Dometic Duo therm 3109266.001 Compressor Delay Kit Installation guide

Type
Installation guide
NOTUSEDONNOTUSEDON
SOMEMODELSSOMEMODELS
WHT
RED COMPSTARTERCOMPSTARTER
*
START
CAP PTCR
BRN
C
HERM
RUNCAPRUNCAP
FAN
RED
YEL
WHT
BLK WHT
GRN/YEL
*
RED
WHT
RED
4
WHT
5
6
BLU
BLK
YEL
1
2
3
SPLICECAPSPLICECAP
CONNECTOR
COMPRESSOR
GRN/YEL
R
MOTOR REVERSINGVALVEREVERSINGVALVE
BLK
S
O.L.
BLK
C
IN-LINE
6PINCONN6PINCONN
120VACIN120VACIN
120VACOUT120VACOUT
COMMON
RELAYBOARDRELAYBOARD
5
7
96
8
STEP
STEP
STEPSTEP
STEP
THIS KIT CONTAINS:
2ea.#6 Sheet Metal Screws
1ea.10" White wire with connectors
2ea.1/4" Female wire connectors
3109266.001 COMPRESSOR DELAY KIT
INSTALLATION INSTRUCTIONS
Form No. 3109272.009 11/99
©1999 The Dometic Corporation
LaGrange, IN 46761
A. GENERAL INSTRUCTIONS
All field wiring modifications should be made in compliance
with all National, State and local codes.
These instructions must be read and under-
stood before installation of this kit. This kit
must be installed by a Dometic Service Cen-
ter or a qualified service technician. Modifi-
cation of this product can be extremely haz-
ardous and could result in personal injury or
property damage.
Disconnect 115 volt AC power and the 12 volt
DC positive (+) terminal at the supply source.
Failure to follow these instructions could cre-
ate a shock hazard causing death or severe
personal injury.
The compressor delay kit, when installed properly, will de-
lay compressor start up for 2-1/2 minutes when 120VAC
power is interrupted or if the thermostat is inadvertently turned
off and back on again, causing the compressor to quick
cycle under load. This will help prevent breaker tripping and
may extend compressor life.
1ea.Relay board
1ea.3109272.009 Installation Instructions
B. INSTALLATION INSTRUCTIONS
1.Shut off 120VAC and 12VDC power to air conditioner or
heat pump.
2.Remove plastic outside shroud.
3.Locate and remove electrical box cover.
4.Find a suitable location and mount relay board inside
electrical box using 2 - #6 sheet metal screws provided.
Important: Give consideration to location of blue
compressor wire when choosing location. See Step 7.
5.Remove one white wire from common terminal of run
capacitor. Connect double spade end of 10" white wire
provided to this terminal. Reconnect original wire on
double spade.
6.Connect single spade end of white wire to common tab
on relay board. See FIG. 1.
7.Cut blue wire that goes to compressor. Make sure blue
wire is cut in a location that will allow each end to be
reconnected to relay board in Step 8 & 9. Strip both ends
of blue wire and install one 1/4" connector on each end.
8.Connect blue wire now coming from compressor to the
120VAC out on relay board. See FIG. 1.
9.Connect blue wire coming from 6-pin connector to the
120VAC IN terminal on relay board. See FIG. 1.
10.Check all connections for tightness and make sure none
will come in contact with electrical box or cover.
11.Install electrical box cover and plastic outside shroud.
12.Turn on 120VAC and 12VDC and check operation.
FIG. 1
(French 3109403.000)
  • Page 1 1

Dometic Duo therm 3109266.001 Compressor Delay Kit Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI