Bernard Controls Fielbus Solution PRIOFIBUS DP FOR INTELLI+ Installation & Operation Manual

Type
Installation & Operation Manual
Profibus - Addressing guide
INTELLI+ AND LOGIC
SUG_18008s – Ind. -.01
Art: TBD
3
TABLE OF CONTENTS
1 CONTROLS AND INDICATIONS ................................. 4
1.1 CONTROLS
Control byte description
1.2 ACTUATOR FEEDBACK INDICATION
2 ACYCLIC COMMUNICATION ................................... 23
English
4
1 CONTROLS AND INDICATIONS
The Profibus DPV1 system has a cyclic communication (compatible
with Profibus DP) and acyclic communication.
The cyclic communication is mainly use for the Process. Data are read
and written in a well-defined timing. The useful data are selected in
the list below and transmitted in a cyclic way. The selection of only a
few data also increases the communication speed. The acyclic
communication is mainly use for maintenance. The data are collected
only on request that avoid to reduce the cyclic communication speed.
See below "§ 5 Acyclic communication"
1.1 CONTROLS
Valve control by the Profibus fieldbus is possible only if the actuator
rotating selector is in the "remote" position.
Conditions which can prevent a command to be executed:
Actuator rotating selector on "local" or "OFF"
Alarm tripped (motor thermal overload)
Emergency command received (ESD)
Command is set by hardwire
Control byte description
Actuators controls are located at the addresses 0 to 4 on the Profibus
interface module. These controls are:
Address 0: ON-OFF control
Bit N° Value Description
BIT 0
0 NO COMMAND
1 OPEN COMMAND
BIT 1
0 NO COMMAND
1 CLOSE COMMAND
BIT 2
0 STOP (OR MAINTAINED COMMAND MODE)
1 NO STOP (OR PULSE COMMAND MODE)
BIT 3 TO 6 NOT USED
BIT 7
0 NO LOCAL COMMAND INHIBITION
1 LOCAL COMMAND INHIBITION
English
5
OPEN/CLOSE: Open and close command. According to the actuator
configuration, it is possible to select a priority to the opening or to
the closing command (refer to the actuator’s manual). By default,
there is no priority given to either opening or closing.
Priority can be used to:
Allow to reverse the actuator rotation direction during a
manoeuvre without having to use the stop command. In this case
it is necessary to set a priority to the opening or to the closing
direction.
Give priority to one or the other rotation direction: if the actuator
receives the open and close commands simultaneously and the
priority has been given to the opening, the actuator will run the
open position.
STOP: if this command is maintained at 0 (most common case), the
open and close commands have to be maintained. If this command is
set to 1, a short duration open / close command pulse is sufficient to
drive the valve to the open or closed position. In this case, the stop
command (0) can be used to stop the actuator during the travel in its
current position.
LOCAL COMMAND INHIBIT: the local command inhibit is remotely
controlled. This command inhibits the local opening and closing
commands, and enables remote commands, even if the local/remote
selector of the actuator is set to local.
English
6
Address 1: Auxiliary commands
Bit N° Value Description
BIT 1 & 0
00 : ACTUATOR CONTROL THE
LOCAL/REMOTE ; 01= REMOTE ; 10
LOCAL ; 11=LOCAL+ REMOTE
BIT 3 & 2
00 (OR 11) = ACTUATOR CONTROL THE
PROPORTIONAL/DIGITAL; 10= CONTROL BY
THE ADDRESS 0; 01= CONTROL BY THE
ADDRESS 2 OR 3)
BIT 4
OPENING IHIBIT
BIT 5
CLOSING INHIBIT
BIT 6*
0
NO ESD COMMAND
1
ESD COMMAND
BIT 7*
0
NO PARTIAL STROKE COMMAND
1
PARTIAL STROKE COMMAND
* Only available with Intelli+ control
Bit 1 & 0: This is used to force the local remote of the actuator, if
these two bits are set to zero, the local remote is given by the actuator
selector, if set to 01, 10 or 11 the value overrides the selector (the
selector has no effect).
Bit 3 & 2: This can only be used if the actuator is a positioning or
modulating actuator. This is used to force the positioner activation or
not (see § 3.4 setup). If the value of the bits is set to 00, the menu
indicates the type of command (on-off or positioning), if you send 1 in
the bit 3 and 0 in the bit 2, the control is by command on-off.
LOCAL or REMOTE: substitutes for the local/remote selector of the
actuator and is used to remotely enable either remote control or local
control.
LOCAL+REMOTE: same definition as above, but local and remote
control can be enabled simultaneously.
English
7
OPEN, CLOSE INHIBIT: this command is used to inhibit opening or
closing of the actuator.
PROPORTIONAL/DIGITAL: for an actuator used in modulation with
positioner function, it is possible to issue remote commands via
proportional control (equivalent to 4-20mA) or via
opening/closing/stop commands. The PROPORTIONAL/DIGITAL
command is used to switch over from one type of command to another.
ESD: the ESD (Emergency Shut Down) is configured by the menu.
PARTIAL STROKE: This command performs automatically a test to
confirm that the actuator is still operational. The test consists to
operate the actuator on a partial stroke and return. The start position
and the stroke % can be configured. An alarm is emitted if the stroke
is not performed in a predetermined delay. This delay is worked out
from the rated operating time.
Address 2 and 3: Proportional control (set-point), only on modulation
actuator
Address N° Bit N° Value Description
2 BIT 0 TO 7 MSB
INCREMENT 0.01%.
RANGE 0 TO 10000.
0= CLOSED, 10000= OPEN
3 BIT 0 TO 7 LSB
To choose between proportional and ON-OFF control, set the menu
positioner activation on ‘Enable’ for proportional command (see §3.4
setup) or send address 1 bit 3&2 to 01.
English
8
Address 4: Relay output
Bit N° Value Description
BIT 0
0
RELAY 1 CONTACT OPEN
1
RELAY 1 CONTACT CLOSED
BIT 1
0
RELAY 2 CONTACT OPEN
1
RELAY 2 CONTACT CLOSED
BIT 2
0
RELAY 3 CONTACT OPEN
1
RELAY
3 CONTACT CLOSED
BIT 3*
0
RELAY 4 CONTACT OPEN
1
RELAY 4 CONTACT CLOSED
BIT 4*
0
1
RELAY 5 CONTACT CLOSED
BIT 5*
0
1
RELAY 6 CONTACT CLOSED
BIT 6*
0
RELAY 7 CONTACT OPEN
1
RELAY 7 CONTACT CLOSED
BIT 7
NOT USED
* Bit 3 to bit 6 is optional.
The relays could be used to have an output indication (wired as a non
fieldbus actuator) or to drive outside devices through Profibus. These
optional relays could be configured in Logic/Intelli+ menu for actuator
indication or output controls.
English
9
1.2 ACTUATOR FEEDBACK INDICATION
Indication byte description
The first five words of the Profibus interface give the actuator status.
Address 0: Indications
Bit N° Value Description
BIT 0
0
VALVE NOT OPEN
1 VALVE OPEN
BIT 1
0 VALVE NOT CLOSED
1
VALVE CLOSED
BIT 2
0 NO ACTION
1 TORQUE LIMITER ACTION IN OPEN DIRECTION
BIT 3
0 NO ACTION
1 TORQUE LIMITER ACTION IN CLOSE DIRECTION
BIT 4
0 ACTUATOR NOT TO LOCAL MODE
1 ACTUATOR TO LOCAL MODE
BIT 5
0 ACTUATOR NOT TO REMOTE MODE
1 ACTUATOR TO REMOTE MODE
BIT 6
0 ACTUATOR NOT TO OFF MODE
1 ACTUATOR TO OFF MODE
BIT 7
0
POWER OFF (ABSENCE OF MAIN POWER SUPPLY
OR TOO LOW)
1 POWER ON (PRESENCE OF MAIN POWER SUPPLY)
English
10
VALVE OPEN/CLOSE: confirms the valve is open or closed
TORQUE LIMITER ACTION OPEN/CLOSE: torque limiter action in
opening/closing direction. This information is transmitted even if the
valve stops normally on torque.
ACTUATOR TO LOCAL MODE: No command allowed from Profibus.
Indications are always available.
ACTUATOR TO REMOTE MODE: command allowed from Profibus
Indications are always available.
ACTUATOR TO OFF MODE: no command allowed in local or from
Profibus. Indications are always available.
POWER ON: The actuator is normally powered.
English
11
Address 1: Indications
Bit N° Value Description
BIT 0
0
ACTUATOR NOT OPENING
1
ACTUATOR OPENING
BIT 1
0 ACTUATOR NOT CLOSING
1
ACTUATOR CLOSING
BIT 2
0 NO HANDWHEEL ACTION
1
HANDWHEEL ACTION
BIT 3*
0 NO ESD COMMAND
1
ACTUATOR RECEIVES AN EMERGENCY
COMMAND ESD
BIT 4
0 THE ACTUATOR IS NOT RUNNING
1
ACTUATOR RUNNING
BIT 5
0 ACTUATOR AVAILABLE
1
ACTUATOR FAULT INDICATION
BIT 6
0 NO POSITION SENSOR FAULT
1
POSITION SENSOR FAULT
BIT 7
0 NO TORQUE SENSOR FAULT
1
TORQUE SENSOR FAULT
* Only available with Intelli+ control
English
12
ACTUATOR OPENING/CLOSING: the actuator is operated in
opening/closing direction.
HANDWHEEL ACTION: the handwheel has been actuated since the last
electrical operation.
ACTUATOR RECEIVES AN EMERGENCY COMMAND ESD: The actuator
is not available because it receives an emergency command which
overrides all other commands.
ACTUATOR RUNNING: the actuator is operated in opening or closing
direction.
ACTUATOR FAULT INDICATION: The actuator is not available due to
a following event, motor thermal overload, lost phase (in case of 3ph
supply) or locked rotor. Including additional faults (refer to the control
manual to configure).
POSITION OR TORQUE POWER FAULT: Intelli+ receives no information
from the position or torque sensor.
English
13
Address 2: Alarms
Bit N° Value Description
BIT 0
0 NO LOCKED MOTOR OPEN ALARM
1 LOCKED MOTOR OPEN
BIT 1
0 NO LOCKED MOTOR CLOSE ALARM
1 LOCKED MOTOR CLOSE
BIT 2
0 NO MOTOR THERMAL OVERLOAD
1 MOTOR THERMAL OVERLOAD
BIT 3
0 NO LOST PHASE ALARM
1 LOST PHASE
BIT 4
0 NO OVERTRAVEL ALARM
1 OVERTRAVEL ALARM
BIT 5
0 NO DIRECTION OF ROTATION OPEN ALARM
1 DIRECTION OF ROTATION OPEN ALARM
BIT 6
0 NO DIRECTION OF ROTATION CLOSE ALARM
1 DIRECTION OF ROTATION CLOSE ALARM
BIT 7*
0 NO RTC BATTERY FAULT
1 RTC BATTERY LOW
* Only available with Intelli+ control
LOCKED MOTOR OPEN/CLOSE: The actuator locked in the
opening/closing direction.
MOTOR THERMAL OVERLOAD: The motor thermal contact tripped.
The actuator will be again available as soon as the motor will cool.
LOST PHASE: In 3-phase, a phase is missing. No start allowed.
OVERTRAVEL ALARM: Position overshoot > 5% after motor shut down.
English
14
DIRECTION OF ROTATION OPEN/CLOSE: Opening/closing direction of
rotation discrepant
BATTERY LOW OR IS NOT PRESENT: The battery should be replaced
because of low voltage or the battery is missing (refer to the Intelli+
manual).
Address 3: Running torque in%
Bit N° Value Description
BIT 0 TO 7 0-150 RUNNING TORQUE IN %
RUNNING TORQUE: Indication of the instantaneous torque. 100% is the
maximum actuator rated torque
Address 4-5: Actuator position feedback
Address Bit N° Value Description
2 BIT 0
TO 7
MSB
INCREMENT 0.01%. RANGE 0 TO
10000.
0= CLOSED, 10000= OPEN.
3 BIT 0
TO 7
LSB
ACTUATOR POSITION FEEDBACK: 0,00%= closed, 100,00%= open
English
15
Address 6: Indication
Bit N° Value Description
BIT 0
0 NO HUNTING
1 ACTUATOR HUNTING
BIT 1
0 HMI COMMUNICATION IS RUNNING
1 HMI COMMUNICATION IS IN FAULT
BIT 2
0 POSITION IS CORRECT
1 POSITION IS IN FAULT (<-10% OR >110%)
BIT 3
0 NO ACTIVITY MEMORY FAULT
1 ACTIVITY MEMORY FAULT
BIT 4
0 NO STOP MID TRAVEL
1 STOP MID TRAVEL
BIT 5
0 NO LOST SIGNAL
1 LOST SIGNAL 4-20MA
BIT 6*
0 NO PARTIAL STROKE IN PROGRESS
1 PARTIAL STROKE IN PROGRESS
BIT 7*
0 NO PARTIAL STROKE FAULT
1 PARTIAL STROKE FAULT
* Only available with Intelli+ control
ACTUATOR HUNTING: positioning is unstable.
HMI: Communication between the HMI and the base board.
POSITION: Error due to a positioning measurement out of the normal
range (-10% 110%).
STOP MID TRAVEL: The actuator is at a stop, neither open nor closed.
English
16
LOST SIGNAL: 4 to 20mA lost signal (In case of analogue and hardwired
input signal)
PARTIAL STROKE IN PROGRESS: A partial stroke command has been
issued and this test is not ended.
PARTIAL STROKE FAULT: The partial stroke test has detected a fault.
The actuator is not fully available.
Address 7: Alarms
Bit N° Value Description
BIT 0* 0-1 NAMUR NE107 MAINTENANCE REQUIRED
BIT 1* 0-1 NAMUR NE107 OUT OF SPECIFICATION
BIT 2* 0 NAMUR NE107 FUNCTION CHECK
BIT 3* 0 NAMUR NE107 FAILURE
BIT 4*
0
TORQUE NOT APPROCHING THE LIMIT (BIT
3 ADDRESS 4)
1 TORQUE APPROCHING THE LIMIT
BIT 5
0 NO ERROR ENTRY AUX2 (BIT 10 ADDRESS 3)
1 ERROR HW ENTRY AUX2
BIT 6
0 NOT TOO MANY START LAST HOUR
1 TOO MANY STARTS IN THE LAST HOUR
BIT 7
0 24V AUX PRESENT
1 LOST OF 24V AUXILLIARY
* Only available with Intelli+ control
English
17
Namur NE107: The NE107 recommendation defines that detailed
device-specific diagnostics are summarised as four simple status
signals. These signals ensure that the plant operator is not inundated
with device troubleshooting details and cryptic error codes. The
NAMUR NE107 recommendation harmonises the display of status for
devices. Each fault or warning can be assigned to one signalling, please
refer to the Intelli+ manual for configuration of this signalling.
TORQUE APPROCHING THE LIMIT: This indicates that, during the
travel, the torque is approaching the limit. This is only a warning and
does not stop the actuator.
ERROR HW ENTRY AUX2: A hardware error is detected on the main
board on the Aux 2 entry. The main board should be replaced.
TOO MANY STARTS IN THE LAST HOUR: Starting rate exceeding the
actuator class average.
LOST OF 24V AUXILLIARY: Auxiliary power supply fault for external
circuits.
English
18
Address 8: Information
Bit N° Value Description
BIT 0*
0
CHANNEL IS BACKUP (REDUNDANCY
OPTION)
1
CHANNEL IS PRIMARY (REDUNDANCY
OPTION)
BIT 1*
0
1 CHANNEL AVAILABLE (REDUNDANCY
OPTION)
1
2 CHANNELS AVAILABLE (REDUNDANCY
OPTION)
BIT 2*
0
SR MODE (SYSTEM REDUNDANCY)
(REDUNDANCY OPTION)
1
FR MODE (FLYING REDUNDANCY)
(REDUNDANCY OPTION)
BIT 3
0
NO BASE BOARD SERIAL COMMUNICATION
FAULT
1
BASE BOARD SERIAL COMMUNICATION
FAULT
BIT 4
1 FIELDBUS HAVE COMMAND
0 HARDWIRED COMMAND
BIT 5*
0 REDONDANT COMMUNICATION
1
IN CASE OF REDUNDANT BOARD THE
COMMUNICATION IS NOT REDONDANT
BIT 6 0-1 VALVE JAMMED
BIT 7 0-1 LOCAL COMMAND INHIBIT
* Only available with Intelli+ control and with redundant board
English
19
CHANNEL IS PRIMARY/BACKUP: For a redundant communication the
Profibus interface has 2 channels connected to the Profibus line. The
one that got a data exchange state is named primary channel and the
other one backup channel.
1 or 2 CHANNELS AVAILABLE: Indication of how many channels are
available.
SR/FR MODE: SR mode uses a redundant fieldbus with 2 lines, FR mode
uses a redundant fieldbus with only one line.
SR mode is the default configuration.
BASE BOARD SERIAL COMMUNICATION FAULT: An error occurs on the
communication between the base board and the fieldbus Board. The
signalling is not refreshed.
FIELDBUS HAVE COMMAND / HARDWIRED COMMAND: Depending on
the configuration of the type of control (see § 3.4 setup).
VALVE JAMMED: Actuation could not be completed due to excess
torque.
LOCAL COMMAND INHIBIT: A local command inhibit is currently
present, as a consequence of sending the following command: LOCAL
COMMAND INHIBITION (Address 0 bit 7 of the control byte). A key is on
the LCD screen for signalling this command in local.
Address 9-10: External device analogue input signal
Address Bit N° Value Description
9 BIT 0 TO 7 MSB
INCREMENT 0.1%. RANGE 0 TO
1000.
0= 0MA, 1000= 20MA
10
BIT 0 TO 7 LSB
EXTERNAL DEVICE INPUT SIGNAL: A hardwired signal (for example 4
to 20mA) is coming from another device and uses the actuator Profibus
interface to communicate the value.
English
20
Address 11: External device input signal/alarms
Bit N° Value Description
BIT 0 0-1
SIGNAL A COMMAND ON STOP HARDWIRED
ENTRY
BIT 1 0-1
SIGNAL A COMMAND ON OPEN HARDWIRED
ENTRY
BIT 2 0-1
SIGNAL A COMMAND ON CLOSE HARDWIRED
ENTRY
BIT 3 0-1
SIGNAL A COMMAND ON AUX1 HARDWIRED
ENTRY
BIT 4 0-1
SIGNAL A COMMAND ON AUX2 HARDWIRED
ENTRY
BIT 5
0 INTERNAL TEMPERATURE OK
1 INTERNAL TEMPERATURE OUT OF RANGE
BIT 6*
0 VIBRATION OK
1 VIBRATION OUT OF RANGE
BIT 7
0 BUTTON OK
1 BUTTON FAULT
* Only available with Intelli+ control
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40

Bernard Controls Fielbus Solution PRIOFIBUS DP FOR INTELLI+ Installation & Operation Manual

Type
Installation & Operation Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI