Ampac FireFinder LED Mimic Installation guide

Type
Installation guide
ADVANCED WARNING
SYSTEMS
FireFinder LED Mimic 302-7150
Installation Guide
Item Numbers: 201-0544
MAN2499-2
N1236
Page 1
WORLD LEADER OF INNOVATIVE SOLUTIONS IN FIRE DETECTION AND ALARM SYSTEMS
Ampac Technologies Australia Tel: +61 8 9201 6100 Europe Tel: +44 (0) 1302 833 522 New Zealand Tel: +64 9 443 8072 www.ampac.net
Description:
The LED Mimic (302-715), LED Mimic Display Board
(302-733), and the FireFinder Controller Interface Card
[CIC] (302-725) is designed to provide remote indication
of the current status of an NZ FireFinder FACP. The
mimic will indicate any zones, or sensors in alarm as
well as providing common Fire, Defect, DBA, system
Normal indication, and a General Purpose Relay
Output.
LED Mimic 302-715 Specifications
Function Keys Lamp Test
Lamp Reset
Buzzer Mute
CPU Reset
Address Switches
System Switches
Indicator
(LED’s)
Power On
Normal
Fault
Power Supply
TB1: 20 to 28VDC @ 100 mA
CN6: 5 volt output (aux power)
Outputs
CN1, 2, 3 & 4: 32 outputs for Zone
indication
CN5: 5 outputs for Fire, Pre-Alarm,
DBA, Defect and Normal indication
CN5: 1 buzzer output
TB4: General Purpose Output, 1A
Voltage-free changeover contacts
Inputs
CN5: 5 inputs for Mimic Reset, Lamp
Test, Buzzer Mute, Bell Isolate and
Evacuate
The LED Mimic derives power (Max 2 Amps) and
RS485 comms from the FireFinder CIC (302-725). In
small systems with 1, or 2 LED Mimics on cable runs of
less than 400 meters suggested cabling is 2 Pair
Twisted 100 Shielded Data Cable (0.2mm² cores
minimum) e.g. OLEX JECP87F5002, BELDEN 9804. In
larger systems with more than two LED Mimics or long
cable distances use 1 Pair Twisted 100 Shielded Data
Cable e.g. OLEX JECP87F5001, BELDEN 9841 for
communications. It will be necessary to supply power to
LED Mimics via separate cables. The size of the power
cables will depend on the number of mimics used and
the total distance Table 2.
Operation of the LED Mimics is not monitored by the
FACP. If communications to the LED Mimics fail, the
LED Mimic will flash the 'Defect' LED rapidly to indicate
a communication defect. Correct operation of the LED
Mimic and FACP is confirmed by the 'Normal' LED
flashing on the LED Mimic.
Recommended Maximum Cabling Distances using 2
Pair Data Cable.
Number of LED Repeater Boards Max Distance
1 400m
2 200m
Table 1
Recommended Power Cable Sizes for Larger
Systems
Number
of LED
Mimics
Distance
= <500m
Distance
= 500m<
>1Km
Distance
= 1Km<
>1.5Km
Distance
=1.5Km<
>2Km
1 0.3mm² 0.5mm² 1mm² 1.5mm²
2 0.5mm² 1mm² 1.5mm² 2.5mm²
3 0.75mm² 1.5mm² 2.5mm² 4mm²
Table 2
Installation:
Controller Interface Card 302-7250 & LED Repeater
Board 302-7150.
Observe anti-static precautions at all times
1. Power system down, and remove batteries.
2. Mount the Controller Interface Card on standoffs in
the left side of the panel.
3. To connect the CIC to the FireFinder Main Board
302-674, plug one end of the sixteen-way cable
provided into CN1 of the CIC and the other end into
CN18 of the Main Board 302-674. Connect TB1
and TB3 of the CIC to the external cabling.
4. Mount the LED Mimic Board 302-715 and the
Expansion LED Board 302-733 on stand-offs within
an enclosure. Connect TB1 of the 302-715 LED
Mimic to the external cabling then connect as
shown in Table 3.
LED Mimic Board Expansion Board
CN5 CN1
CN1 CN2
CN3 CN3
Table 3
5. Set Switches as follows SW2-1 ON, SW2-2 OFF,
SW2-3 OFF, SW2-4 OFF, SW2-5 OFF, SW2-6
OFF , SW2-7 OFF, and SW2-8 OFF (All LED
Mimic Boards are set to address No. 4).
6. Power up and test LED Mimic functions.
ADVANCED WARNING
SYSTEMS
FireFinder LED Mimic 302-7150
Installation Guide
Item Numbers: 201-0544
MAN2499-2
N1236
Page 2
WORLD LEADER OF INNOVATIVE SOLUTIONS IN FIRE DETECTION AND ALARM SYSTEMS
Ampac Technologies Australia Tel: +61 8 9201 6100 Europe Tel: +44 (0) 1302 833 522 New Zealand Tel: +64 9 443 8072 www.ampac.net
Communications
& 27VDC From:
FACP CIC
EXT Cabling
Communications
& Power To Next:
LED Mimic
Board 302-715
To LED D is p l ay
302-733 CN1
Fire, Pre-alarm,
DBA,Defect, Normal
To LED Display
302-733 CN2
Zones 1-8
To LED Display
302-733 CN3
Zones 9-16
To LED Display
302-733/1 CN2
Zones 17-24
To LED Display
302-733/1 CN3
Zones 25-32
N/F
SCR TX- TX+
+27
OV
+27
K2
CN5
CN1
CN2
CN3
CN6
CN4
TB3
TB1
TB5
TB4
SW6
SW4
SW5
SW2
SW7
SW3
POWER OUT
Buzzer Mute
Lamp Reset
Lamp Test
FAULT
NORMALPOWER ON
LED DISPLAY
N/ON/CC0VGPI
OUT
OV GND
IN
CPU
RESET
OFF
ON
ADDRESS
SYSTEM
LEDS FLASH
SCR TX- TX+
FIT K2
FOR BUZZER
ALM
PRE
DBA
FLT
NOM
RST
LT
BM
BI
EVC
BZ
1
2
3
4
5
LED
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
LED AUX 5V
SW2 Settings
1-5, Address ( Max 31 )
6, Configuration
set to OFF for FireFinder
set to ON for NZ3200
7, Not used
8, LED Setting
ON = Flash OFF = Steady
1A Voltage
Free Contact
Programmable
I/P
ON
1 2 3 4 5 6 7 8
+
-
SCR TX- TX+
+27
OV
+27
TB3
TB1
OUT
OV GND
IN
SCR TX- TX+
To TB1 on
next LED
Mimic Board
LED MIMIC DRIVER BOARD 302-715
TB1
TO
MIMICS
0V
+
Tx +
Tx -
SH
302-725CIC
NOTE:INSERT 'LK1'
ON LAST LED MIMIC
DRIVER BOARD
CN1
CN18
FIREFINDER MAIN BOARD
302-674
CN4
CN3
CN3
CN2
CN2
CN3
CN1
CN2
CN5
CN1
LED MIMIC DISPLAY BOARDS 302-733
ZONES 1 - 16ZONES 17 - 32
FIRE
PRE-ALARM
DBA
DEFECT
NORMAL
RESET
BUZZER
FACP
SCR
OV
+27
Tx +
Tx -
GND
SCR
+27
OV
A
B
TB3
COMMS & PWR
Figure 1: General Power Wiring and Board Layout
3
2 1
OUT
IN
302-725
2A
TB3
K2
K1
CN1
U8
U7
U9
U10
U13
U11
U6
U4
U5
U1
U12
U2
U3
TB2
TB1
CN5
CN6
CN3
CN2
TO PREVIOUS CIC CN3 (OUT)
TO CN2 ( IN ) OF NEXT CIC OR CN1 OF THE NIC
27VDC IN
AUX FUSED
( F1 2A )
27VDC OUT
+ -
+ -
- - -
- - -
K1, K2:
LINK PINS 1 & 2
ON FIRST CIC ONLY
COM
TXD
RXD
RTS
CTS
SCRN
TRX-
TRX+
0V
+27V
F1
ON
1 2 3 4 5 6 7 8
302-715 REMOTE LED INDICATOR BOARD
REMOTE BUZZER
EVACUATION SW
BELL ISOLATE SW
BUZZER MUTE SW
LAMP TEST SW
RESET SW
302-733 REMOTE
EXPANSION
LED BOARD
26 WAY RIBBON
16 WAY RIBBON
16 WAY RIBBON
RS485
In
1.2K Max
27VDC
-
+
MUTE
TEST
N/F
SCR TX- TX+
+27
OV
+27
K1
K2
Q2
CN5
X1
U3
CN1
CN2
CN3
HY1
Q1
U5
CN6
CN4
U8
U9
U7
TB3
TB1
TB5
TB4
RL1
U10
SW6
SW4
SW5
SW2
SW7
CN7
SW3
D2
D3
D4
POWER OUT
BUZZER
RESET
LAMP
FAULTNORMALPOWER ON
LED DISPLAY
N/ON/CC0VGPI
302-715
OUT
OV GND
IN
CPU RESET
OFF
ON
ADDRESS
SYSTEM
LEDS FLASH
FACT ORY
USE ONLY
SCR TX- TX+
FIT K1 ON
LAST MIMIC
ONLY
FIT K2
FOR BUZZER
ALM
PRE
DBA
FLT
NOM
RST
LT
BM
BI
EVC
BZ
1
2
3
4
5
LED
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
LAMP
LED AUX 5V
U2
BZ1
+
U4
U6
TB2
TB1
D2
CN1
D10
D4
D3
D20
D19
D18
D17
D15
D14
D13
D12
D11
D9
D8
D7
D6
D5
D1
CN3
CN2
D21
RESET
LAMP TSTBZ MUTEBELL ISOLEVAC
BZ+BZ-
ALARM
PRE-ALM
DBA
DFCT
NORM
D16
IF APPLICABLE ONLY
LOWER SECTION OF
BOARD IS USED FOR
ZONES 17 - 32
IF APPLICABLE CN3, CN4 CONNECT TO CN2, CN3
RESPECTIVELY OF 2nd REMOTE EXPANSION LED
BOARD FOR ZONES 17- 32
0V
+27V
TB1
SCRN
TRX-
TRX+
TB3
+ -
+-
a b c
ON
1 2 3 4 5 6 7 8
FIREFINDER
MAIN BOARD (302-674)
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
O O O
CN18
TO LOOP
COMMS
(CN18)
+27
TB1
OV
GND
IN
SCR TX- TX+
SLAVE CPU3SLAVE CPU4 SLAVE CPU2
NOTE; SLAVE CPU1 IS SITUATED ON THE MAIN BOARD
Figure 2: General Cabling
Main System Board
302 708
Controller Interface Card
302 725
Mimic
Driver
Board
302 715
Remote LED
Board 302 733
CN5
CN1
CN2
CN3
CN4
CN1
CN2
CN3
CN4
CN5
TB1
TB1
CN18
Comms
RS485
+/- 27VDC
CN1
CN6
27VDC IN
Figure 3: Block Diagram