Digital Monitoring Products XR6 Product information

Category
Fire protection
Type
Product information
WARNING
THIS UNIT MAY BE PROGRAMMED TO USE AN ALARM
VERIFICATION FEATURE THAT RESULTS IN A DELAY OF
THE SYSTEM ALARM SIGNAL FROM THE INDICATED
CIRCUITS. THE TOTAL DELAY (CONTROL UNITS PLUS
SMOKE DETECTORS) SHALL NOT EXCEED 60 SEC-
ONDS. NO OTHER SMOKE DETECTOR SHALL BE
CONNECTED TO THESE CIRCUITS UNLESS APPROVED
BY THE LOCAL AUTHORITY HAVING JURISDICTION.
LT-0445 (3/01)
DMP transformers:
Model 320
16.5 VAC 40VA
Class 2 wire-in
Model 321
16.5 VAC 40VA
Class 2 plug-in
Model 324
16.5 VAC 20VA
Class 2 plug-in
Secondary Power
Supply
1.2 Amps max. charging
current. Use only 12 VDC
rechargeable batteries.
DMP Model 367. Replace
every 3 - 5 years.
Bell
10.4 - 13.2 VDC
Total current:
1.5 Amps max. w/ 40 VA
600mA w/ 20 VA
Household System
An alarm sounding device
must be installed indoors
so that it is clearly heard
in all sleeping areas.
Keypads
Models 670, 770, 771,
100mA @ 8 - 16 VDC
125mA with display lit
Models 690, 790, 791,
793
100mA @ 8 - 16 VDC
Model 692
75mA @ 8 -16 VDC
Bell
Plug into
120 VAC
outlet not
controlled
by switch.
16 - 18 gauge wire
Cold Water Pipe Earth Ground
Maximum AC wire distance
With 16 gauge wire: 70 feet
With 18 gauge wire: 40 feet
NFPA 72
This equipment should be installed in accordance with Chapter 2 of the National Fire Alarm
Code, ANSI/NFPA 72-1996, (National Fire Protection Association, Batterymarch Park, Quincy,
MA 02269). Printed information describing proper installation, operation, testing, maintenance,
evacuation planning, and repair service is to be provided with this equipment. Warning: Owner’s
instruction notice, not to be removed by anyone except occupant.
MODEL XR6 WIRING DIAGRAM
Refer to the XR6 Installation Guide (LT-0229) for a complete description of wiring connections.
Refer to the XR6 Programming Guide (LT-0230) for complete programming instructions.
POWER LIMITED
All circuits on the Model
XR6 comply with the
requirements for inherent
power limitation and are
Class 2.
Output Header J11
All outputs must be
connected to devices
located within the same
room as the control
panel.
Use DMP Model 300
Harness.
Front Tamper
Rear Tamper
Household Fire Warning
UL Recognized limited energy cable
must be used for connection of all
initiating, indicating, and
supplementary devices.
Tamper protection
when required for
Model 350A Attack
Resistant Enclo-
sure.
Zone 6 compatibility
identifier: A
Maximum operating
range: 8.8 VDC -
14.2 VDC.
See section 11.1 in the XR6
Installation Guide (LT-0229)
for a list of approved
2-wire smoke detectors.
Heat detectors, manual pull stations, or any other
shorting device. Unlimited number of units.
2-wire
smoke
detector
4-wire smoke detector
Power
Supervision
Relay
Up to 500mA auxiliary
current at 10.4 - 13.2
VDC from Terminal 7.
Smoke Output
100mA @ 10.4 - 13.2 VDC
Terminal 11
3.3k W
DMP Model 309
AC wiring must be in conduit and exit
out the left side of the panel enclosure. Wiring on
terminals 5 - 26
must exit to the
right and
maintain a 1/4”
separation from
the AC and
battery positive
wiring.
Command Processor Reset
Phone Jack Connector
PROG Programmer Header J8
Use DMP Model 330 Harness
RJ Cable Monitor J7
Use DMP Model 306 Harness
J4
J7
J8
J16 J11
U11
RJ SUP
1
2
3
4
EPROM
Socket
+ -
Smoke
Detector
22 GA. MIN BLACK
22 GA. MIN GREEN
22 GA. MIN YELLOW
22 GA. MIN RED
ZONE 4
ZONE 6
ZONE 2
ZONE 1
ZONE 3
1K W1K W
BLACK
RED
1K W1K W
1K W
AC AC +B -B BELL GND RED YEL GRN BLK SMK Z1 GND Z2 Z3 GND Z4 Z5 Z6+ Z6-
Red
Types of Service
When used with the 350A
Enclosure:
suitable for Grade A Local and
Police Connect Mercantile
Premises with basic line security,
Grade A Local and Police Connect
Mercantile Safe and Vault with
basic line security, Grade B Central
Station and Grade A proprietary.
See sections 17.3, 18.6, 19.2, and
19.5 - 19.7.
Suitable for Household Fire and
Grade A Household Burglary. Test
weekly.
Verification
Zone
6*
Control
Unit Delay
13.6 sec.
Smoke
Model
______
Detector
Delay
_____ sec.
Black
  • Page 1 1