POWER SUPPLY MODULE
MODEL
R5-PS1
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
n PACKAGE INCLUDES:
Power supply module .................................................. (1)
n MODEL NO.
Confirm that the Model No. marking on the product is exactly
what you ordered.
n INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, including installation, connection and basic
maintenance procedures.
POINTS OF CAUTION
n CONFORMITY WITH EU DIRECTIVES
•ThisequipmentissuitableforuseinInstallationCategory
II (power input), Measurement Category II (RUN contact
output) and Polution Degree 2. Reinforced insulation (in-
ternal power or RUN contact output to power input to FG:
300V) and basic insulation (internal power to RUN contact
output: 300V) are maintained. Prior to installation, check
that the insulation class of this unit satisfies the system
requirements.
•Theequipmentmustbemountedinsideapanel.
•Insertanoiselterforthepowersourceconnectedtothe
unit. Densei-Lambda Noise Filter Model MZS-1206-33 or
equivalent is recommended.
•Theactualinstallationenvironments suchaspanelcon-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
n POWER INPUT RATING & OPERATIONAL RANGE
•Checkthepowerratingfortheunitonthespecicationlabel.
AC power: 85 – 132V or 170 – 264V, 47 – 66 Hz,
approx. 90VA
DC power: 24V ±10%, approx. 45W, approx. 1.8A
n UNPLUGGING THE UNIT
•Beforeyouremovetheunitfromitsbaseormountit,turn
off the power supply for safety.
n ENVIRONMENT
•Indooruse
•When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
•Donotinstalltheunitwhereitissubjectedtocontinuous
vibration.Donotsubjecttheunittophysicalimpact.
•Environmentaltemperaturemustbewithin-10to+55°C
(14to131°F)withrelativehumiditywithin30to90%RH
in order to ensure adequate life span and operation.
n WIRING
•Donotinstallcablesclosetonoisesources(relaydrivecable,
high frequency line, etc.).
•Donotbindthesecablestogetherwiththoseinwhichnoises
are present. Do not install them in the same duct.
n RUN CONTACT OUTPUT
•FunctionofRUNcontactoutput
During a Network Module communicates normally with
a master device (PLD or PC etc.), RUN contact output of
Power Supply Module turns ON.
•Whenusingwithdualredundantcommunicationor two
system.
During both Network Module or one of them communicates
normally with a master device (PLD or PC etc.), RUN contact
output of Power Supply Module turns ON.
•WhenusingR5-PSwithredundantortwosystem.
RUN contact output works in same function for both cases.
However, when I/O capacity code of installation base is
"05:5 slots (single network module)" or "09: 9 slots (single
network module)", the RUN contact output of Power Supply
Module installed in a Extender Power Module Base (model:
R5-EX1) is not available.
n AND ....
•Theunitisdesignedtofunctionassoonaspowerissupplied,
however, a warm up for 10 minutes is required for satisfying
complete performance described in the data sheet.
INSTALLATION
Use the Installation Base (model: R5-BSx) or the Extender
Power Module Base (model: R5-EX1).
In order to separate the Power Supply Module from a base,
push the recess at the center of the locking clamp (See below)
with a minus screwdriver.
Recess
R5-PS
P. 2 / 2
EM-6110 Rev.4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
TERMINAL CONNECTIONS unit: mm (inch)
Connect the unit as in the diagram below.
n DIMENSIONS mm (inch)
23415
90 (3.54)
TERMINAL COVER
7 (.28)
5–M3.5 TERMINAL SCREW
90 (3.54) 5.6
(.22)
45 (1.77)
LOCKING CLAMP
POSITIONING GUIDE
n CONNECTION DIAGRAM
INTERNAL POWER
1
2
3
4
5
U (+)
V (–)
FG
RUN
+
RUN
POWER INPUT
RUN CONTACT
OUTPUT
BUS CONNECTOR
/