOR FIRE CONTROL
SWITCH RELEVANT
ON
1 2 3 4
OFF
FIRE TRIG. +
-
R/POL
RESET/REX
REMOTE
&
JJ1
JJ2
DIP
SWITCH
1
LY4
LY3
K4
K3
K9
K6
MODE
LATCH
JL
L9
CASCADE
JR
C13
C10
D17
J4L4
J3L3
J2
NC C NO COM
NC C NO COM
OUTPUT 4 (Neg)
OUTPUT 3 (Neg)
POWERPLEX
NC
NO
C
C
NO NC
POSITION TO OFF
TRBL
C ON CN
STATUS
CONTROL
POWER
GND
EARTH
INPUT
FIRE
ACM4ECB
--
++NC
CNO
NCNO
C
C
NC
NO
FOR FIRE CONTROL
SWITCH RELEVANT
ON
1 2 3 4
OFF
FIRE TRIG. +
-
R/POL
RESET/REX
REMOTE
&
JJ1
JJ2
DIP
SWITCH
EOLR
2K2
2K2
EOLR
REMOVE JR
TO CONNECT
IN CASCADE
NEXT ACM4ULECB
USE ONLY UL LISTED
EOL RESISTOR
KEY SWITCH
USE UL LISTED EOL RESISTOR
RESET CAN BE PERFORMED
ONLY FROM UNIT 1
TO FACP OR ACP
KEEP POWER LIMITED WIRING FROM NON POWER LIMITED WIRING AT LEAST 0.25" INCH APART
FOR WIRING SIZE USE 22 TO 14AWG
N/C CONFIGURATION
N/0 CONFIGURATION
2K2
_
+
REV POL.
CONTROL PANEL
ACP or FACP
2K2
1 INPUT ONLY
REV POL or FACP/ACP
INPUT CAN BE USED.
Page 8 of 9
CX-PS300 POWER SUPPLY / CHARGER
INSTALLATION INSTRUCTIONS
Fig. 2
Call: 1.877.226.3369 / 905.366.3377
Visit: www.camdencontrols.com
Opening New Doors to
Innovation, Quality and Support!
CX-PS300 POWER SUPPLY / CHARGER
INSTALLATION INSTRUCTIONS
File: CX-PS300UL_Manual.indd
Rev.: September 19, 2022
Part No.: 40-82B302
Page 9 of 9
Fig. 3
Tamper Switch Connection
DICGU
DICGU
DICGU
DICGU
DICGU
DICGU
VM3
VM3
VM3
VM3
VM3
VM3
CONNECT TO MONITORING POINTCONNECT TO MONITORING POINT
CONNECT TO MONITORING POINT
2
1
1
2 TAMPERS N/O
1 TAMPER N/O
CONNECT TO MONITORING POINT
C
N/C
N/O
C
N/C
N/O
N/C
N/O
C
EOLR
EOLR
EOLR
EOLR
C
N/O
N/C
N/O
N/C
C
N/O
N/C
C
1 TAMPER N/C
2 TAMPERS N/C
1
1
2
17
File: CX-PS300UL_Manual.indd
Revision: JAN 30th 2023
Part No: # 40-82B302
Fig. 3
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9

CAMDEN CX-PS300UL User manual

Type
User manual

CAMDEN CX-PS300UL is a power supply and charger designed for use with fire alarm systems. It provides a total of 3-amp nominal continuous supply current at 12/24V DC outputs and can accommodate one or two 12 Ah lead acid rechargeable batteries. The CX-PS300UL includes a built-in dedicated charger for sealed lead acid or gel cell type batteries, with a maximum charging current of 1.5 Amps. It also features automatic switch over to standby battery upon AC failure or below V, battery presence detection within 10 seconds, and a temperature compensated battery charger.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI