ICP DAS USA MDC-714, MDC-711 User manual

  • Hello! I am an AI chatbot trained to assist you with the ICP DAS USA MDC-714 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
MDC700SeriesUserManual
November2014,Version1.00
TheMDC700seriesmoduleisaModbusDataConcentratorthathastheabilitytocommunicate
withupto127ModbusslavedevicesusingModbusRTUprotocol.TheMDC700seriesmodulealso
supportstheModbusTCPprotocolforcommunicationwithPCbasedapplicationssuchasSCADA
(SupervisorControlandDataAcquisition)andHMI(HumanMachineInterface)programs.
ThefollowingsectionswillhelpyoutosetupyourMDC711/MDC714andshowyouhowtousethe
webinterfacetoobtainconfigurationandotherinformationrelativetotheMDC711/MDC714
moduleandassociatedslavedevices.
Basicoperatingprocedure
STEP1AssignanIPaddresstotheMDC711/MDC714.
STEP2Edittheconfig.csvfile.Notethatbeforeeditingthisfile,youshouldconfirmtheparameter
valueforanyassociatedSlavedevices.
STEP3Uploadtheconfig.csvfiletotheMDC711/MDC714.
STEP4Verifythestatusofboththeconnectionandtheconfigurationbybrowsingtheweb.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐1‐
AssigninganIPaddresstoMDC700
TheMDC711/MDC714isanEthernetdevice,whichcomeswithadefaultIPaddress;therefore,you
mustfirstassignanewIPaddresstothemodule.ToaccesstheMDC711/MDC711byusing
webbasedinterface,youmustknowtheIPaddresstheMDC711/MDC714isusing.The
MDC711/MDC714usesthefactorydefaultIPaddressof192.168.255.1bydefault.
STEP1PoweronthecomputerandtheMDC711/MDC714.
STEP2SettheIPconfigurationonyourcomputer.
IftheMDC711/MDC714isusingthedefaultIPaddressof192.168.255.1,youmustchosean
IPaddressforthecomputerintherangeof192.168.255.2192.168.255.253thatisnot
alreadyinuse.
NOTE:DetailsonhowtochangetheIPaddressonyourcomputerdependuponthetype
architectureandoperatingsystemyouareusing.UsethecomputerHelpandSupport
functionalitytosearchfor“IPAddressing.
STEP3Openawebbrowserandgotothewebsiteathttp://192.168.255.1,where192.168.255.1is
thedefaultIPaddressofyourMDC711/MDC714.
STEP4OpentheIPaddressconfigurationinterfacebyclickingtheEthernetConfiguration.
STEP5ChooseanewIPaddressforyourMDC711/MDC714.Makesurethattheaddressyoupickis
notcurrentlyinusebyanotherdeviceonthenetwork.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐2‐
NOTE:TheMDC711/MDC714canberesettofactorydefaultsbyshortingtheRESETpinto
GNDpinfor3seconds.TheLEDdisplaywillshow“RESETasbelowandremovetheIP
addresssetpreviouslyfortheMDC711/MDC714.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐3‐
Editingtheconfig.csvfile
TheMDC711/MDC714moduleisconfiguredusingtheconfig.csvfile,whichcanbeeditedtowork
withyourRTUslavedevices.TheCommaSeparatedValues(CSV)filescanbeviewedandeditedin
spreadsheetapplicationslikeMicrosoftExcel,orinanytexteditor.Thefollowingdescribeshowto
edittheconfigurationfileforyourdevices.
Thefiguresbelowillustratethefourmainsectionsthatneedtobeedited:ModbusConnection,
Moduleinformation,COMPortConfigurationandPollingDefinition.
ModbusConnection
TheModbusConnectionsectionisusedtoconfiguretheparametersfortheModbusIDof
MDC711/MDC714andTCP /IPPortnumber.
TCPPort:DefinetheTCP /IPPortnumber.
ModbusID:DefinetheModbusIDofMDC71 1/MDC714.
ModuleInformation
TheModuleInformationsectionisusedtorecordrelativeinformationfortheMDC711/MDC714.
# Mod busInfo
* thisismydataconcentrator
# TCPPort Mod busID
* 502 1
ModuleInfo:DefinetherelativeinformationforMDC711/MDC714.Thestringconstanthasa
maximumlengthof32c haracters.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐4‐
COMPortConfiguration
TheConnectionConfigurationforRS485sectionisusedtoconfiguretheparametersforthe
connectionbetweentheMDC711/MDC714moduleandtheRTUslavedevices.
# ComPortNo BaudRate DataBit Parity StopBit Timeout PollDelay OperatingMode
* 1 115200 8 0 1 100 20 Master
* 2 115200 8 0 1 100 20 Master
* 3 115200 8 0 1 100 20 Master
* 4 115200 8 0 1 100 20 Master
* 5 115200 8 0 1 100 20 Master
EachConnectionConfigurationconsistsof8parameters.Thedefinitionsoftheparametersareas
follows.
ComPortNo:IndicatestheCOMnumberusedinMDC711/MDC714.TheCOMportnumbercanbe1
or2forMDC711.TheCOMportnumbercanbe1,2,3,4or5forMDC714.
BaudRate:DefinesthetransmissionspeedbetweentheMDC711/MDC714andtheRTUslave
devices.Thebaudratecanbesetto4800bps,9600bps,19200bps,34800bps,57600
bpsor115200bpsdependingontheRTUslavedevicebeingused.
DataBit:Definesthenumberofdatabitsineachcharacter.Either7or8canbeselected.Besurethis
settingisthesameasthesettingfortheRTUslavedevice.
Parity:DefinestheParitybit.Theparitybitcanbesetto0(none),1(even)or2(odd).
StopBit:DefinestheStopbits.Either1or2canbeselected.
Timeout:DefinestheperiodoftimethattheMDC711/MDC714willwaitforaresponsefromthe
RTUslavedevice.
PollDelay:DefinesthePollDelaybetweeneachscanforModbusRTUcommunication.Theunitsare
milliseconds(ms).
OperatingMode:Thisparametercanbeignoredfornow.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐5‐
PollingDefinition
Beforeat temptingtoconfiguretheparametersforthePollingDefinition,besuretocheckthe
settingsforComport,theslaveaddress,thefunctioncodeandthequantityofregisters.
# UseComPort SlaveModbusID FunctionCode RegStartAddr RegCount
* 1 1 1 0 8
* 1 1 2 0 8
* 2 2 1 0 4
* 3 3 2 0 4
* 4 4 3 0 4
* 5 5 4 0 4
EachPollingDefinitionconsistsof5parameters.Thedefinitionsoftheparametersareasfollows.
UseComPort:DefinestheCOMporttobeusedtoconnectbetweentheslavedeviceandthe
MDC711/MDC714module.TheCOMportnumbercanbe1or2forMDC711.The
COMportnumbercanbe1,2,3,4or5forMDC714.
SlaveModbusID:Definestheidentificationoftheremoteslave.Thevalidrangeisfrom1to255.
FunctionCode:Definestherequestfunctioncode.Avalidcodecanbe1(ReadDO),2(ReadDI),3
(ReadAO)or4(ReadAI)dependingontheI/Ofeaturesoftheslavedevice.
RegStartAddr:Definesthestartingaddress,i.e.theaddressofthefirstregisterspecified.Thevalid
rangeisfrom0to8192.
RegCount:Definethequantityofregisterstoberead.Thevalidvalueisfr om1to64.
NOTE:
y Thetotalnumberofthepollingdefinitionsmustnotexceed127.
y TheMDC711/MDC714providesatotalof4127internalModbusregisters,4000ofthemare
usedtoholddatacollectedfromtheRTUslavedevices,meaningthatthetotalnumberof
registersthatcanbereadfromslavedevicesmustnotexceed4000.
y TheModbusaddressfortheMDC711/MDC714moduleisallocatedautomatically.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐6‐
Importing/exportingconfigurationfilesinCSVformat
Gotothewebinterfaceathttp://xxx.xxx.xxx.xxx,wherexxx.xxx.xxx.xxxistheIPaddressofyour
MDC711/MDC714.AnystandardbrowsercanbeusedtointerfacetheMDC711/MDC714,suchas
MozillaFirefox,InternetExplorerorGoogleChrome.
NOTE:Ifyouhaven’tchangedthedefaultoftheMDC711/MDC714,pleaserefertoAssigninganIP
addresstoMDC700”toconfigureit.
ImportingaCSVfiletoMDC711/MDC714
STEP1OpentheImportandExportinterfacebyclickingtheImport/ExportConfigurationbutton.
STEP2ChooseaCSVfilefromyourcomputerbyclickingtheChooseFilebutton.
STEP3ClicktheImportbuttontoimporttheconfig.csvfiletotheMDC711/MDC714.
NOTE:Aftertheimportprocessisfinished,theMDC711/MDC714willrebootin5seconds.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐7‐
ExportingaCSVfilefromMDC711/MDC714
STEP1OpentheImportandExportinterfacebyclickingtheImport/ExportConfigurationbutton.
STEP2ClicktheExportbuttontoexporttheconfig.csvfilefromtheMDC711/MDC714.Whenyou
clicktheExportbutton,youwillgetapopupboxtodownloadthefile.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐8‐
ConnectingtotheWebHMI
Gotothewebinterfaceathttp://xxx.xxx.xxx.xxx,wherexxx.xxx.xxx.xxxistheIPaddressofyour
MDC711/MDC714.AnystandardbrowsercanbeusedtointerfacetheMDC711/MDC714,suchas
MozillaFirefox,InternetExplorerorGoogleChrome.
NOTE:Thecontentsofthesectionmaybedifferentdependingonthesettingscontainedinthe
config.csvfile.
IntroductiontotheWebHMI
Afterconnectingtothewebsite,thefollowingsectionswillbedisplayed.
y ModuleInformation
TheModuleInformationsectionofthepageprovidesthemoduleinformationaboutthe
MDC711/MDC714.
y FirmwareInformation
IntheFirmwareInformationsectionofthepage,informationabouttheFirmwareVersionand
theOSVersionisdisplayed
y Connection
IntheConnectionsectionofthepage,informationaboutthecurrentConnectionconfiguration
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐9‐
isdisplayed,includingtheTCPPort,ModbusIDofMDC711/MDC714,BaudRate,DataBit,
Parity,StopBit,Timeout,DelayPollsandOperatingModedetails.
y PollingDefinition
InthePollingDefinitionsectionofthepage,informationaboutthecurrentconfigurationforthe
PollingDefinitionisdisplayed,includingtheComPort,SlaveModbusID,FunctionCode,Starting
AddressofRegisterandCountofRegisterdetails.
TheStateoftheConnection
WhenthestateisshownasGOOD,itindicatesthattheconnectionwassuccessfullyesta blishedand
theparametersettingsarevalid.
WhenthestateisshownasTIMEOUT,itindicatesthattheattemptedconnectionhasfailed.To
resolvethisissue,checkwhethertheparameterslistedbelowmatchthesettingsoftheRTUslave
device.
y BaudRate
y SlaveAddress
y DataFormat(DataBit,ParityandStopBit)
WhenthestateisshownasERROR:ILLEGALFUNCTION,itindicatesthattheconnectionwas
successfullyestablished,buttheparameterisinvalid.Toresolvethisissue,checkwhetherthe
FunctionCodelistedinthe PollingDefinitionmatchthesettingsoftheModbusRTUslavedevice.
WhenthestateisshownasERROR:ILLEGALDATAVALUE,itindicatesthattheconnectionwas
successfullyestablished,butoneormoreoftheparametersareinvalid.Toresolvethisissue,check
whethertheStartAddressofRegisterandCountofRegisterlistedinthePollingDefinitionmatchthe
settingsoftheModbusRTUslavedevice.
NOTE:TheWebHMIrequirestheAdobeFlashPlayertobeinstalled.ThelatestversionoftheAdobe
FlashPlayercanbedownloadedbyaccessingtheAdobeSystemsIncorporatedwebsite.The
followinginstructionswillhelpyoutoinstalltheAdobeFlashPlayerinyourwebbrowser.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐10‐
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐11‐
STEP1GototheAdobeFlashPlayerDownloadCenter
TheaddressforAdobeFlashPlayerDownloadCenterishttp://get.adobe.com/flashplayer/
NOTE:TheAdobeFlashPlayerissubjecttochangewithoutnotice;referto
http://www.adobe.com/support/flashplayer/downloads.htmlforthelatestversionofthis
software.
STEP2FollowtheinstructionstodownloadtheinstallationfileandinstallitonyourPC.
/