DPA 250 S4
50-250kW
OPERATING MANUAL
DPA 250 S4 UPS
50-250 kW 380/400/415 V IEC
2 DPA 250 S4 50-250 KW OPERATING MANUAL
About this document
File name : 4NWD004098_OPM_ABB_DPA-S4_250_EN_REV-A
UPS model : DPA 250 S4 50-250kW
Date of issue : 11.12.2018
Issued by : Product Marketing
Checked by : R&D
After Sales
Article number : N/A
Document number : 4NWD004098
Revision : A
The following symbols are used in this manual,
the list below describes each symbol.
Document information
Safety symbols and warnings
This symbol in conjunction with the signal word "DANGER" indicates an imminent electrical
hazard. Failure to observe the related safety note may cause personnel injury or death or
equipment damages.
This symbol in conjunction with the signal word "WARNING" indicates a potentially dangerous
situation. Failure to observe the related safety note may cause personnel injury or death or
equipment damages.
This symbol indicates a safety note: “ATTENTION! Hazardous voltage!”
Installation by a certified service engineer only.”
This symbol in conjunction with the signal word "NOTE" indicates operator tips, particularly useful
or important information for the use of the product. This symbol and wording does not indicate a
dangerous situation.
This symbol indicates a compulsory action: “Reading the instruction manual/booklet before
starting work or before operating equipment or machinery.
Recycle.
Do not dispose with ordinary trash.
3CONTENTS
Contents
1 Important safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.1 Save these instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.2 Safety rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.1 Declaration of safety compliance and EC marking . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.2 System nameplate and identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.3 UPS module nameplate and identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3 System description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.1 DPA 250 S4 UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.1.1 DPA 250 S4 UPS Frame types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
3.1.2 UPS Frame with closed door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.1.3 DPA 250 S4 UPS Frame with open door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1.4 General UPS Frame dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2 DPA 250 S4 M50 UPS Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
3.2.1 UPS Module dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.3 System configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.3.1 Standalone configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.3.2 Parallel system configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.3.3 Parallel UPS configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
3.4 Description of the main elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.4.1 Single line diagram with single input feed and common batteries (default) . . . . . . . . . . 20
3.4.2 Single line diagram with dual input feed and common batteries . . . . . . . . . . . . . . . . . 21
3.4.3 Single Line Diagram with single input feed and separate batteries . . . . . . . . . . . . . . . .22
3.4.4 Single line diagram with dual input feed and separate batteries . . . . . . . . . . . . . . . . . 23
3.4.5 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
3.4.6 UPS measure, control & monitoring element description . . . . . . . . . . . . . . . . . . . . . . 26
4 Operating modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.1 Double conversion mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.2 Xtra-VFI Mode (Enhanced double conversion mode). . . . . . . . . . . . . . . . . . . . . . . . . 28
4.3 Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.4 Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.5 Maintenance bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5 Control & monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.1 System display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
5.1.1 Graphical display operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
5.1.2 Rear View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.1.3 Start up and installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
5.1.4 Home screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.1.4.1 Icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.1.5 Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.1.5.1 Mimic diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.1.5.2 Module selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.1.5.3 Screen measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.1.5.4 Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.1.5.5 UPS Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
5.1.5.6 User . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.1.5.7 X-tra VFI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.2 Control panel UPS module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2.1 Control panel elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2.1.1 LCD display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2.1.2 ON/OFF power button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2.1.3 Control and navigation buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
5.2.1.4 LED status indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
5.2.2 Control panel menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4 DPA 250 S4 50-250 KW OPERATING MANUAL
5.2.2.1 Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
5.2.2.2 Events log Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.2.2.3 Measurements Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.2.2.4 Commands Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.2.2.5 UPS Data Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
5.2.2.6 Set Up User Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.2.2.7 Set up Service Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
5.3 Customer interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.3.1 Input dry ports (X3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
5.3.2 Output dry port (X2 and X1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
5.3.3 Network management cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
5.3.4 Smart port JD1 (Serial RS 232 / Sub D9 / Male) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
5.3.5 USB PC / Laptop Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
6 Options and accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
7 Maintenance & troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.1 General maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.1.1 User responsibilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.1.2 Preventive maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.1.3 Deep battery test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.1.4 Battery maintenance, disposal and recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
7.2 UPS disposal and recycling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7.2.1 For professional users in the European Union . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7.2.2 For disposal in countries outside of the European Union . . . . . . . . . . . . . . . . . . . . . . 49
7.3 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7.3.1 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7.3.2 Menu, commands, event log and measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7.3.3 Fault identification and rectification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
8 Packing, transportation & storage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
8.1 Packing & transportation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
8.2 Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
8.2.1 Standard package (film) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
8.2.2 Sea freight cases (wooden box) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
8.3 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
8.3.1 UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
8.3.2 Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
9 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
9.1 Environmental condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
9.1.1 Climatic conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
9.1.2 Biological conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
9.1.3 Mechanical active substance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
9.1.4 Chemical active substance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
9.1.5 Mechanical conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
9.2 UPS location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
9.2.1 Battery cabinet location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
9.2.2 Fixing of the UPS to the building structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
9.3 Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
9.3.1 Single input feed - Terminals overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
9.3.2 Dual input feed - Terminals overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
9.3.3 Electrical protection and cable sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
9.3.3.1 Single input feed and common battery (default) . . . . . . . . . . . . . . . . . . . . . .66
9.3.3.2 Single input feed and separate battery . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
9.3.3.3 Dual input feed and common battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
9.3.3.4 Dual input feed and separate battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
9.4 UPS connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
5
9.4.1 UPS Input connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
9.4.1.1 Mains supply and earth connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
9.4.1.2 Single input feed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
9.4.1.3 Dual input feed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
9.4.2 Output connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
9.4.2.1 Load connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
9.5 Parallel UPS connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.5.1 Input & output connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
9.5.2 Communication connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.5.3 Interface set-up and configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
10 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78
10.1 Start-up procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
10.1.1 UPS parallel installation situation
10.1.2 UPS input phase rotation check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
10.1.3 Module installation and parameters check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
10.1.4 Q1 and Q2 feed-back check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
10.1.5 Modules check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
10.1.6 Start-up procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
10.1.7 Battery connection and check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
10.1.8 Connecting the load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
11 Shut-down procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .84
11.1 Complete shut-down procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
12 Maintenance bypass operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
12.1 Load transfer from inverter mode to maintenance bypass . . . . . . . . . . . . . . . . . . . . . 86
12.2 Load transfer from maintenance bypass to inverter mode . . . . . . . . . . . . . . . . . . . . . 88
13 Adding/replacing a UPS module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
13.1 Single module system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
13.1.1 Remove the module from the frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90
13.1.2 Insert the module in the frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92
13.2 Redundant multi-module system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
13.2.1 Remove the module from the frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
13.2.2 Insert the module in the frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
13.3 Capacity multi-module system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
13.3.1 Remove the module from the frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
13.3.2 Insert the module in the frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98
14 Operation procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
14.1 Remote shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
14.2 Generator ON facility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .102
14.3 Xtra VFI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .103
14.3.1 Set-up mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
14.3.2 Display menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
15 Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
15.1 Network interface card (SNMP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .107
15.1.1 CS121 basic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
15.1.2 CS121 advanced . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
15.1.3 CS121 modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
15.1.4 Installation of the SNMP board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
15.2 Elevation kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
15.3 Battery temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
15.3.1 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .111
15.3.2 Battery temperature probe installation. . . . . . . . . . . . . . . . . . . . . . . . . . . .111
Attachments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Technical data sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112
© Copyright 2018 ABB, All rights reserved.
DPA 250 S4
50-250kW
SAFETY INSTRUCTIONS
DPA 250 S4 UPS
50-250 kW 380/400/415 V IEC
8 DPA 250 S4 50-250 KW OPERATING MANUAL
1 Important safety instructions
This manual contains important instructions for
models DPA 250 S4 that should be followed
during installation and maintenance of the UPS.
It also provides guidelines to check delivery and
is in- tended for people who plan the installation,
installation, commission and use or service the
UPS system and/or the battery cabinet. The
reader is expected to know the fundamentals of
electricity, wiring, electrical components and
electrical schematic symbols.
READ ALL SAFETY AND OPERATING
INSTRUCTIONS BEFORE OPERATING THE
UPS SYSTEM. OBSERVE TO ALL WARNINGS
ON THE UNIT AND IN THIS MANUAL
DANGER
SERVICING THE UNIT SHOULD BE
PERFORMED OR SUPERVISED BY
PERSONNEL KNOWLEDGEABLE ABOUT
BATTERIES AND REQUIRED PRECAUTIONS.
RISK OF ELECTRIC SHOCK - THIS UNIT
RECEIVES POWER FROM MORE THAN
ONE SOURCE - DISCONNECTION OF AC
SOURCE(S) (AND THE DC SOURCE) IS
REQUIRED TO DE-ENERGIZE THIS UNIT
BEFORE SERVICING
THERE IS DANGER OF AN ELECTRICAL
IMPACT.
RISK OF EXPLOSION IF USING AN
INCORRECT BATTERY TYPE.
DO NOT EXCEED UPS AND/OR BATTERY
CABINETS RATING LABELS.
AS THE BATTERY LIFE DEPENDS ON THE
ROOM TEMPERATURE, FOR THE UPS
WITH INTERNAL BATTERY MODULES,
AN ENVIRONMENT WITH A CLIMATE
CONTROLLED SYSTEM IS
RECOMMENDED IN ORDER TO
MAINTAIN THE ROOM TEMPERATURE

1.1 Save these instructions
1.2 Safety rules
The UPS system operates with mains, batteries or
bypass power carrying high currents and volt-
age. The correctly installed UPS system is
grounded to earth and IP 20 rated against electric
shocks and foreign objects when all dead fronts
are in place. Installation and service should be
carried out by the manufacturer’s qualified tech-
nicians or their certified service partners.
COMMISSIONING AND OPERATIONS
INSIDE THE UPS MUST BE CARRIED OUT
BY A CERTIFIED SERVICE ENGINEER OF
THE MANUFACTURER OR BY AN AGENT
CERTIFIED BY THE MANUFACTURER.
BY NOT FULFILLING THIS OBLIGATION,
THE PRODUCT MAY LOSE ITS WARRANTY
WARNING
INSTALLATION SHALL BE IN COMPLIANCE
WITH ALL APPLICABLE NATIONAL, STATE,
AND LOCAL CODES
Follow all operating and user instructions.
WARNING
EAD THE INFORMATION, IN ORDER TO
AVOID DAMAGE TO EQUIPMENT
DANGER
KEEP OUT OF BATTERY POLES WHICH
CONTAIN DANGEROUS DC-VOLTAGES
CAUSING FATAL ACCIDENTS. NOTE:
MANIPULATION ON THE BATTERY SYSTEM
SHOULD ONLY BE DONE BY TRAINED
SERVICE AND MAINTENANCE PERSONNEL
OF THE MANUFACTURER OR HIS CERTIFIED
SERVICE PARTNERS. INAPPROPRIATE
MANIPULATIONS OF THE BATTERIES CAN
CAUSE LIGHTNING SPARKS.
A BATTERY CAN PRESENT A RISK OF
ELECTRICAL SHOCK AND HIGH SHORT
CIRCUIT CURRENT. THE FOLLOWING
PRECAUTIONS SHOULD BE OBSERVED
WHEN WORKING ON BATTERIES:
BEFORE READING THE OPERATING MANUAL, PLEASE CAREFULLY READ THIS CHAPTER ON IMPORTANT
SAFETY INSTRUCTIONS
91 IMPORTANT SAFETY INSTRUCTIONS
DANGER
a. REMOVE WATCHES, RINGS OR OTHER
METAL OBJECTS.
b. USE TOOLS WITH INSULATED
HANDLES.
c. WEAR RUBBER GLOVES AND BOOTS.
d. DO NOT LAY TOOLS OR METAL PARTS
ON TOP OF BATTERIES.
e. DISCONNECT THE CHARGING SOURCE
PRIOR TO CONNECTING OR
DISCONNECTING OF BATTERY
TERMINALS.
f. ESTABLISH IF THE BATTERY IS
INADVERTENTLY GROUNDED. IF
INADVERTENTLY GROUNDED, REMOVE
SOURCE FROM GROUND. CONTACT
WITH ANY PART OF A GROUNDED
BATTERY CAN RESULT IN ELECTRICAL
SHOCK. THE LIKELIHOOD OF SUCH
SHOCK CAN BE REDUCED IF SUCH
GROUNDS ARE REMOVED DURING
INSTALLATION AND MAINTENANCE
(APPLICABLE TO EQUIPMENT AND
REMOTE BATTERY SUPPLIES NOT
HAVING GROUNDED SUPPLY CIRCUIT.
WARNING
THE UNIT IS HEAVY AND MAY TIP DURING
TRANSPORTATION CAUSING SERIOUS
INJURY IF UNPACKING INSTRUCTIONS
ARE NOT CLOSELY FOLLOWED.
The only user operations permitted are:
• Start up and shut down of the UPS system and/
or UPS modules (excluding the commissioning
start up).
• Control of the battery circuit breaker, UPS out-
put switch and Manual Bypass switch.
• Monitoring of the UPS system by the central
graphical display and the UPS Module by the lo-
cal control panel.
• Remote monitoring of the UPS system by SNMP,
Modbus and I/O relays interfaces
The user must follow the precautions and only
perform the operations described. Also in these
measures the operator of the UPS System must
observe the instructions in this manual. Any devi-
ations from the instructions could be dangerous
to the user or cause accidental load loss.
THE MANUFACTURER WILL NOT BE HELD
RESPONSIBLE FOR DAMAGES CAUSED THROUGH
INCORRECT MANIPULATION OF THE UPS SYSTEM.
DANGER
IT IS PROHIBITED TO REMOVE ANY PARTS
FROM THE UPS SYSTEM OR FROM ANY
OPTIONAL PART (E.G. BATTERY CABINET).
THERE IS A DANGER OF ELECTRICAL SHOCK!
DANGER
HIGH FAULT CURRENTS (LEAKAGE
CURRENTS):
BEFORE CONNECTING THE MAINS YOU
MUST ENSURE THAT THERE IS A PROPER
EARTH CONNECTION!
DANGER
THE USER MUST DISPLAY A WARNING
SHIELD ON ALL PRIMARY UPS CIRCUIT
BREAKERS. THE SERVICE PERSONNEL HAS
TO BE INFORMED ABOUT DANGEROUS
VOLTAGES. THE WARNING PANELS MUST
CONTAIN THE FOLLOWING TEXT (OR
SIMILAR): “BEFORE STARTING WITH THE
MAINTENANCE WORK ON THE CIRCUIT
BREAKERS MAKE SURE THE UPS IS
ISOLATED”.
DANGER
ALL THE INPUT/OUTPUT PORTS ARE

MAINTAIN SECURITY WHEN CONNECTING
TO OTHER DEVICES.
© Copyright 2018 ABB, All rights reserved.
DPA 250 S4
50-250kW
USER MANUAL
DPA 250 S4 UPS
50-250 kW 380/400/415 V IEC
12 DPA 250 S4 50-250 KW OPERATING MANUAL
WARNING
THIS IS A PRODUCT FOR INDUSTRIAL
APPLICATION IN THE SECOND
ENVIRONMENT AS DEFINED IN IEC/EN

RESTRICTIONS OR ADDITIONAL
MEASURES MAY BE NEEDED TO PREVENT
DISTURBANCES
The UPS must be installed according to the rec-
ommendations in this manual. To operate the UPS
at peak efficiency, your installation site should
satisfy the environmental parameters outlined in
this manual. Excessive amount of dust in the op-
erating environment of UPS may cause damage or
lead to malfunction. The UPS should be always
protected from the outside weather and sun-
shine. If you intend to operate the system at an al-
titude higher than 1000 meters above sea level,
contact your local sales or service office for im-
portant information about high altitude opera-
tion. The operating environment must meet the
weight, airflow, size and clearance requirements
specified in the technical datasheet.
The basic environmental requirements of the UPS
system are:
Ambient Temperature Range 
Recommended Operating Range 
Maximum Relative Humidity 
The UPS cabinet uses forced air cooling to regu-
late the internal temperature of components. Air
inlets are located at the front of the cabinet, and
outlets at the top of the cabinet. You must allow
clearance on the top of the cabinet for proper air
circulation. Refer to the chapter "9.2 UPS loca-
tion".
2 General information
The product has the EC marking in compliance
with the following European directives:
Low Voltage Directive: 2014/35/EC
EMC Directive: 2004/30/EC
Further ABB UPS systems are in compliance with
following standards:
Product Standards Standards
Safety Standard  
Electromagnetic Compatibility
Standard (EMC)











Performance Standard 
2.1
Declaration of safety compliance and EC marking
The primary function of the ABB UPS covered by
the above standards is to ensure continuity of an
AC power source. The UPS may also be used to
improve the quality of the power source by keep-
ing it within specified characteristics. The UPS
has been developed over a wide range of power
ranges, from 50kW to 1.25MW to satisfy require-
ments for availability and quality of power to vari-
ety of IT equipment and devices.
Furthermore, the ABB manufacturer is certified
successfully in every area according to the model
of the International Standard:
ISO 9001/EN 29001. Certification of the UPS with
the operating performance according to the stan-
dard IEC 62040-3 and VDE 0558 Part 530 is ac-
complished.
13
2.2 System nameplate and identification
The UPS system has a nameplate positioned on the inside of the UPS door. It contains
1 UPS product name and frame type
2 UPS electrical characteristics
3 UPS serial number
4 Production date
5 EC Marking
2.2-1
2.2-1:
System nameplate
2.3 UPS module nameplate and identification
The UPS module has a nameplate positioned on the inside of the UPS module. It contains
1 UPS module name and module type
2 UPS module electrical characteristics
3 UPS module serial number
4 Production date
5 EC Marking
2.3-1
2.3-1: UPS
module nameplate
2 GENERAL INFORMATION
14 DPA 250 S4 50-250 KW OPERATING MANUAL
3 System description
The DPA 250 S4 is a 3 ph transformer less Uninter-
ruptible Power System (UPS). It is a true modular
on-line double conversion UPS with a perfor-
mance qualification code VFI-SS-111 providing
quality power for sensitive equipment.
It is a modular UPS system consisting of:
DPA 250 S4 UPS Frame, max rated power of

Up to 6 x DPA 250 S4 UPS modules, rated
power 50 kW
Bottom/Top cable entry including incoming
/ outgoing and battery terminals
Maintenance bypass switch (optional)
System graphical display (optional)
Parallel kit and cable (5mt) (optional)
Communication interfaces
3.1 DPA 250 S4 UPS
The DPA 250 S4 frame has 6 configuration as
follow:
Description Configuration
Bottom cable entry (BCE)
UPS DPA 250 S4 F250-6 BCE SP
Version with built-in MBS available
UPS frame is equipped with system graphical display, par-

Suitable for parallel system configuration.
UPS DPA 250 S4 F250-6 BCE P
Version with built-in MBS available
UPS frame is equipped with parallel kit and cable, up to 6 x

Suitable for parallel system configuration.
UPS DPA 250 S4 F250-6 BCE S MBS UPS frame is equipped with system graphical display, main-
tenance bypass switch (MBS), up to 6 x UPS Module slots

Suitable for standalone configuration.
Top cable entry (TCE)
UPS DPA 250 S4 F250-6 TCE SP
Version with built-in MBS available
UPS frame is equipped with system graphical display, par-

Suitable for parallel system configuration.
UPS DPA 250 S4 F250-6 TCE P
Version with built-in MBS available
UPS frame is equipped with parallel kit and cable, up to 6 x

Suitable for parallel system configuration.
UPS DPA 250 S4 F250-6 TCE S MBS UPS frame is equipped with system graphical display, main-
tenance bypass switch (MBS), up to 6 x UPS Module slots

Suitable for standalone configuration.
3.1.1 DPA 250 S4 UPS Frame types
1515
3.1.2 UPS Frame with closed door
3 SYSTEM DESCRIPTION
With display, applicable for: Without display, applicable for:
UPS DPA 250 S4 F250-6 BCE SP
UPS DPA 250 S4 F250-6 BCE S MBS
UPS DPA 250 S4 F250-6 TCE SP
UPS DPA 250 S4 F250-6 TCE S MBS
UPS DPA 250 S4 F250-6 BCE P
UPS DPA 250 S4 F250-6 TCE P
16 DPA 250 S4 50-250 KW OPERATING MANUAL
3.1.3 DPA 250 S4 UPS Frame with open door
Bottom cable entry Top cable entry
3.1.4 General UPS Frame dimensions
Model DPA 250 S4
Dimensions (WxHxD) mm 795 x 1978 x 943
17173 SYSTEM DESCRIPTION
The UPS module of the DPA 250 S4 is the core
engine of this modern, high quality UPS. The
module includes all essential parts of a complete
double conversion UPS: Rectifier, inverter,
DC-converter (battery charger), static bypass
switch and back feed protection. Each module
has also its own control logic and small display
3.2 DPA 250 S4 M50 UPS Module
for monitoring and management. This allows for
the modules to be completely independent and
act fully redundant with each other. Decentral-
ized paralleling architecture (DPA) is the most
-
vidual UPS connected in parallel, but in a single
frame.
3.2.1 UPS Module dimensions
Rated power 50kW
Ingress of protection IP20
Weight 66 kg
Dimensions (WxHxD) 706 x 175 x 825
WARNING
DANGER
THE FOLLOWING LABELS ARE PLACED ON THE UPS MODULE:
18 DPA 250 S4 50-250 KW OPERATING MANUAL
3.3 System configuration
3.3.1 Standalone configuration
3.3.2 Parallel system configuration

below, standard configurations are listed and described.
Number of modules
1 x 50 kW 2 x 50 kW 3 x 50 kW 4 x 50 kW 5 x 50 kW 6 x 50 kW
Maximum load
50 kW 100 kW 150 kW 200 kW 250 kW 250 kW
Configuration with maximum load
     
Note: Depending on the actual load level system features automatically redundancy.
The DPA 250 S4 UPS unit can be paralleled to increase the power capacity up to 1500kW. Up to 6 UPS
units with 30 UPS modules can be configured as shown in the table below:
Number of UPS units
1 x 250 kW 2 x 250 kW 3 x 250 kW 4 x 250 kW 5 x 250 kW 6 x 250 kW
Maximum load
250 kW 500 kW 750 kW 1000 kW 1250 kW 1500 kW
Maximum number of UPS Modules
6 12 18 23 29 30
Configuration with maximum load per frame
     
Note: Depending on the actual load level system features automatically redundancy.
19
ONLY PEOPLE WHICH HAVE BEEN
TRAINED BY SERVICE TECHNICIANS OF
THE MANUFACTURER OR HIS CERTIFIED
SERVICE PARTNERS ARE ALLOWED TO
START UP AND COMMISSIONING THE UPS
SYSTEM.
The control and monitoring communication for
the parallel UPS units are secured by using a
ring-bus communication. The ring-bus technique
loops back the parallel communication cable from
the last frame in the system. This introduces an
alternative communication path in case one cable
in between two UPS units is disconnected for
whatever reason.
3.3.3-1
3.3.3-1: Ring
communication for
parallel UPS units
3.3.3 Parallel UPS configuration
The UPS system consisting of parallel UPS units requires:
Master UPS unit equipped with system graphical display, N x UPS modules (N > 0 and < 6) and
parallel cable kit (5 mts).
N parallel UPS unit equipped with parallel cable kit (N < 6)
FRAME 1 FRAME 2 FRAME 5 FRAME 6
System graphical display
Parallel Cable Kit
3 SYSTEM DESCRIPTION
20 DPA 250 S4 50-250 KW OPERATING MANUAL
3.4 Description of the main elements
The UPS has single input feed and common battery connections. These are provided by a common in-
put feed busbar and a common battery busbar.
3.4.1 Single line diagram with single input feed and common batteries (default)
3.4.1-1
3.4.1-1: Single line
diagram with single
input feed and common
batteries (default)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114

ABB DPA 250 S4 Operating instructions

Category
Uninterruptible power supplies (UPSs)
Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI