ABB PowerWave 33 Series 3 User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual
© Copyright 2017 ABB, All rights reserved
User Manual
PowerWave 33 Series 3
60 – 120 kW
Modifications reserved
Page 2/50
Document information
: 4NWP100532R0001_OPM_ABB_PW33_S3_60-120kW_EN_REV-B.docx
:
PowerWave 33 Series 3
: 02.02.2016
: 4NWP100532R0001
: 4NWD003253
: B
Foreword
OPERATIONS INSIDE THE UPS MUST BE
PERFORMED BY A SERVICE ENGINEER FROM THE
MANUFACTURER OR FROM AN AGENT CERTIFIED
BY THE MANUFACTURER.
This user manual contains guidelines for delivery, installation and commissioning of the UPS, and is
intended for personnel who plan the installation, commissioning, use and service of the UPS. The reader
is expected to know the fundamentals of electricity, wiring, electrical components and electrical
schematic symbols.
CAREFULLY READ THE USER MANUAL BEFORE
OPERATING THE UPS OR WORKING ON IT.
Modifications reserved
Page 3/50
Contents
1 Safety regulation ....................................................................................... 5
1.1 Safety rules ............................................................................................................ 5
1.2 Safety symbols and warnings ............................................................................... 6
2 General characteristics ............................................................................. 7
2.1 Environmental requirements ................................................................................. 7
2.2 CE marking and declaration of safety and emc conformity ................................. 7
2.3 Inquiries .................................................................................................................. 7
2.4 Type plate and model identification ...................................................................... 8
3 Transport – storage – unpacking .............................................................. 9
3.1 Visual inspection .................................................................................................... 9
3.2 Storage ................................................................................................................... 9
3.3 Unpacking ............................................................................................................ 10
3.3.1 Standard packaging .............................................................................................................. 10
3.3.2 Optional sea freight packaging (wooden box) ........................................................................ 12
4 Installation and wiring ............................................................................. 14
4.1 Positioning of the UPS and battery cabinet........................................................ 14
4.2 Electrical installation ............................................................................................ 16
4.3 Block diagram ...................................................................................................... 17
4.4 Wiring ................................................................................................................... 17
4.4.1 Conversion from single input feed to dual input feed and vice-versa...................................... 20
4.4.2 Installation checklist ............................................................................................................... 20
5 Connectivity ............................................................................................. 21
5.1 Customer interface .............................................................................................. 21
5.1.1 Customer inputs .................................................................................................................... 22
5.1.2 Customer outputs (OPTIONAL USB port & Relay card) ......................................................... 22
5.2 Connectivity options ............................................................................................ 23
5.2.1 Remote SHUT DOWN (EPO) ................................................................................................. 23
5.2.2 Generator on facilities ............................................................................................................ 23
5.2.3 Wavemon Shutdown and management software .................................................................. 24
5.2.4 SNMP CARD/ADAPTER for network management / remote monitoring ................................ 25
6 Operation ................................................................................................. 27
6.1 Commissioning .................................................................................................... 27
6.2 Parallel - multicabinet- configuration .................................................................. 27
6.2.1 Installation instructions .......................................................................................................... 27
6.2.2 Paralleling of UPS-Cabinets ................................................................................................... 28
Modifications reserved
Page 4/50
6.2.3 Dip switch SW1-9 ................................................................................................................. 29
6.2.4 Multidrop Master/Slave configuration - Dip switch SW2 ....................................................... 29
6.3 Control panel ........................................................................................................ 30
6.3.1 Led indicators ....................................................................................................................... 30
6.3.2 Buttons ................................................................................................................................. 31
6.3.3 Status screens ...................................................................................................................... 31
6.3.4 Main menu screen ................................................................................................................ 32
6.3.5 Event log screen ................................................................................................................... 32
6.3.6 Measurements screen .......................................................................................................... 33
6.3.7 Commands screen ............................................................................................................... 33
6.3.8 Ups data ............................................................................................................................... 34
6.3.9 Set-up user........................................................................................................................... 34
6.3.10 Set-up service ...................................................................................................................... 34
6.4 Operating modes .................................................................................................. 35
6.4.1 Mode "ON LINE" (INVERTER MODE) .................................................................................... 35
6.4.2 Mode"OFF-LINE"(ECO- or BYPASS MODE) ......................................................................... 35
6.4.3 "Maintenance bypass" - mode .............................................................................................. 36
6.4.4 Output switch/parallel isolator (ia2) ....................................................................................... 36
6.5 Operation procedures .......................................................................................... 37
6.5.1 Start-up procedure ............................................................................................................... 37
6.5.2 Shutdown procedure ............................................................................................................ 38
6.5.3 Load Transfer: from Inverter operation to Maintenance Bypass ............................................ 39
6.5.4 Load Transfer: from Maintenance Bypass to Inverter operations .......................................... 40
7 Maintenance ............................................................................................ 42
7.1 User responsibilities ............................................................................................. 42
7.2 Preventative maintenaince ................................................................................... 42
7.3 Deep battery test .................................................................................................. 42
7.4 Battery maintenance, disposal and recycling ..................................................... 43
8 Troubleshooting....................................................................................... 44
8.1 Alarms ................................................................................................................... 44
8.2 Menu, commands, event log and measurements ............................................... 44
8.3 Fault identification and rectification .................................................................... 44
9 End of life treatment ................................................................................ 45
9.1 UPS and material disposing ................................................................................ 45
10 Attachments ......................................................................................... 46
10.1 Technical data sheet .......................................................................................... 46
Modifications reserved
Page 5/50
1 Safety regulation
1.1 Safety rules
This UPS operates with mains, battery or bypass power. It contains components that carry high currents
and voltages. The properly installed UPS is grounded to earth and IP20 rated against electric shock
and foreign objects. Installation and service have to be performed by the manufacturer’s qualified
technicians or their certified service partners.
WARNING!
THERE IS DANGER OF ELECTRICAL SHOCK
This user manual contains guidelines for delivery, installation and commissioning of the UPS, and is
intended for personnel who plan the installation, commissioning, use and service of the UPS. The reader
is expected to know the fundamentals of electricity, wiring, electrical components and electrical
schematic symbols.
NOTE!
READ THE INFORMATION IN ORDER TO AVOID EQUIPMENT DAMAGE
The only user operations permitted are:
Use of the LCD control panel (LCD) and of the maintenance bypass
Start-up and shut-down of the UPS user field (except during commissioning start-up)
Operation of additional connectivity modules:
SNMP adapters and their software
Modem/GSM or modem/Ethernet adapters and their software
The user must take the precautions set out in this manual and only perform the operations described.
The UPS operator must adhere to the instructions in this manual. Any deviations from the instructions
could be dangerous to the user or could cause accidental load loss.
THE MANUFACTURER DOES NOT TAKE ANY RESPONSIBILITY FOR DAMAGE CAUSED BY
INCORRECT USE OF THE UPS.
WARNING!
IT IS PROHIBITED TO REMOVE ANY SCREWS FROM THE UPS OR FROM
THE BATTERY CABINET. THERE IS A DANGER OF ELECTRIC SHOCK.
Modifications reserved
Page 6/50
WARNING!
HIGH FAULT CURRENTS (LEAKAGE CURRENTS):
BEFORE CONNECTING THE MAINS, YOU MUST ENSURE THAT THERE IS A
PROPER EARTH CONNECTION!
WARNING!
THE USER MUST DISPLAY A WARNING SHIELD ON ALL PRIMARY UPS
CIRCUIT BREAKERS. THE SERVICE PERSONNEL HAS TO BE INFORMED
ABOUT DANGEROUS VOLTAGES. THE WARNING PANELS MUST CONTAIN
THE FOLLOWING TEXT: “ BEFORE STARTING WITH MAINTENANCE WORK
ON THE CIRCUIT BREAKERS, MAKE SURE THE UPS IS ISOLATED.”
1.2 Safety symbols and warnings
The following symbols are used in this manual; the list below provides a description of each symbol.
DANGER Serious damage to health / risk to life
This symbol in conjunction with the signal word "DANGER" indicates an
imminent electrical hazard. Failure to observe the related safety note may cause
personnel injury or death or equipment damages.
WARNING Bodily injury
This symbol in conjunction with the signal word "WARNING" indicates a
potentially dangerous situation. Failure to observe the related safety note may
cause personnel injury or death or equipment damages.
IMPORTANT (NOTE)
This symbol indicates operator tips, particularly useful or important information
for the use of the product. This symbol and wording does not indicate a
dangerous situation.
PE Protective Earth terminal
The PE terminal must be connected to earth prior to making any other
connection to the equipment.
AC alternating current or voltage
A terminal to which or from which an alternating current or voltage is applied or
supplied.
DC direct current or voltage
A terminal to which or from which direct current or voltage is applied or supplied.
Battery
This symbol indicates a battery (source of DC voltage and current) which can be
both internal or external to the UPS system and accessories (battery cabinet).
Power ON/OFF or shutdown
Symbol used to indicate the action of Powering ON, Idle or shutdown the UPS.
Recycle
Do not dispose with ordinary trash.
Modifications reserved
Page 7/50
2 General characteristics
2.1 Environmental requirements
WARNING!
THIS IS A PRODUCT FOR COMMERCIAL AND INDUSTRIAL APPLICATION
IN THE SECOND ENVIRONMENT INSTALLATION RESTRICTIONS OR
ADDITIONAL MEASURES MAY BE NEEDED TO PREVENT DISTURBANCES.
To operate the UPS at the best efficiency point, your installation site should meet the environmental
parameters outlined in this manual. Excessive amount of dust or moisture in the operating environment
may cause damage or lead to malfunction. The UPS should be always protected from the outside
weather and sunshine. The operating environment must meet the weight, airflow, size and clearance
requirements specified in the section 4.1 of this manual or in the technical datasheet (TDS) of the same
product (separate document).
Under no circumstances, the UPS should be installed in an airtight room, in the presence of flammable
gases, or in an environment, exceeding environmental requirements specified here below.
The ambient temperature for operating the UPS must be in the range 0 °C to +40 °C. The Ideal
temperature also recommended to achieve a long life of the UPS and VRLA batteries is +20°C to +25°C.
The relative humidity should be below 95% (non-condensing) and the max. altitude without de-rating is
1000m above sea level.
2.2 CE marking and declaration of safety and emc conformity
The product has the CE marking in compliance with the following European directives
Low Voltage Directive: 2006/95/EC
EMC Directive: 2004/108/EC
The product applies the actual UPS standards, listed in the Table 1 below.
Table 1: UPS Standards.
Description Product standards General standards
Safety IEC/EN 62040-1 IEC/EN 60950-1
Electromagnetic Compatibility (EMC)
IEC/EN 62040-2
Emission cat. C3
Immunity cat. C3
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
IEC/EN 61000-4-8
IEC/EN 61000-2-2
Performance IEC/EN 62040-3
Environmental aspects IEC/EN 62040-4
2.3 Inquiries
Address inquiries about the UPS to the local office or agent CERTIFIED by the supplier. Please note the
type code and the serial number shown in the type plate of the product (see section 2.4) of the
equipment and contact your nearest agent CERTIFIED by the supplier.
Modifications reserved
Page 8/50
2.4 Type plate and model identification
The type plate shown in Figure 1 here below is positioned on the internal side of the UPS door in a
center position. It contains the basic electrical characteristics as well as, product name, serial number
and production date. The identification table (Table 2) helps to crosscheck the Type (first part of the
serial number) with the UPS model.
Figure 1: Type plate of PowerWave 33 Series 3.
Table 2: identification table with dimensions of PowerWave 33 Series 3.
TYPE UPS MODEL
Dimensions w/o
packaging in mm
Dimensions with
std. packaging in
mm
Dimensions w/
wooden box in
mm
PWAxxxx
PowerWave 33 S3 60kW
615 x 1954
1)
x 480
615 x 1978
2)
x 480
615 x 1992
3)
x 480
873x2133x873 884x2182x730
PWAxxxx
PowerWave 33 S3 80kW
PWAxxxx
PowerWave 33 S3 100kW
PWAxxxx
PowerWave 33 S3 120kW
1) without adjustable feet
2) with adjustable feet, adjusted all downwards.
3) with adjustable feet, adjusted all upwards.
Table 3: weight table of PowerWave 33 Series 3.
TYPE UPS MODEL
NET weight in kg
Weight with
standard packaging
in kg
Weight with
wooden box in kg
PWAxxxx
PowerWave 33 S3 60kW
198
219 269
PWAxxxx
PowerWave 33 S3 80kW
206
227 277
PWAxxxx
PowerWave 33 S3 100kW
228
249 299
PWAxxxx
PowerWave 33 S3 120kW
230
251 301
Modifications reserved
Page 9/50
3 Transport – storage – unpacking
3.1 Visual inspection
Upon receiving the goods, make sure that they corresponds to the material indicated in the delivery
note. Carefully examine the packed unit(s) for any sign of physical damage. Two TiltWatch indicators
(see Figure 2) are placed on two sides of the packed unit, in a well visible position. They should both be
intact and not red color. If tipping has occurred the white arrow becomes red, like shown on the Figure
2 below.
In case of damaged unit(s) or even only suspect of damaged (TiltWatch is red) inform immediately:
The carrier
The manufacturer
IMPORTANT
NOTES!
VISIBLE TRANSPORT DAMAGES MUST BE CLAIMED TO THE CARRIER
IMMEDIATELY AFTER RECEIPT.
OTHER CLAIM FOR SHIPPING DAMAGE MUST BE FILED ALSO
IMMEDIATELY AND THE CARRIER MUST BE INFORMED WITHIN 7 DAYS
OF RECEIPT OF THE EQUIPMENT. THE PACKING MATERIALS SHOULD
BE STORED FOR FURTHER INVESTIGATION.
Figure 2: TiltWatch indicator: left when intact and right when tipping has occurred.
3.2 Storage
The packing of the goods protects it from mechanical and environmental damage. UPS and Battery
cabinets should be store in its original packaging. Make sure that the goods are stored indoor, protected
from water and sunshine in a clean environment.
IMPORTANT
NOTES!
THE RECOMMENDED TEMPERATURE FOR STORAGE OF THE UPS
SYSTEM AND BATTERIES IS BETWEEN +20 °C AND +25°C, HUMIDITY <
95% (NON-CONDENSING).
FOR UPS SYSTEM ONLY THE STOREAGE TEMPERATURE CAN BE
BETWEEN -25 °C AND +70°C, HUMIDITY < 95% (NON-CONDENSING).
BEFORE SWITSIHG ON THE UNIT(S), MAKE SURE THE AMBIENT
TEMPERATURE HAS REACHED THE OPERATION TEMPERATURE RANGE
WHICH IS 0°C - +40°C.
Modifications reserved
Page 10/50
3.3 Unpacking
Prior unpacking make sure that the floor surface is solid and suitable for supporting the weight of all the
equipment. Bring the unit(s) close to the end position and unpack them by removing the packing and
shipping materials as described next.
WARNING!
UPS AND BATTERY CABINETS ARE HEAVY AND TALL. MAKE SURE YOU
ARE ALWAYS WORKING SAFELY BY USING APPROPIRATE TOOLS AND
EQUIPMENT. WHEN MOVING THE UNITS AROUND USING FORKLIFT,
ALWAYS MAKE SURE THE UNITS ARE IN UPRIGHT POSITION AND MOVE
WITH SLOW SPEED AND SLOW ACCELERATIONS.
3.3.1 Standard packaging
Perform the following steps to unpack the UPS equipment from the standard packaging:
1. Remove the plastic film from the UPS, by cutting it where there is the cardboard underneath (on
one edge),
2. Remove the 4x cardboard edges carefully by paying attention that the accessory box placed on
top of the UPS does not fall down. Lower the accessory box with the help of a stool or ladder;
make sure you are safe by doing that. The std. content of the accessory box is: user manual, 2x
painted sockets, screws, 4x feet and keys.
3. Remove the bubble-film by removing the small type pieces by hand.
4. Disassemble the front and back fixing bars (see Figure 3, right inside here below as well as Figure
4 on the next page) by unscrewing 8x M8 hexagonal screws.
5. Mount the 4x adjustable feet (feet are in the accessory box) as shown in Figure 5 on the next page.
6. After having placed the UPS in its final position, disassemble the left and right socket as shown in
Figure 6 on the next page and mount the front and back painted sockets.
7. You may want to keep some packaging materials for later use. Alternatively, in case in makes more
sense to dispose the packing material, it must be disposed in accordance with the applicable laws
in the country where the UPS is installed.
1) 2) 3)
Figure 3: Photographs of PowerWave 33 S3 being unpacked step-by-step.
Modifications reserved
Page 11/50
4)
Figure 4: side view of the lower part of PowerWave 33 S3 with the socket (base).
5)
Figure 5: front view of the lower part of PowerWave 33 S3 showing the adjustable feet.
6)
Figure 6: side view of the lower part of PowerWave 33 S3 showing the socket and its screws.
Modifications reserved
Page 12/50
3.3.2 Optional sea freight packaging (wooden box)
Perform the following steps to unpack the UPS equipment from the sea freight package:
1. Disassemble the wooden box by removing all screws.
2. Remove the plastic film and bag from the UPS, by cutting it without causing damage to the cabinet;
the edges are not protected.
3. Remove the accessories form its location, see Figure 8 on the next page. The std. set of
accessories is: user manual, 2x painted sockets, screws, 4x feet and keys.
4. Tear out the 2x humidity-absorber. One is inside the front part of the UPS: open the door using the
keys and then tear out the absorber. The other one is at the back as shown in Figure 9 (next page)
5. Follow the steps 5) - 7) of the previous section 3.3.1.
1) 2)
Figure 7: Photograph and 3D drawing of PowerWave 33 S3 with sea freight packaging.
Modifications reserved
Page 13/50
3)
Figure 8: Photograph of the accessories zone, PowerWave 33 S3 front bottom.
4)
Figure 9: Photographs showing the 2x humidity-absorber. One on the inside front part of the UPS (left) and another on the
rear (right).
Modifications reserved
Page 14/50
4 Installation and wiring
4.1 Positioning of the UPS and battery cabinet
The UPS is designed for location in a restricted access location only and should be located where:
The relative humidity does not exceed 95% (non-condensing) and the temperature remains always
between 0°C and +40°C. Note: an optimal temperature for the UPS and especially for VRLA
batteries is 20°C- 25°C. The UPS room shall have temperature control (air-cooling)
Any kind of dust or corrosive/explosive gases must be absent
Fire protection standards are respected
The place is vibration free
The floor material should be non-flammable and strong enough to support the heavy load.
Cabling can be performed easily
Available front accessibility of 1m from front of the unit for service or maintenance
Only front access is necessary for service and maintenance
If the UPS will be installed in bayed enclosures, partition walls have to be installed as well
Also the needed clearances to allow proper airflow on the UPS system and to allow proper service and
maintenance shall be respected as reported in the Table 4 below.
Modifications reserved
Page 15/50
Figure 10: Top view and indication of the minimum clearances for UPS + other cabinets in row.
Table 4: minimum clearances for UPS + other cabinets in row.
PowerWave 33 Series 3 Cabinets 60 / 80 / 100 / 120
UPS + battery cabinets
in row.
A
Back clearance for ventilation
(forced air outlet)
0 mm 100mm
4)
B
Front clearance needed to allow
a correct door opening
1000 mm
C
Maximum door opening angle 115°
D
Top Clearance
(Top clearance is only needed if there is no
side clearance)
400 mm
4)
Battery cabinet requires 100mm clearance for natural ventilation. The UPS does not require any back clearance.
Modifications reserved
Page 16/50
4.2 Electrical installation
The electrical installation procedure is described in the following text.
To ensure correct operation of the UPS, the voltage Total Harmonic Distortion (THDu) of the mains shall
not exceed the values according to Standard IEC 61000-2-2. In case of exceeding of the indicated
values, please contact the manufacturer.
The installation inspection and initial start-up of the UPS and extra battery cabinet must be carried out
by a qualified service personnel such as a licensed service engineer from the manufacturer or from an
agent CERTIFIED by the manufacturer.
WARNING!
THE INSTRUCTIONS IN THIS USER MANUAL HAVE TO BE FOLLOWED
ALWAYS IN ORDER TO AVOID INJURIES FROM ELECTRICAL SHOCK.
WARNING!
ALL THE OPERATIONS DESCRIBED IN THIS MANUAL MUST BE
PERFORMED BY CERTIFIED ELECTRICIANS OR BY QUALIFIED INTERNAL
PERSONNEL.
DO NOT OPERATE IF WATER OR MOISTURE IS PRESENT.
BY OPENING OR REMOVING THE UPS COVERS YOU RUN THE RISK OF
EXPOSURE TO DANGEROUS VOLTAGES.
PHYSICAL INJURY OR DEATH MAY FOLLOW, OR DAMAGE MAY OCCUR TO
THE UPS OR THE LOAD EQUIPMENT IF THESE INSTRUCTIONS ARE
IGNORED.
To ensure correct operation of the UPS and its ancillary equipment it is necessary to provide the appropriate
wiring and with fuse protection in accordance with the prescribed local standards or with the local regulations/law.
Alternatively refer to the suggested appropriate wiring and fuse protection in the next subsections 4.3 and 4.4.
The UPS unit has the following power connections:
Rectifier input: three-phase (1-L1, 1-L2, 1-L3)
Bypass input :three-phase (2-L1, 2-L2, 2-L3)
Neutral: (N) The Neutral connection at UPS input (upstream) is mandatory.
Load output : three-phase (3-L1, 3-L2, 3-L3)
Battery: (+) and (-) Note: The battery (-) is at the same potential and is the same connection point as N.
Protective earth (PE)
IMPORTANT
NOTE
INPUT NEUTRAL IS REQUIRED TO OPERATE THE RECTIFIER.
In TN-S Systems, no 4-pole input switches or circuit breakers should be used. If you have
to use a 4-pole switch for another reason, you have to be aware that, when open, the
system - UPS and all downstream equipment - are floating against the PE.
Figure 11: Input neutral
Modifications reserved
Page 17/50
4.3 Block diagram
Figure 12: Block diagram of PowerWave 33 S3. On the left with single input feed configuration and on the right with dual
input feed configuration.
4.4 Wiring
Before proceeding to wire the UPS, make sure that you have read and understood the chapter above
4.2 Electrical installation and make sure that the following is respected:
The cable sections and fuse ratings are respecting the local standards. Alternatively, you can
use the recommended cable sections and fuse rating in the tables 6 and 7, which are according
to (IEC 60950-1).
Table 5: SINGLE INPUT FEED (CABLE LINKS TO ACHIEVE SINGLE INPUT ARE OPTIONAL)
Rated
output
power
Fuse A
Type:gL or
CB
(quantity x A)
Cable A
(quantity x
mm
2
)
Cable D
(quantity x
mm
2
)
Fuse E
Type:gR or
CB
(quantity x A)
Cable E
(quantity x mm
2
)
60 kW
3x100 5x(1x35) 5x(1x35) 2x160 2x(1x50)
80 kW
3x125 5x(1x50) 5x(1x50) 2x200
2x(1x95) @ 42-45 batt. blocks
2x(1x70) @ 46-50 batt. blocks
100
kW
3x160 5x(1x70) 5x(1x70) 2x250
2x(1x120) or 2x(2x50) @ 42-45 batt.
blocks
2x(1x95) @ 46-50 batt. blocks
120
kW
3x200 5x(1x95) 5x(1x95) 2x300
2x(1x150) or 2x(2x50) @ 42-45 batt.
blocks
2x(1x120) or 2x(2x50) @ 46-50 batt.
blocks
Modifications reserved
Page 18/50
Table 6: DUAL INPUT FEED (STANDARD VERSION)
Rated
output
power
Fuse B
Type:gL or
CB
(qty. x A)
Cable B
(qty. x
mm
2
)
Fuse C
Type:gL or
CB
(qty. x A)
Cable C
(qty. x
mm
2
)
Cable D
(qty. x
mm
2
)
Fuse E
Type:
gR or
CB
Cable E
(qty. x mm
2
)
60
kW
3x100 5x35 3x100 5x35 5x35 2x160 2x(1x50)
80
kW
3x125 5x50 3x125 5x50 5x50 2x200
2x(1x95) @ 42-45
batt. blocks
2x(1x70) @ 46-50
batt. blocks
100
kW
3x160 5x70 3x160 5x70 5x70 2x250
2x(1x120) or 2x(2x50)
@ 42-45 batt. blocks
2x(1x95) @ 46-50
batt. blocks
120
kW
3x200 5x95 3x200 5x95 5x95 2x300
2x(1x150) or 2x(2x50)
@ 42-45 batt. blocks
2x(1x120) or 2x(2x50)
@ 46-50 batt. blocks
No mains voltage is present on the wires
All Loads are shut down and disconnected
UPS is shut down and voltage-free (no battery is connected)
Make sure the unit is pre-configured as you need: single input or dual input feed (see Figure 12).
Factory standard is dual input feed, single feed is optional and if ordered with the units it comes
pre-assembled. To convert single feed into dual or vice-versa go to subsection 4.4.1.
All 4x switches (IA1 Maintenance Bypass IA2 Output Isolator IA3 Bypass Input IA4 Rectifier
Input) are in position OFF
Mains voltage (
Input Voltage
) and frequency (
Input Freq.
)
correspond to the values indicated on
the type plate of the UPS. The type plate (Figure 1) is on the inside part of the door in a center
position.
Make sure that the total power of the load is equal or lower than the rated power of the UPS
(
Output power
) indicated on the type plate of the UPS.
PE wiring is performed in accordance with the prescribed IEC Standards or with local regulations;
UPS is connected to the mains through a Low Voltage (LV)-Distribution Board with a separate
mains line (protected with a circuit breaker or fuse) for the UPS.
The wiring must be done in the following order:
1. Connect first the PE wire coming from the LV Distribution Board (mains) to the terminal "PE".
2. Connect the input wires
3-phases + N
coming from the LV Distribution Board (mains). Keep the
phase rotation in clock-wise sense. In case of dual input with 2xN wires, the 2xN have to be at the
same potential, ideally they have to be joined together somewhere upstream the UPS. Dual input
feed with just 1xN is also possible.
3. Connect the output wires
3-phases + N
. N at the output is not mandatory (depends on the type
of load).
4. Connect the battery wires, make sure the polarity (+) and (-) are correct.
Make sure you are using the recommended tightening torque (Table 7) and you are connecting each
wire at the correct terminal, on the unit itself each terminal is labelled, as shown here below in Figure
13.
Modifications reserved
Page 19/50
Figure 13: bottom front view and connection terminals of PW33 S3 60-80-100-120 kW models.
Table 7: connection terminals overview and tightening torque.
PW33 S3
Model
Input
Rectifier
Input
Bypass
Output Batt (+) N / Batt. (-) PE
Tightening
torque (Nm)
60 kW
2xM8 1xM8 1xM8
2xM8
1xM10
5xM8 5xM8
12.3 (M8)
25.1 (M10)
80 kW
2xM8 1xM8 1xM8
2xM8
1xM10
5xM8 5xM8
12.3 (M8)
25.1 (M10)
100 kW
2xM8 1xM8 1xM8
2xM8
1xM10
5xM8 5xM8
12.3 (M8)
25.1 (M10)
120 kW
2xM8 1xM8 1xM8
2xM8
1xM10
5xM8 5xM8
12.3 (M8)
25.1 (M10)
Modifications reserved
Page 20/50
4.4.1 Conversion from single input feed to dual input feed and vice-versa
The Figure 14 below shows the situation with single input feed which is achieved thank to 3x link wires
which are factory mounted in case the unit is ordered with single input feed.
To convert the unit from single into dual input feed
simply remove the 3x link wires which connect
the INPOUT RECTIFIER 1-L1, 1-L2, 1-L3 with the INPUT BYPASS 2-L1, 2-L2, 2-L3. All link wires have
M8 ending.
To convert the unit from dual into single input feed
first you need to have the 3x link wires (for PW33
60-80kW Art. 04-3820) (for PW33 100-120kW Art. 04-3822) then connect the INPOUT RECTIFIER 1-
L1, 1-L2, 1-L3 with the INPUT BYPASS 2-L1, 2-L2, 2-L3. All link wires have M8 ending, apply a
tightening torque of 12.3 Nm.
Link wires
Link wires
Figure 14: Detail of the single input feed configuration.
4.4.2 Installation checklist
All units and accessories have been unpacked properly. Some packaging material has been
kept for future use.
Each unit has been positioned at the planned spot.
The area around the installed UPS system(s) and surrounding devices is clean and dust-free
and respect the recommended clearances.
The PE wire(s) is(are) properly sized, routed and terminated.
All power wire(s) is(are) properly sized, routed and terminated.
Battery cabinet installation instructions have been completed.
Air conditioning equipment is installed and operating properly.
Adequate lighting is provided around all UPS equipment.
Any optional accessories are mounted in their installed location and properly wired.
Summary alarms and/or building alarms are wired appropriately. (OPTIONAL)
Startup and operational checks performed by CERTIFIED service personnel.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63

ABB PowerWave 33 Series 3 User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI