ICP DAS USA MDC-714 is a Modbus Data Concentrator that can communicate with up to 127 Modbus slave devices using Modbus RTU protocol. It supports Modbus TCP protocol for communication with PC-based applications such as SCADA and HMI programs.

Here is a brief overview of the capabilities of the MDC-714:

  • Modbus RTU and TCP support: The MDC-714 can communicate with Modbus slave devices using either Modbus RTU or Modbus TCP protocol. This makes it compatible with a wide range of devices.
  • Up to 127 slave devices: The MDC-714 can connect to and communicate with up to 127 Modbus slave devices. This allows you to easily integrate multiple devices into a single system.

ICP DAS USA MDC-714 is a Modbus Data Concentrator that can communicate with up to 127 Modbus slave devices using Modbus RTU protocol. It supports Modbus TCP protocol for communication with PC-based applications such as SCADA and HMI programs.

Here is a brief overview of the capabilities of the MDC-714:

  • Modbus RTU and TCP support: The MDC-714 can communicate with Modbus slave devices using either Modbus RTU or Modbus TCP protocol. This makes it compatible with a wide range of devices.
  • Up to 127 slave devices: The MDC-714 can connect to and communicate with up to 127 Modbus slave devices. This allows you to easily integrate multiple devices into a single system.
MDC700SeriesUserManual
November2014,Version1.00
TheMDC700seriesmoduleisaModbusDataConcentratorthathastheabilitytocommunicate
withupto127ModbusslavedevicesusingModbusRTUprotocol.TheMDC700seriesmodulealso
supportstheModbusTCPprotocolforcommunicationwithPCbasedapplicationssuchasSCADA
(SupervisorControlandDataAcquisition)andHMI(HumanMachineInterface)programs.
ThefollowingsectionswillhelpyoutosetupyourMDC711/MDC714andshowyouhowtousethe
webinterfacetoobtainconfigurationandotherinformationrelativetotheMDC711/MDC714
moduleandassociatedslavedevices.
Basicoperatingprocedure
STEP1AssignanIPaddresstotheMDC711/MDC714.
STEP2Edittheconfig.csvfile.Notethatbeforeeditingthisfile,youshouldconfirmtheparameter
valueforanyassociatedSlavedevices.
STEP3Uploadtheconfig.csvfiletotheMDC711/MDC714.
STEP4Verifythestatusofboththeconnectionandtheconfigurationbybrowsingtheweb.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐1‐
AssigninganIPaddresstoMDC700
TheMDC711/MDC714isanEthernetdevice,whichcomeswithadefaultIPaddress;therefore,you
mustfirstassignanewIPaddresstothemodule.ToaccesstheMDC711/MDC711byusing
webbasedinterface,youmustknowtheIPaddresstheMDC711/MDC714isusing.The
MDC711/MDC714usesthefactorydefaultIPaddressof192.168.255.1bydefault.
STEP1PoweronthecomputerandtheMDC711/MDC714.
STEP2SettheIPconfigurationonyourcomputer.
IftheMDC711/MDC714isusingthedefaultIPaddressof192.168.255.1,youmustchosean
IPaddressforthecomputerintherangeof192.168.255.2192.168.255.253thatisnot
alreadyinuse.
NOTE:DetailsonhowtochangetheIPaddressonyourcomputerdependuponthetype
architectureandoperatingsystemyouareusing.UsethecomputerHelpandSupport
functionalitytosearchfor“IPAddressing.
STEP3Openawebbrowserandgotothewebsiteathttp://192.168.255.1,where192.168.255.1is
thedefaultIPaddressofyourMDC711/MDC714.
STEP4OpentheIPaddressconfigurationinterfacebyclickingtheEthernetConfiguration.
STEP5ChooseanewIPaddressforyourMDC711/MDC714.Makesurethattheaddressyoupickis
notcurrentlyinusebyanotherdeviceonthenetwork.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐2‐
NOTE:TheMDC711/MDC714canberesettofactorydefaultsbyshortingtheRESETpinto
GNDpinfor3seconds.TheLEDdisplaywillshow“RESETasbelowandremovetheIP
addresssetpreviouslyfortheMDC711/MDC714.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐3‐
Editingtheconfig.csvfile
TheMDC711/MDC714moduleisconfiguredusingtheconfig.csvfile,whichcanbeeditedtowork
withyourRTUslavedevices.TheCommaSeparatedValues(CSV)filescanbeviewedandeditedin
spreadsheetapplicationslikeMicrosoftExcel,orinanytexteditor.Thefollowingdescribeshowto
edittheconfigurationfileforyourdevices.
Thefiguresbelowillustratethefourmainsectionsthatneedtobeedited:ModbusConnection,
Moduleinformation,COMPortConfigurationandPollingDefinition.
ModbusConnection
TheModbusConnectionsectionisusedtoconfiguretheparametersfortheModbusIDof
MDC711/MDC714andTCP /IPPortnumber.
TCPPort:DefinetheTCP /IPPortnumber.
ModbusID:DefinetheModbusIDofMDC71 1/MDC714.
ModuleInformation
TheModuleInformationsectionisusedtorecordrelativeinformationfortheMDC711/MDC714.
# Mod busInfo
* thisismydataconcentrator
# TCPPort Mod busID
* 502 1
ModuleInfo:DefinetherelativeinformationforMDC711/MDC714.Thestringconstanthasa
maximumlengthof32c haracters.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐4‐
COMPortConfiguration
TheConnectionConfigurationforRS485sectionisusedtoconfiguretheparametersforthe
connectionbetweentheMDC711/MDC714moduleandtheRTUslavedevices.
# ComPortNo BaudRate DataBit Parity StopBit Timeout PollDelay OperatingMode
* 1 115200 8 0 1 100 20 Master
* 2 115200 8 0 1 100 20 Master
* 3 115200 8 0 1 100 20 Master
* 4 115200 8 0 1 100 20 Master
* 5 115200 8 0 1 100 20 Master
EachConnectionConfigurationconsistsof8parameters.Thedefinitionsoftheparametersareas
follows.
ComPortNo:IndicatestheCOMnumberusedinMDC711/MDC714.TheCOMportnumbercanbe1
or2forMDC711.TheCOMportnumbercanbe1,2,3,4or5forMDC714.
BaudRate:DefinesthetransmissionspeedbetweentheMDC711/MDC714andtheRTUslave
devices.Thebaudratecanbesetto4800bps,9600bps,19200bps,34800bps,57600
bpsor115200bpsdependingontheRTUslavedevicebeingused.
DataBit:Definesthenumberofdatabitsineachcharacter.Either7or8canbeselected.Besurethis
settingisthesameasthesettingfortheRTUslavedevice.
Parity:DefinestheParitybit.Theparitybitcanbesetto0(none),1(even)or2(odd).
StopBit:DefinestheStopbits.Either1or2canbeselected.
Timeout:DefinestheperiodoftimethattheMDC711/MDC714willwaitforaresponsefromthe
RTUslavedevice.
PollDelay:DefinesthePollDelaybetweeneachscanforModbusRTUcommunication.Theunitsare
milliseconds(ms).
OperatingMode:Thisparametercanbeignoredfornow.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐5‐
PollingDefinition
Beforeat temptingtoconfiguretheparametersforthePollingDefinition,besuretocheckthe
settingsforComport,theslaveaddress,thefunctioncodeandthequantityofregisters.
# UseComPort SlaveModbusID FunctionCode RegStartAddr RegCount
* 1 1 1 0 8
* 1 1 2 0 8
* 2 2 1 0 4
* 3 3 2 0 4
* 4 4 3 0 4
* 5 5 4 0 4
EachPollingDefinitionconsistsof5parameters.Thedefinitionsoftheparametersareasfollows.
UseComPort:DefinestheCOMporttobeusedtoconnectbetweentheslavedeviceandthe
MDC711/MDC714module.TheCOMportnumbercanbe1or2forMDC711.The
COMportnumbercanbe1,2,3,4or5forMDC714.
SlaveModbusID:Definestheidentificationoftheremoteslave.Thevalidrangeisfrom1to255.
FunctionCode:Definestherequestfunctioncode.Avalidcodecanbe1(ReadDO),2(ReadDI),3
(ReadAO)or4(ReadAI)dependingontheI/Ofeaturesoftheslavedevice.
RegStartAddr:Definesthestartingaddress,i.e.theaddressofthefirstregisterspecified.Thevalid
rangeisfrom0to8192.
RegCount:Definethequantityofregisterstoberead.Thevalidvalueisfr om1to64.
NOTE:
y Thetotalnumberofthepollingdefinitionsmustnotexceed127.
y TheMDC711/MDC714providesatotalof4127internalModbusregisters,4000ofthemare
usedtoholddatacollectedfromtheRTUslavedevices,meaningthatthetotalnumberof
registersthatcanbereadfromslavedevicesmustnotexceed4000.
y TheModbusaddressfortheMDC711/MDC714moduleisallocatedautomatically.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐6‐
Importing/exportingconfigurationfilesinCSVformat
Gotothewebinterfaceathttp://xxx.xxx.xxx.xxx,wherexxx.xxx.xxx.xxxistheIPaddressofyour
MDC711/MDC714.AnystandardbrowsercanbeusedtointerfacetheMDC711/MDC714,suchas
MozillaFirefox,InternetExplorerorGoogleChrome.
NOTE:Ifyouhaven’tchangedthedefaultoftheMDC711/MDC714,pleaserefertoAssigninganIP
addresstoMDC700”toconfigureit.
ImportingaCSVfiletoMDC711/MDC714
STEP1OpentheImportandExportinterfacebyclickingtheImport/ExportConfigurationbutton.
STEP2ChooseaCSVfilefromyourcomputerbyclickingtheChooseFilebutton.
STEP3ClicktheImportbuttontoimporttheconfig.csvfiletotheMDC711/MDC714.
NOTE:Aftertheimportprocessisfinished,theMDC711/MDC714willrebootin5seconds.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐7‐
ExportingaCSVfilefromMDC711/MDC714
STEP1OpentheImportandExportinterfacebyclickingtheImport/ExportConfigurationbutton.
STEP2ClicktheExportbuttontoexporttheconfig.csvfilefromtheMDC711/MDC714.Whenyou
clicktheExportbutton,youwillgetapopupboxtodownloadthefile.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐8‐
ConnectingtotheWebHMI
Gotothewebinterfaceathttp://xxx.xxx.xxx.xxx,wherexxx.xxx.xxx.xxxistheIPaddressofyour
MDC711/MDC714.AnystandardbrowsercanbeusedtointerfacetheMDC711/MDC714,suchas
MozillaFirefox,InternetExplorerorGoogleChrome.
NOTE:Thecontentsofthesectionmaybedifferentdependingonthesettingscontainedinthe
config.csvfile.
IntroductiontotheWebHMI
Afterconnectingtothewebsite,thefollowingsectionswillbedisplayed.
y ModuleInformation
TheModuleInformationsectionofthepageprovidesthemoduleinformationaboutthe
MDC711/MDC714.
y FirmwareInformation
IntheFirmwareInformationsectionofthepage,informationabouttheFirmwareVersionand
theOSVersionisdisplayed
y Connection
IntheConnectionsectionofthepage,informationaboutthecurrentConnectionconfiguration
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐9‐
isdisplayed,includingtheTCPPort,ModbusIDofMDC711/MDC714,BaudRate,DataBit,
Parity,StopBit,Timeout,DelayPollsandOperatingModedetails.
y PollingDefinition
InthePollingDefinitionsectionofthepage,informationaboutthecurrentconfigurationforthe
PollingDefinitionisdisplayed,includingtheComPort,SlaveModbusID,FunctionCode,Starting
AddressofRegisterandCountofRegisterdetails.
TheStateoftheConnection
WhenthestateisshownasGOOD,itindicatesthattheconnectionwassuccessfullyesta blishedand
theparametersettingsarevalid.
WhenthestateisshownasTIMEOUT,itindicatesthattheattemptedconnectionhasfailed.To
resolvethisissue,checkwhethertheparameterslistedbelowmatchthesettingsoftheRTUslave
device.
y BaudRate
y SlaveAddress
y DataFormat(DataBit,ParityandStopBit)
WhenthestateisshownasERROR:ILLEGALFUNCTION,itindicatesthattheconnectionwas
successfullyestablished,buttheparameterisinvalid.Toresolvethisissue,checkwhetherthe
FunctionCodelistedinthe PollingDefinitionmatchthesettingsoftheModbusRTUslavedevice.
WhenthestateisshownasERROR:ILLEGALDATAVALUE,itindicatesthattheconnectionwas
successfullyestablished,butoneormoreoftheparametersareinvalid.Toresolvethisissue,check
whethertheStartAddressofRegisterandCountofRegisterlistedinthePollingDefinitionmatchthe
settingsoftheModbusRTUslavedevice.
NOTE:TheWebHMIrequirestheAdobeFlashPlayertobeinstalled.ThelatestversionoftheAdobe
FlashPlayercanbedownloadedbyaccessingtheAdobeSystemsIncorporatedwebsite.The
followinginstructionswillhelpyoutoinstalltheAdobeFlashPlayerinyourwebbrowser.
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐10‐
Copyright©2014ICPDASCo.,Ltd.AllRightsReserved. Email:[email protected]‐11‐
STEP1GototheAdobeFlashPlayerDownloadCenter
TheaddressforAdobeFlashPlayerDownloadCenterishttp://get.adobe.com/flashplayer/
NOTE:TheAdobeFlashPlayerissubjecttochangewithoutnotice;referto
http://www.adobe.com/support/flashplayer/downloads.htmlforthelatestversionofthis
software.
STEP2FollowtheinstructionstodownloadtheinstallationfileandinstallitonyourPC.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11

ICP DAS USA MDC-714 User manual

Type
User manual
This manual is also suitable for

ICP DAS USA MDC-714 is a Modbus Data Concentrator that can communicate with up to 127 Modbus slave devices using Modbus RTU protocol. It supports Modbus TCP protocol for communication with PC-based applications such as SCADA and HMI programs.

Here is a brief overview of the capabilities of the MDC-714:

  • Modbus RTU and TCP support: The MDC-714 can communicate with Modbus slave devices using either Modbus RTU or Modbus TCP protocol. This makes it compatible with a wide range of devices.
  • Up to 127 slave devices: The MDC-714 can connect to and communicate with up to 127 Modbus slave devices. This allows you to easily integrate multiple devices into a single system.