Hydrel m9000 Series Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Hydrel m9000 Series Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
INSTALLATION DIAGRAM
1.
2.
Remove existing power module or power
cord by removing the junction box cover &
gasket and undoing the wire nuts (3). Then
loosen the cord seal so you can pull the cord
all the way through. Do not discard the
junction box cover, screws and gasket, you
will need to re-use those.
3.
Install the new LED driver module by running
pig tailed supply cord from power module
through cord seal and junction box cover
(provide enough cord for proper splicing
within junction box).
4.
Tighten junction box seal nut around power
cord. Make electrical connection using
silicone-filled wire nuts or fill junction box
with re-enterable potting compound (PC21,
ordered separately) prior to replacing lid and
gasket.
5.
6.
7.
Re-install junction box cover and gasket.
Tighten to ensure proper sealing.
CAUTION: DO NOT OVER TIGHTEN
(20 in-lbs or 2 N-m).
M9000 Series LED Retrofit
INSTALLATION INSTRUCTIONS
Installation should be performed by a qualified electrician
in accordance with the National Electrical Code
and relevant local codes.
SUITABLE FOR WET LOCATIONS
©2014 Acuity Brands Lighting, Inc.
7/30/15
M9000 LED retro
NOTE: Hydrel Reserves The Right To Modify Specification Without Notice.
Any dimension on this sheet is to be assumed as a reference dimension:
“Used for information purposes only. It does not govern manufacturing or
inspection requirements.” (ANSI Y14.5-1973)
9144 Deering Avenue | Chatsworth, CA 91311
Phone: 866.533.9901 | Fax: 866.533.5291
www.hydrel.com
Remove door assembly.
1.
NOTICE:
DO NOT INSTALL RETROFIT WHILE SYSTEM
IS ENERGIZED. TURN OFF POWER BEFORE
INSTALLATION.
Remove existing lamp module by
unplugging it from the power cord.
2.
3. 4.
Install the new LED lamp module by plugging
it into the driver and positioning it in the
housing to key into the existing mounting
ring to maintain original aiming.
Close the fixture by replacing the metal door.
CAUTION: DO NOT OVER TIGHTEN
(20 in-lbs or 2 N-m).
©2014 Acuity Brands Lighting, Inc.
7/30/15
M9000 LED retro
NOTE: Hydrel Reserves The Right To Modify Specification Without Notice.
Any dimension on this sheet is to be assumed as a reference dimension:
“Used for information purposes only. It does not govern manufacturing or
inspection requirements.” (ANSI Y14.5-1973)
SPLICE
SUPPLY POWERPOWER FROM FIXTURE
SUPPLY POWER - LINE VOLTAGE
0-10 LOW VOLTAGE DIMMING LINE
-
+
POWER FROM FIXTURE
2. LDIM 5 WIRE - SINGLE CORD TO DOUBLE CORD
1. STANDARD 3 WIRE ELECTRICAL - SINGLE CORD TO SINGLE CORD
9144 Deering Avenue | Chatsworth, CA 91311
Phone: 866.533.9901 | Fax: 866.533.5291
www.hydrel.com
WIRING DIAGRAMS
M9000 Series LED Retrofit
/