McQuay M5WM015JR User manual

Category
Split-system air conditioners
Type
User manual

This manual is also suitable for

Wall Mounted Split Systems
Models:
MWM009J/JR
MWM015J/JR
M5WM010J/JR
M5WM015J/JR
Catalog
MWM - J - 2009
Cover.indd 1Cover.indd 1 3/6/2009 6:06:22 PM3/6/2009 6:06:22 PM
Catalog.indb 2Catalog.indb 2 3/2/2009 4:40:55 PM3/2/2009 4:40:55 PM
MWM-J-2009 Table of Contents
“McQuay” is a registered trademark of McQuay International. All rights reserved.
© 2009 McQuay International. All rights reserved throughout the world.
Bulletin illustrations cover the general appearance of McQuay International products at the time of publication.
We reserve the right to change design and construction speci cations at any time without notice.
Table of Contents
Nomenclature......................................................................................................................1
Indoor Unit .....................................................................................................................1
Outdoor Unit ..................................................................................................................2
Product Line-Up .............................................................................................................3
Features...............................................................................................................................7
Application Information .....................................................................................................8
Operating Range ...........................................................................................................8
Refrigerant Circuit Diagram ...........................................................................................9
Controller ....................................................................................................................11
Installation Guideline ...................................................................................................12
Sound Data ........................................................................................................................24
Sound Pressure Level .................................................................................................24
NC Curve .....................................................................................................................25
Engineering & Physical Data ........................................................................................... 27
General Data ...............................................................................................................27
Component Data .........................................................................................................31
Performance Data ............................................................................................................. 35
Calculation Steps .........................................................................................................36
Performance Table ......................................................................................................39
Outline and Dimension ....................................................................................................45
Electrical Data ................................................................................................................... 46
Wiring Diagram .................................................................................................................48
Service and Maintenance.................................................................................................50
Troubleshooting ...............................................................................................................52
Exploded View and Part List ...........................................................................................60
Catalog.indb 3Catalog.indb 3 3/2/2009 4:40:55 PM3/2/2009 4:40:55 PM
Nomenclature MWM-J-2009
1
Nomenclature
Indoor Unit
M 5 WM 010 J R
Brand
M : Mcquay
Refrigerant
“ “
4
5
: Omitted if R22
: R407C
: R410A
Model Name
WM : Wall Mounted
Capacity Index
010
015
: 10,000 Btu/h
: 15,000 Btu/h
Series
G
J
: G Series
: J Series
Model Type
“ “
R
: Omitted if cooling only
: Heatpump
Catalog.indb 1Catalog.indb 1 3/2/2009 4:40:55 PM3/2/2009 4:40:55 PM
MWM-J-2009 Nomenclature
2
Outdoor Unit
M 5 LC 010 C R
Brand
M : Mcquay
Refrigerant
“ “
4
5
: Omitted if R22
: R407C
: R410A
Model Name
LC : Single Split Condensing Unit
Capacity Index
010
015
: 10,000 Btu/h
: 15,000 Btu/h
Series
C : C Series
Model Type
“ “
R
: Omitted if cooling only
: Heatpump
Catalog.indb 2Catalog.indb 2 3/2/2009 4:40:55 PM3/2/2009 4:40:55 PM
3
Product Line-Up MWM-J-2009
Product Line-Up
Indoor Unit
MWM-J
MWM
Nomenclature
Classi cation
PCB
Handset
Air Puri cation
Grille
Marking
Others
LGSN
G17
Saranet Filter
Bio Filter
A
CE
COOLING
ONLY
009J
ACBAA X X X X X X
009J
ACLAA X X X X X
015J
ACBAA X X X X X X
015J
ACLAA X X X X X
HEATPUMP
009JR
ACBAA X X X X X X
009JR
ACLAA X X X X X
015JR
ACBAA X X X X X X
015JR
ACLAA X X X X X
Catalog.indb 3Catalog.indb 3 3/2/2009 4:40:55 PM3/2/2009 4:40:55 PM
4
MWM-J-2009 Product Line-Up
Indoor Unit
M5WM-J
M5WM
Nomenclature
Classi cation
PCB
Handset
Air Puri cation
Grille
Marking
Others
LGSN
G17
Saranet Filter
Bio Filter
A
CE
COOLING
ONLY
010J ACBAA X X X X X X
010J ACLAA X X X X X
015J ACBAA X X X X X X
015J ACLAA X X X X X
HEATPUMP
010JR ACBAA X X X X X X
010JR ACLAA X X X X X
015JR ACBAA X X X X X X
015JR ACLAA X X X X X
Catalog.indb 4Catalog.indb 4 3/2/2009 4:40:56 PM3/2/2009 4:40:56 PM
5
Product Line-Up MWM-J-2009
Outdoor Unit
MLC
MLC
Nomenclature
Classi cation
PCB
Refrigerant
Control
FIN
Safety Devices
Compressor
Marking
Others
Cap Tube
EXV
Gold Coated
Blue Coated
Bare
Contactor
HP
LP
Rotary
CE
Drain Elbow
Low Ambient Kit
COOLING
ONLY
009C ACPOH X X X X
015C ACPOH X X X X
HEATPUMP
009CR ACPOH X X X X X
015CR ACPOJ X X X X X
Catalog.indb 5Catalog.indb 5 3/2/2009 4:40:56 PM3/2/2009 4:40:56 PM
6
MWM-J-2009 Product Line-Up
Outdoor Unit
M5LC
M5LC
Nomenclature
Classi cation
PCB
Refrigerant
Control
FIN
Safety Devices
Compressor
Marking
Others
Cap Tube
EXV
Gold Coated
Blue Coated
Bare
Contactor
HP
LP
Rotary
CE
Drain Elbow
Low Ambient Kit
COOLING
ONLY
010C ACPGG X X X X X
010C ACPOG X X X X
015C ACPGG X X X X X
015C ACPOG X X X X
HEATPUMP
010CR ACPOG X X X X
015CR ACPOG X X X X
Catalog.indb 6Catalog.indb 6 3/2/2009 4:40:56 PM3/2/2009 4:40:56 PM
7
Features MWM-J-2009
Features
Air Filtration with Bio Antibody Filter and Photo-catalytic Deodorizing Titanium Apatite
Filter
Bio Antibody Filter is effective against various airborne infectious viruses while Titanium Apatite Filter is able to
trap microscopic particles as well as break down and decompose odors. The lter can be used for approximately
3 years without replacement if wash about once every six months.
Self Diagnosis
The microprocessor provides the possibility to detect and diagnose any fault or malfunction that occurs in the
system. The error will be re ected by the blinking of the LED lights.
On / Off Button on Indoor Unit
On/Off button is provided on the front panel of the unit. It can be used when the remote controller is missing or
if its battery has run out. (Note: This button can also be used for forced operation mode)
Auto Random Restart
Auto random restart function allows the unit to automatic restart as the last setting condition when the power
supply is resumed after power failure. However, the compressor will restart randomly if more than one unit is
installed and sharing the same phase of power.
Wireless Remote Controller
The compact LCD transmitter is able to operate the air conditioner unit within the distance of 8 meters.
Fan speed can be set at high / medium / low / super low or automatic.
Sleep mode auto control will gradually increase or decrease the setting temperature to provide a
comfortable surrounding for sleeping.
Air ow direction can be controlled automatically.
Room temperature is controlled by electronic thermostat.
The real time timer allows the air conditioner to be switched On and Off automatically based on user
settings.
Turbo mode function is available to enables the required set temperature to be achieved in a short time.
Personalized Setting allows user to preset and store 2 groups of personal settings (including timer setting)
in the handset.
Energy Ef ciency
Using a more ef cient compressor and superior R410A refrigerant, M5WM10JR series achieves the highest
European Energy Rating of A/A. This ensures higher energy savings is accomplished especially during daily
usage. M5WM-J series participates in the Eurovent Certi cation Programme under category of Comfort Air
Conditioners rated below 12kW cooling capacity (AC1). The certi ed data for the certi ed models are listed in
the Eurovent Directory.
Catalog.indb 7Catalog.indb 7 3/2/2009 4:40:57 PM3/2/2009 4:40:57 PM
8
MWM-J-2009 Application Information
Application Information
Operating Range
Ensure the operating temperature is in allowable range.
Cooling only
Note :
Standard operating range.
With Low ambient kit. (Optional item)
Please refer to local dealer for unit of this specification.
Indoor temp. (°CDB)
Cooling
Outdoor temp. (°CDB)
Indoor temp. (°CWB)
Outdoor temp. (°CDB)
Indoor temp. (°CWB)
Heating
Outdoor temp. (°CWB)
-9
16 21
6
30
-5
19
35
14
46
23
Standard
point
Low ambient kit
18
-5
19
35
14
46
23
Low ambient kit
Standard
point
Standard
point
! Caution :
The use of your air conditioner
outside the range of working
temperature and humidity can
result in serious failure.
Heatpump
Catalog.indb 8Catalog.indb 8 3/2/2009 4:40:57 PM3/2/2009 4:40:57 PM
9
Application Information MWM-J-2009
70034 049971
Refrigerant Circuit Diagram
Model: MWM009J - MLC009C M5WM010J - M5LC010C
MWM015J - MLC015C M5WM015J - M5LC015C
70034 023154
Model: MWM009JR - MLC009CR M5WM010JR - M5LC010CR
M5WM015JR - M5LC015CR
Catalog.indb 9Catalog.indb 9 3/2/2009 4:40:58 PM3/2/2009 4:40:58 PM
10
MWM-J-2009 Application Information
70034 095236
Model: MWM015JR - MLC015CR
Catalog.indb 10Catalog.indb 10 3/2/2009 4:40:58 PM3/2/2009 4:40:58 PM
11
Application Information MWM-J-2009
Controller
G17
Operation Guide
1 Transmission Source
The source where the signal will be transmitted.
2 Signal Transmission Indication
Blink to con rm that the last setting has been transmitted
to the unit.
3 Temperature Setting
To set the desired room temperature, press the v or V
button to increase orde crease the set temperature.
The temperature setting range is from 16°C to 30°C
(optional setting 20°C to 30°C).
4 Personalize Setting
Press
and hold for 3s, then will blink. Press again to
cycle between and
Set the desire setting, then leave the hand set for 4s
without pressing any key and it will save the setting into the
programme.
Press once to activate the P1 setting, press again to
cycle between P1 and P2.
Press any key to deactivate the personalize setting.
5 Automatic Air Swing (optional)
Press the SWING
button to activate the automatic air
swing function.
To distribute the air to a speci c direction, press the
SWING button and wait until the louver move to the
desired direction and press the button once again.
6 Silent Function
Press
for quiet operation.
Fan speed turn to minimum speed.
Press again to deactivate the function.
7 Sleep Mode Setting
Press the SLEEP button will activate the sleep mode
function. This function is available under COOL, HEAT and
AUTO mode.
When the unit is operating under cooling mode, the set
temperature is increased by 0.5°C after 30 minutes, 1°C
after an hour, and 2°C after 2 hours.
When the unit is operating under heating mode, the set
temperature is decreased by 1°C after 30 minutes, 2°C
after an hour, and 3°C after 2 hours.
8 Operating Mode
Press the MODE button to select the type of operating
mode.
For cooling only unit, the available modes are: COOL (
7
),
DRY (6) and FAN (
).
9 Fan Speed Selection
Press the
button continuously will toggle the fan speed
in the following order:
Low p Med p High p Auto
Stop pressing when the desired fan speed appears on the
display screen.
10 “ON/OFF” Button
Press one to start the air conditioner unit.
Press again to stop the unit.
11 Timer Cancel
Press the TIMER CANCEL button to cancel the on timer
setting.
12 OFF Timer Setting
Press the OFF TIMER button will activate the off timer
function.
Set the desired off time by pressing the OFF TIMER button
continuously.
13 ON Timer Setting
Press the ON TIMER button will activate the on timer
function.
Set the desired on time by pressing the ON TIMER
button continuously. If the timer is set to 7.30am, the air
conditioner will turn on at 7.30am sharp.
14 Turbo Function
Press
for fast cooling.
Fan speed turn to maximum speed.
Press again to deactivate the function.
15 Clock Time Setting
Press
and hold to set the clock time.
MODE
P1 P2
SLEEP
SET
CANCEL
ON TIMER
SET
CANCEL
OFF TIMER
6a 6b
12
15
11
13
14
7
4
3
10
9
2
1
8
5
05_Application Information.indd 1105_Application Information.indd 11 4/1/2009 8:28:08 AM4/1/2009 8:28:08 AM
12
MWM-J-2009 Application Information
Installation Guideline
Safety Precautions
WARNING
CAUTION
Installation and maintenance should be performed by
qualifi ed persons who are familiar with local code and
regulation, and experienced with this type of appliance.
All fi eld wiring must be installed in accordance with the
national wiring regulation.
Ensure that the rated voltage of the unit corresponds
to that of the name plate before commencing wiring
work according to the wiring diagram.
The unit must be GROUNDED to prevent possible
hazard due to insulation failure.
All electrical wiring must not touch the refrigerant
piping or any moving parts of the fan motors.
Confi rm that the unit has been switched OFF before
installing or servicing the unit.
Disconnect from the main power supply before
servicing the air conditioner unit.
DO NOT pull out the power cord when the power is
ON. This may cause serious electrical shocks which
may result in fi re hazards.
Keep the indoor and outdoor units, power cable and
transmission wiring, at least 1m from TVs and radios,
to prevent distorted pictures and static. {Depending on
the type and source of the electrical waves, static may
be heard even when more than 1m away}.
Please take note of the following important points
when installing.
Do not install the unit where leakage of ammable
gas may occur.
If gas leaks and accumulates around the unit, it
may cause re ignition.
Ensure that drainage piping is connected properly.
If the drainage piping is not connected properly,
it may cause water leakage which will dampen
the furniture.
Do not overcharge the unit.
This unit is factory pre-charged. Overcharge will
cause over-current or damage to the compressor.
Ensure that the unit’s panel is closed after service
or installation.
Unsecured panels will cause the unit to operate
noisily.
Sharp edges and coil surfaces are potential
locations which may cause injury hazards. Avoid
from being in contact with these places.
Before turning off the power supply, set the remote
controllers ON/OFF switch to the “OFF” position
to prevent the nuisance tripping of the unit. If this is
not done, the unit’s fans will start turning automatically
when power resumes, posing a hazard to service
personnel or the user.
Do not operate any heating apparatus too close to the
air conditioner unit. This may cause the plastic panel to
melt or deform as a result of the excessive heat.
Ensure the color of wires of the outdoor unit and
the terminal markings are same to the indoors
respectively.
IMPORTANT : DO NOT INSTALL OR USE THE
AIR CONDITIONER UNIT IN A LAUNDRY ROOM.
Do not use joined and twisted wires for incoming
power supply.
NOTICE
Disposal requirements
Your air conditioning product is marked with this symbol. This means that electrical and electronic products
shall not be mixed with unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of
the refrigerant, of oil and of other parts must be done by a quali ed installer in accordance with relevant
local and national legislation. Air conditioners must be treated at a specialized treatment facility for re-use,
recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential
negative consequences for the environment and human health. Please contact the installer or local authority
for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with relevant
local and national legislation.
Catalog.indb 12Catalog.indb 12 3/2/2009 4:41:00 PM3/2/2009 4:41:00 PM
13
Application Information MWM-J-2009
Installation Diagram
Indoor Unit
Air filter
M4 x 12L
Air-Purifying Filter with
bacteriostatic virustatic function (2)
Front panel
30mm or more from ceiling
Outdoor Unit
50mm or more from walls
(on both sides)
Air filter
Air-Purifying Filter with
bacteriostatic virustatic
function
Filter frame
Tab
Caulk pipe
hole gap
with putty.
Cut thermal insulation
pipe to an appropriate
length and wrap it with
tape, making sure that no
gap is left in the insulation
pipe's cut line.
Wrap the insulation pipe with
the finishing tape from bottom
to top.
Service lid
Opening service lid
Service lid is opening/closing
type.
Opening method
1) Remove the service lid
screws.
2) Pull out the service lid
diagonally down in
thedirection of the arrow.
1) Pull down.
250mm from wall
Caution
Before installing the unit, ensure that the power supply matches the power requirement of the air conditioner.
Installation of Indoor Unit
Service Space
Install the indoor unit at a location with the following requirements
Location is suitable for wiring, piping and drainage.
No obstruction of air ow into and out of unit where cooler air can be evenly distributed.
Ensure that air discharge is not short circuited with air intake.
Ensure that wall is suf ciently strong, rigid, at, perpendicular and vibration free.
Where air lter cassette can be slided in or out easily.
Where there is no danger of ammable gases.
Where there is no direct sunlight on unit.
min. 50
(Space for
maintenance)
Air flow
(Indoor)
min. 50
(Space for
maintenance)
03.n
im
rofecap
S(
)ecn
am
rof
rep
Required space
Catalog.indb 13Catalog.indb 13 3/2/2009 4:41:01 PM3/2/2009 4:41:01 PM
14
MWM-J-2009 Application Information
Routing of Piping
The refrigerant piping can be routed to the unit in one of 5 directions, by using the cut outs in the unit
casing (refer to Figure 1).
1
2
3
4
5
Figure 1
Carefully bend the pipes to the required position to align with the hole. For right hand and rear side draw
out, hold the bottom of the piping and x direction before shaping it to the desired position
(refer to Figure 2).
Right & Rear Side Routing
Right-back piping
Bind coolant pipe
and drain hose
together with
insulating tape.
Right-bottom
piping
Remove pipe port cover
here for right-bottom piping
Right-side
piping
Remove pipe port cover
here for right-side piping
Remove pipe port cover here for
left-bottom piping
Remove pipe port
cover here for
left-side piping
Left-back
piping
Left-side
piping
Left-bottom piping
Figure 2
Mounting Installation Plate
Paste the installation plan provided on the desired location on the wall and marks the holes location
accordingly.
Ensure the wall is strong enough to withstand the weight of the unit. Otherwise, it is necessary to reinforce
the wall with plates, beams or pillars.
Ensure the levelness of the installation plate, and x with 5 suitable screws.
Mounting plate
Mounting plate
fixing screw
Catalog.indb 14Catalog.indb 14 3/2/2009 4:41:02 PM3/2/2009 4:41:02 PM
15
Application Information MWM-J-2009
Fix the installation plate rmly to the wall, without tilting to left or right. Use a plumb line, if available.
Through
the wall
hole
Ø 65mm
Drain
hose
position
Recommended mounting plate
retention spots (5 spots in all)
Use tape measure as shown.
Position the end of a tape measure
at
Gas pipe end
Liquid pipe end
166
184
181.7
55554.5
153.8
263
51.9
800
45.9
42.2
288
42.2
45.9
42.2
All dimensions are in mm
In case of rear piping drawings out, drill a hole 65mm in diameter with a cone drill, slightly lower on the
outside wall.
Inside
Caulking
Outside
Wall embedded pipe
(Field supply)
Wall hole cover
(Field supply)
Wall embedded pipe
(Field supply)
Ø65
Hole with cone drill
Mounting Unit onto the Installation Plate
Hook the indoor unit onto the upper portion of the installation plate (engage the two hooks at the rear top of
the indoor unit with the upper edge of the installation plate). Ensure the hooks are properly seated onto the
installation plate by moving it to the left and right.
To attach the indoor unit, hook the claws of the bottom frame to the mounting plate. If the claws are dif cult
to hook, remove the front grille.
To remove the indoor unit, push the marked area (at the lower part of the front grille) to release the claws.
If it is dif cult to release, remove the front grille.
Mounting
plate
Clip
Mark (rear side)
Bottom frame
Front grille
Mounting plate
Interconnecting
wires
Hang indoor unit's hook here.
Wire guide
When stripping the
ends of interconnecting
wires in advance, bind
right ends of wires with
insulating tape.
Catalog.indb 15Catalog.indb 15 3/2/2009 4:41:03 PM3/2/2009 4:41:03 PM
16
MWM-J-2009 Application Information
Water Drainage Piping
The indoor drain pipe must be downward gradient for smooth drainage. Avoid situation as shown in gure
below.
End
dipped
into
water
Water
leaking
Water
leaking
Water
leaking
Wrong
Wrong
Wrong
Drain
Water Drainage
Water
Retention
Correct
Installation of Outdoor Unit
Condensed Water Disposal of Outdoor Unit (Heat Pump Unit Only)
There are 2 holes on the base of outdoor unit for condensed water to ow out. Insert the drain elbow to
one of the holes.
To install the drain elbow, rst insert one portion of the hook to the base (portion A), the pull the drain elbow
in the direction shown by the arrow while inserting the other portion to the base. After installation, check to
ensure that the drain elbow clings to base rmly.
If the unit is installed in a snowy and chilly area, condensed water may freeze in the base. In such case,
please remove plug at the bottom of unit to smooth the drainage.
A
Catalog.indb 16Catalog.indb 16 3/2/2009 4:41:04 PM3/2/2009 4:41:04 PM
17
Application Information MWM-J-2009
As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve
maximum cooling capacity, the location selected for outdoor unit should ful ll the following requirements:
Install the condensing (outdoor) unit in a way such that hot air distributed by the outdoor condensing unit
cannot be drawn in again (as in the case of short circuit of hot discharge air). Allow suf cient space for
maintenance around the unit.
Ensure that there is no obstruction of air ow into or out of the unit. Remove obstacles which block air
intake or discharge.
The location must be well ventilated, so that the unit can draw in and distribute plenty of air thus lowering
the condensing temperature.
A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.
A place protected from direct sunlight. Otherwise use an awning for protection, if necessary.
The location must not be susceptible to dust or oil mist.
Installation Clearance
Outdoor units must be installed such that there is no short circuit of the hot discharge air or obstruction to
smooth air ow. Select the coolest possible place where intake air should not be hotter than the outside
temperature (max. 45˚C).
ALL MODELS A B C D
Minimum Distance 300 mm 1000 mm 300 mm 500 mm
CAUTION : If the condensing unit is operated in an atmosphere containing oils (including machine oils), salt (coastal area),
sulphide gas (near hot spring, oil re nery plant), such substances may lead to failure of the unit.
Catalog.indb 17Catalog.indb 17 3/2/2009 4:41:06 PM3/2/2009 4:41:06 PM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72

McQuay M5WM015JR User manual

Category
Split-system air conditioners
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI