Model : MCC020C/MLC020B
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
5.264 5.010 4.783 4.556 4.330 4.058
SC
4.788 4.634 4.497 4.360 4.223 4.058
15 TC
5.607 5.313 5.051 4.788 4.526 4.211
SC
4.749 4.585 4.439 4.292 4.146 3.970
18 TC
6.542 6.139 5.780 5.420 5.061 4.629
SC
4.643 4.451 4.279 4.108 3.936 3.730
19.4 TC
6.979 6.525 6.120 5.715 5.310 4.824
SC
4.594 4.388 4.205 4.022 3.838 3.618
20 TC
7.166 6.694 6.272 5.851 5.429 4.923
SC
4.572 4.347 4.145 3.944 3.742 3.501
22 TC
7.789 7.255 6.779 6.302 5.825 5.253
SC
4.502 4.209 3.947 3.685 3.424 3.110
24 TC
8.413 7.817 7.286 6.754 6.222 5.584
SC
4.431 4.070 3.749 3.427 3.105 2.719
Model : MCC025C/MLC025B
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
6.800 6.463 6.163 5.863 5.563 5.202
SC
5.808 5.680 5.567 5.453 5.339 5.202
15 TC
7.260 6.864 6.510 6.156 5.802 5.377
SC
5.689 5.557 5.439 5.321 5.203 5.061
18 TC
8.516 7.955 7.455 6.954 6.454 5.853
SC
5.366 5.221 5.091 4.961 4.831 4.676
19.4 TC
9.102 8.465 7.896 7.327 6.758 6.076
SC
5.215 5.064 4.929 4.793 4.658 4.496
20 TC
9.353 8.693 8.103 7.514 6.924 6.217
SC
5.151 4.978 4.825 4.671 4.517 4.332
22 TC
10.190 9.453 8.795 8.136 7.478 6.688
SC
4.935 4.693 4.477 4.261 4.045 3.786
24 TC
11.027 10.213 9.486 8.758 8.031 7.159
SC
4.720 4.408 4.130 3.852 3.574 3.240
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the
formula below :
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, BPF = Bypass factor
EDB = Entering dry bulb temperature, ° C
Model MCC010C MCC015C MCC020C MCC025C
Bypass factor 0.61 0.56 0.60 0.61