M-system TR3EX User manual

Category
Networking
Type
User manual
TR3EX
P. 1 / 7EM-8632
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
ETHERNET INTERFACE MODULE
(Modbus/TCP, use with TR30)
MODEL
TR3EX
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
PACKAGE INCLUDES:
Network interface module ............................................ (1)
MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrat-
ed in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
POWER INPUT RATINGS
• Operational range & power consumption: Check the pow-
er rating for the unit on the specification label.
Rating 24V DC: 24V ±10%, approx. 12W
UNPLUGGING THE MODULE
• Before you remove the module from its base or mount it,
turn off the power supply for safety.
ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
INSTALLATION
Use the Installation Base Model R3-BSx, or Model R3-
BSWx for free I/O address capability.
Before mounting the Network Interface Module onto the
Base, be sure to configure the module as explained below.
DATA ALLOCATION
The setting determines the data area size assigned to each
I/O module mounted on the base.
The data sent/received via Modbus is mapped according to
this setting.
See “COMPONENT IDENTIFICATION.”
NODE ADDRESS
See “COMPONENT IDENTIFICATION.”
NETWORK SLOTS ON THE BASE
I/O 1 I/O 2 I/O n
With Model R3-BSx base, mount the I/O Modules from the
left end (I/O 1) to the right in order that the Network Mod-
ule assigns data areas from I/O 1.
Network Module is mounted basically at the right end
though technically they could be mounted in any position.
With Model R3-BSWx base, there is no limitation in mount-
ing positions as I/O address can be assigned freely to each
module using rotary switches equipped on the base.
TR3EX
P. 2 / 7EM-8632
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
COMPONENT IDENTIFICATION
SW2
ON
8
7
6
5
4
3
2
1
SW3
ON
4
3
2
1
ON
8
7
6
5
4
3
2
1
SW1
1
2
3
4
5
6
RUN LED
ERR LED
RJ-45 Modular
Jack
Not used
Not used
Configuration
Jack
Functions
LINK
DPLX (Duplex)
LINK10 (10Mbps)
LINK100
(100Mbps)
COL (Collision)
FRONT VIEW SIDE VIEW
8
6
7
3
4
5
2
1
0
F
E
D
C
B
A
9
8
6
7
3
4
5
2
1
0
F
E
D
C
B
A
9
ETHERNET INDICATORS
ID COLOR FUNCTION
LINK Red ON at LINK
DPLX Red ON with full-duplex communication
LINK10 Red ON with 10 Mbps connection
LINK100 Red ON with 100 Mbps connection
COL Red Blinking when collision occurs
SIDE DIP SW
(*) Factory setting
• Data Allocation: SW1, SW2
Data Allocation Type* must be assigned to each I/O module
position to specify how many data areas (four types) are to
be occupied by each.
Two bits from SW1 and SW2 are assigned to each posi-
tion, and data areas can be specified from the module No. 1
through 8. Setting for No. 9 and later modules is identical
to No. 8.
SW ASSIGNMENT MODULE NO.
SW1-1 SW1-2 1
SW1-3 SW1-4 2
SW1-5 SW1-6 3
SW1-7 SW1-8 4
SW2-1 SW2-2 5
SW2-3 SW2-4 6
SW2-5 SW2-6 7
SW2-7 SW2-8 8
SW SETTTING DATA ALLOCATION
OFF OFF 1
ON OFF 4
OFF ON 8
ON ON 16
* Refer to the specifications of the related series for the Data
Allocation Type of I/O modules.
• Dual Communication: SW3-1
When two network modules are mounted, one must be
‘Main’ (OFF) network and the other must be ‘Sub’ (ON) net-
work. For single communication, the network module must
always be set to ‘Main’ (OFF).
SW
DUAL COMMUNICATION
MAIN (*)
SUB
SW3-1 OFF ON
• Input Error Data: SW3-2
Hold: When the communication from an input module is lost
due to the input module error, the network module holds the
signal and stands by until the communication recovers.
Set to ‘0’: When the communication from an input module
is lost due to the input module error, the network module
outputs ‘0.
SW
INPUT ERROR DATA
HOLD
(*) SET ‘0’
SW3-2 OFF ON
• LED Function: SW3-4
Functions assigned to the front RUN and ERR LEDs can
be selected.
SW3-4
LED
RUN ERR
OFF (*) Green when normal Green when abnormal
ON Red when receiving Red when transmitting
Note: Be sure to set unused SW3-3 to OFF
TR3EX
P. 3 / 7EM-8632
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
DIMENSIONS mm (inch)
1
2
3
4
5
6
130 (5.12)
27.5 (1.08)
109 (4.29)
POSITIONING
GUIDE
TERMINAL
COVER
6–M3
SCREW
6.2
(.24)
CONNECTION DIAGRAM
In order to improve EMC performance, bond the FG terminal to ground.
Caution: This terminal is NOT a protective conductor terminal.
INTERNAL
POWER
INTERNAL
COMM. BUS
Modbus/TCP
CONFIGURATION JACK
JACK
RJ-45 MODULAR JACK
BUS CONNECTOR
* Not provided with ‘No Power Supply’ type module.
1
4
RUN +
RUN
RUN CONTACT OUTPUT
2
3
6
U (+)
V (–)
FG
POWER INPUT
*
WIRING INSTRUCTIONS
SCREW TERMINAL
Torque: 0.5 N·m
SOLDERLESS TERMINAL mm (inch)
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solder-
less terminals with insulation sleeve do not fit.
Applicable wire size: 0.75 – 1.25 mm
2
3.2 (.13) dia.
4 min.
(.16)
12 (.47) max.
6 max.
(.24)
3 (.12) max.
TR3EX
P. 4 / 7EM-8632
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
SETTING & CHECKING
1) IP ADDRESS
The R3-NE1 does not support BootP Table Software. The IP Address can be configured by using the R3CON Configurator
Software.
The Modbus/TCP Port No. is fixed to 502.
2) DATA ALLOCATION
Data Allocation Type must be assigned to each I/O module position to specify how many data areas (four types) are to be
occupied by each.
Two bits from SW1 and SW2 are assigned to each position on the base.
3) CHECK WIRING
Connect an Ethernet cable to the front RJ-45 jack.
4) CHECK LED
When wiring is correct, LINK and LINK10, or LINK and LINK100 are turned on.
When the module is receiving or sending data, LINK10 or LINK100 blinks.*
* For firmware version V3.00 or later, LED turns ON.
5) CHECK R3-GE1 CONNECTION
Enter “ping command” on the Windows MS-DOS as follows:
C:¥WINDOWS>ping ***.***.***.***
(***.***.***.***: Enter IP address in decimal.)
ping ***.***.***.*** with 32 bytes of data:
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Ping statistics for ***.***.***.***
Packets:Sent=4,Received=4,Lost=0(0% loss)
Replies in case of normal connection are as shown above. If the connection cannot be established normally due to e.g. wrong
IP address, other replies such as “time over” will be received.
6) CHECK CONNECTION TO THE APPLICATION SOFTWARE
Check Point 1: LINK LEDs
When a normal connection is established, the front LINK and LINK10 or LINK100 are turned on regardless of data send-
ing/receiving status. Check power supply to the hub in case that these LEDs are not on.
Check Point 2: RUN Indicator LED
With the side DIP SW3-4 is set to OFF, the RUN Indicator LED turns to Green in normal data sending/receiving.
Check Point 3: Sending/Receiving Indicators
With the side DIP SW3-4 is set to ON, the RUN Indicator LED turns to Red in data receiving, and the ERR Indicator LED
turns to Green in data sending. In normal operating conditions, these LEDs may seem to flash at once due to the high speed
transmission.
TR3EX
P. 5 / 7EM-8632
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
MODBUS I/O ASSIGNMENTS
ADDRESS DATA TYPE DATA
Coil (0X) 1 – 1024 Digital Output (discrete output)
Inputs (1X)
1 – 1024 Digital Input (discrete input)
1025 – 1040 Module Status
1041 – 1056 Error Status
1057 – 1072 Data Error Status
Input Registers (3X)
1 – 256 I Analog Input
257 – 768 F Analog Input
Holding Registers (4X)
1 – 256 I Analog Output
257 – 768 F Analog Output
I: Integer, 0 – 10000 (0 – 100%)
F: Floating (32-bit data cannot be accessed using floating addresses.)
Note: DO NOT access addresses other than mentioned above. Such access may cause problems such as inadequate operation.
• Module Status indicates whether individual I/O module are mounted or not. The bit corresponding to the mounted slots
turns to “1”, and the unmounted slots to “0”.
• Error Status indicates error status for each module as described below. The bit corresponding to such modules turns to “1”.
R3-TSx, R3-RSx, R3-US4: Input burnout
R3-DA16A: Power input in error or disconnected
R3-YSx: Output current error (e.g. load unconnected)
• Data Error Status indicates overrange (R3-US4: out of -10% to +110%; the other types: out of -15% to +115%) status for each
module. The bit corresponding to such modules turns to “1”.
TRANSMISSION DATA ASSIGNMENTS
The DIP SW located at the side of the module specifies each I/O module’s data allocation (occupied data area).
For example, when the data areas are assigned as shown below:
Module 1 4
Module 2 4
Module 3 4
Module 4 1
Module 5 1
Module 6 1
Module 7 1
Then the I/O data are assigned as in the table below:
ADDRESS POSITION
Input Registers (3X)
Holding Registers (4X)
1 – 4, 257 – 264 Slot 1
5 – 8, 265 – 272 Slot 2
9 – 12, 273 – 280 Slot 3
13, 281 – 282 Slot 4
14, 283 – 284 Slot 5
15, 285 – 286 Slot 6
16, 287 – 288 Slot 7
ADDRESS POSITION
Coil (0X)
Inputs (1X)
1 – 64 Slot 1
65 – 128 Slot 2
129 – 192 Slot 3
193 – 208 Slot 4
209 – 224 Slot 5
225 – 240 Slot 6
241 – 256 Slot 7
For Coil (0X) and Inputs (1X), addresses 16 times assigned
data areas (Data Allocation Type) are allotted with the Data
Allocation Type ‘1’ and ‘4’. With ‘8’ and ‘16’, 64 (4 × 16) are
automatically assigned.
TR3EX
P. 6 / 7EM-8632
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
MODULE STATUS, ERROR STATUS, DATA ERROR STATUS
Shows each module’s availability and error status.
0
15
Module 1
Module 2
Module 3
:
Module 16
I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
ANALOG DATA (models: R3-SV4, YV4, DS4, YS4 and US4, etc.)
16-bit binary data.
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary). Negative percentage is represented in 2’s
complements.
0
15
TEMPERATURE DATA (models: R3-RS4, TS4 and US4, etc.)
16-bit binary data.
With °C temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data. For example, 135.4°F is con-
verted into 135.
Minus temperature is converted into negative values, represented in 2’s complements.
0
15
ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)
32-bit binary data is used for accumulated counts and encoder positions.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.
32-bit data cannot be accessed using floating addresses.
0
15
+0
Lower 16 bits
0
15
+1
Higher 16 bits
BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)
32-bit binary data is used for BCD.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.
32-bit data cannot be accessed using floating addresses.
0
15
+0
Lower 16 bits
0
15
+1
Higher 16 bits
TR3EX
P. 7 / 7EM-8632
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
DISCRETE DATA (models: R3-DA16, DC16 and RR8, etc.)
0
15
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
: :
Input 16 (Output 16)
0 : OFF
1 : ON
Regarding detailed data assignment of R3-RR8, refer to the instruction manual for R3-RR8 (EM-8432).
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7

M-system TR3EX User manual

Category
Networking
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI