English
19
CHANNEL IS PRIMARY/BACKUP: For a redundant communication the
Profibus interface has 2 channels connected to the Profibus line. The
one that got a data exchange state is named primary channel and the
other one backup channel.
1 or 2 CHANNELS AVAILABLE: Indication of how many channels are
available.
SR/FR MODE: SR mode uses a redundant fieldbus with 2 lines, FR mode
uses a redundant fieldbus with only one line.
SR mode is the default configuration.
BASE BOARD SERIAL COMMUNICATION FAULT: An error occurs on the
communication between the base board and the fieldbus Board. The
signalling is not refreshed.
FIELDBUS HAVE COMMAND / HARDWIRED COMMAND: Depending on
the configuration of the type of control (see § 3.4 setup).
VALVE JAMMED: Actuation could not be completed due to excess
torque.
LOCAL COMMAND INHIBIT: A local command inhibit is currently
present, as a consequence of sending the following command: LOCAL
COMMAND INHIBITION (Address 0 bit 7 of the control byte). A key is on
the LCD screen for signalling this command in local.
Address 9-10: External device analogue input signal
Address Bit N° Value Description
9 BIT 0 TO 7 MSB
INCREMENT 0.1%. RANGE 0 TO
1000.
0= 0MA, 1000= 20MA
10
BIT 0 TO 7 LSB
EXTERNAL DEVICE INPUT SIGNAL: A hardwired signal (for example 4
to 20mA) is coming from another device and uses the actuator Profibus
interface to communicate the value.