![](//vs1.manuzoid.com/store/data-gzf/8131e09bcb1166b30544658626dad7ab/2/001021428.htmlex.zip/bg10.jpg)
Q3-3 Closed Loop Settings
Q3-30 Single Zone Int. S. Q3-31 Single Zone Ext. S Q3-32 Multi Zone / Adv.
1-00 Configuration mode 1-00 Configuration mode 1-00 Configuration mode
20-12 Reference/feedb unit 20-12 Reference/feedback 20-12 Reference/feedb unit
3-02 Minimum reference 3-02 Minimum reference 3-02 Minimum reference
3-03 Maximum reference 3-03 Maximum reference 3-03 Maximum reference
6-24 Terminal 54 low ref/feedb value 6-10 Terminal 53 low voltage 3-15 Reference 1 source
6-25 Terminal 54 high ref/feedb value 6-11 Terminal 53 high voltage 3-16 Reference 2 source
6-26 Terminal 54 Filter time constant 6-14 Terminal 53 low ref/feedb. value 20-00 Feedback 1 source
6-27 Terminal 54 live zero 6-15 Terminal 53 high ref/feedb. value 20-01 Feedback 1 conversion
6-00 Live zero timeout time 6-24 Terminal 54 low ref/feedb value 20-03 Feedback 1 source
6-01 Live zero timeout function 6-25 Terminal 54 high ref/feedb value 20-04 Feedback 2 conversion
20-81 PID normal/inverse control 6-26 Terminal 54 Filter time constant 20-06 Feedback 3 source
20-82 PID start speed [RPM] 6-27 Terminal 54 live zero 20-07 Feed back 3 conversion
20-21 Setpoint 1 6-00 Live zero timeout time 6-10 Terminal 53 low voltage
20-93 PID proportional gain 6-01 Live zero timeout function 6-11 Terminal 53 high voltage
20-94 PID integral time 20-81 PID normal/inverse control 6-14 Terminal 53 low ref/feedb. value
20-82 PID start speed [RPM] 20-93 PID proportional gain
20-94 PID integral time
4-56 Warning feedback low
4-57 Warning feedback high
20-20 Feedback function
20-21 Setpoint 1
20-22 Setpoint 2
Q3-4 Application Settings
Q3-40 Fan Functions Q3-41 Pump Functions Q3-42 Compressor Functions
22-60 Broken belt function 22-20 Low power auto setup 1-03 Torque characteristics
22-61 broken belt torque 22-21 Low power detection 1-71 Start delay
22-62 Broken belt delay 22-22 Low speed detection 22-75 Short cycle protection
4-64 Semi auto bypass setup 22-23 No-flow function 22-76 Interval between starts
1-03 Torque characteristics 22-24 No-flow delay 22-77 Minimum run time
22-22 Low speed detection 22-40 Minimum run time 5-01 Terminal 27 mode
22-23 No-flow function 22-41 Minimum sleep time 5-02 Terminal 29 mode
22-24 No-flow delay 22-42 Wake-up speed 5-12 Terminal 27 digital input
22-40 Minimum run time 22-26 Dry pump function 5-13 Terminal 29 digital input
22-41 Minimum sleep time 22-27 Dry pump delay 5-40 Function relay
22-42 Wake-up speed 1-03 Torque characteristics 1-73 Flying start
2-10 Brake function 1-73 Flying start
2-17 Over-voltage control
1-73 Flying start
1-71 Start delay
1-80 Function at stop
2-00 DC hold/preheat
4-10 Current motor speed direction
See also
VLT
®
HVAC Drive Operating Instructions
for a detailed description of the Function Setups
parameter groups.
1.1.8. Main Menu Mode
Select the Main Menu mode by pressing the
[Main Menu] key. The below read-out appears
on the display.
The middle and bottom sections on the display
show a list of parameter groups which can be
chosen by toggling the up and down buttons.
130BP066.10
Each parameter has a name and number which remain the same regardless of the programming
mode. In the Main Menu mode, the parameters are divided into groups. The first digit of the
parameter number (from the left) indicates the parameter group number.
1. How to Programme VLT
®
HVAC Drive Programming Guide
16
MG.11.C2.02 - VLT
®
is a registered Danfoss trademark
1