3.3.2 Spot Testing
Asageneralruleinspottesting,testvoltageshouldbeapplieduntilno
variation in reading is noted for 15 seconds, or applied for a xed 60
seconds.
What minimum value should be measured?
TheIEEEstandardNo.43-1974statesthatitisimpossibletospecifythe
valueofinsulationresistanceatwhichawindingwillfailelectrically,buton
motors,minimumreadingsgenerallystatedare:
Rated Voltage R Minimum
250 or less 2M
Ω
460 2MΩ
Table 4-2
Thereisnoxedgurefordeterminingwhatisgoodandbadinresistance
readings,but agoodguidewouldbe1megohmforevery onehundred
operatingvoltsapplied,asaminimumgure.Thisappliestomotorsand
transformers. When the insulation resistance gets this low, an electri-
calbreakdowncanbeexpectedatanytime,andrewindingorreplacing
shouldbeconsidered.
Itisnotunusualforawindingtobe10to100timestherecommended
minimumvalue(IEEEStd.#43-1974:Recommended Practice for Testing
Insulation Resistance of Rotating Machinery), but this varies with tem-
peratureandhumidity.
3.3.3 Ratio Testing
In timed resistance testing (Dielectric Absorption Ratio), readings are
takenat30and60secondstoobtainthedielectricabsorptionratio.
Insulationresistance@60s
=DielectricAbsorptionRatio(DAR)
Insulationresistance@30s
Thistestisusefultoincreasetheaccuracyofspottesting.Ingeneral,a
ratioof1.25:2orbettershouldberequired.Aratiobelowthisindicatesthat
repairisprobablyneeded.
Remember,aDCinsulationtestmaybeusedforacceptancetesting,but
ismorecommonlyusedtocheckthegradualdeteriorationofequipment
overitslife.Consultyourequipmentmanufacturerforspecictestortest
voltageifnotknown.
Insulationresistancedecreaseswithmoisture,temperatureandageand
shouldberecordedovertimeatagiventemperatureandcorrected.