Eurotherm iX T7 Installation guide

Category
Touch screen monitors
Type
Installation guide

This manual is also suitable for

iXT7B
InstallationManual
English
MAEN095C,2013-09
Foreword
InstallationmanualforiXT7B
Foreword
All operator panels are developed to satisfy the demands of human-machine
communication. Built-in functions such as displ a ying and controlling text,
dynamic indication, time channels, alarm and recipe handling are included.
The operator panel works primarily in an object-oriented way, making it easy to
understand and u se. Configuration is carried out on a PC using the iX Developer
configuration tool. The project can then be transferred and stored in the operator
panel itself.
Various types of automation equipment such P LCs, servos or drives can be
connected to the operator panels. In this manual, the term the controller” refers
to the connected equipment.
This manual explains how to install the operator panel. Please refer to the
iX Developer reference manual for further information.
Order no: MAEN095C
Copyright © 2013-09 Beijer Electronics AB. All rights reserved.
The information in this document is subject to changewithoutnoticeandisprovidedasavailableatthe
time of printing. Beijer Electronics AB, including all its group companies, reserves the right to change any
information without updating this publication. Beijer Electronics AB, including all its group companies,
assumesnoresponsibilityforanyerrorsthatmayappearinthisdocument. Readtheentireinstallation
manual prior to installing and using this equ ipm ent. Only qualified personnel may install, operate o r repair
this equipment. Beijer Electronics AB , including all its group comp anies, are not responsible for modified,
altered or renovated equipment. Because the equipment has a wide range of applications, users must acquire
the appropriate knowledge to use the equipment properly in their specific applications. Persons responsible
for the applic atio n and the equipment must themselves ensure that each application is in compliance with
all relevant requirements, standards and legislationinrespecttocongurationandsafety. Onlypartsand
accessoriesmanufactured according to specifications set by Beijer Electronics AB, including all its group
companies, may be used.
BEIJER ELECTRONICS AB, INCLUDING ALL ITS GROUP
COMPANIES, SHALL NOT BE LIABLE TO ANYONE FOR ANY
DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL
DAMAGES RESULTING FROM THE INSTALLATION, USE OR
REPAIR OF THIS EQUIPMENT, WHETHER ARISING IN TORT,
CONTRACT, OR OTHERWISE. BUYER'S SOLE REMEDY SHALL
BE THE REPAIR, REPLACEMENT, OR REFUND OF PURCHASE
PRICE, AND THE CHOICE OF THE APPLICABLE REMEDY SHALL
BE AT THE SOLE DISCRETION OF BEIJER ELECTRONICS AB,
INCLUDING ALL ITS GROUP COMPANIES.
BeijerElectronics, MAEN095C
Contents
Contents
1 SafetyPrecautions ....................................................... 4
1.1 General ...........................................................
4
1.2 UL and cUL Installation .........................................
4
1.3 DuringInstallation ..............................................
5
1.4 DuringUse .......................................................
6
1.5 Service and Maintenance ........................................
6
1.6 Dismantling and Scrapping .....................................
6
1.7 Appearance of A ir in Touch Screen .............................
6
2 Installation ............................................................... 7
2.1 Space Requirements .............................................
7
2.2 Installation Process ..............................................
8
2.2.1 ConnectionstotheController ..................................
9
2.2.2 OtherConnectionsand Peripherals .............................
10
3 Technical Data ........................................................... 11
4 Chemical Resistance .................................................... 13
4.1 Metal Casing .....................................................
13
4.2 Touch Screen and Overlay .......................................
14
4.2.1 AutoexEBA180L ..............................................
14
4.2.2 Touch ScreenSurface ............................................
15
4.2.3 AutoexEBA180L ..............................................
15
5 Operator PanelDrawings .............................................. 16
5.1 Connectors .......................................................
16
5.2 Communication Ports ...........................................
16
5.3 iX T7B Outline ..................................................
17
6 Additional Installation Tips ............................................ 18
6.1 Grounding the Operator Panel .................................
18
6.2 Ethernet Connection in the Ope
rator Panel ...................
19
6.3 To Achieve Better EMC Protec
tion .............................
21
6.4 AmbientTemperature ...........................................
22
6.5 Safety .............................................................
23
6.6 Galvanic Isolation ................................................
24
6.7 Cable and Bus Terminati
onRS485 .............................
25
BeijerElectronics, MAEN095C
Safety Precautions
1SafetyPrecautions
Both the in staller and the owner and/or operator of the operator panel must read
and understand this installation manual.
1.1 General
Read the safety precautions carefully.
Check the delivery for transportation damage. If damage is found, notify the
supplier as soon as possible.
Do not use the operator panel in an environment with high explosive hazards.
The supplier is not responsible for modified, altered or reconstructed
equipment.
Use only parts and accessories manufactured according to specifications of
the supplier.
Read the installation and operating instructions carefully before installing,
using or repairing the operator panel.
Neverallowfluids,metalfilingsorwiringdebristoenteranyopeningsinthe
operator panel. This may cause fire or electrical shock.
Only qualified personnel may operate the operator panel.
Storing the operator panel where the temperature is lower/higher th an
recommended in this manual can cause the LCD display liquid to
congeal/become isotopic.
The LCD display liquid c ontains a powerful irritant. In case of skin contact,
wash immediately with plenty of water. In case of eye contact, hold the eye
open,flushwithplentyofwaterandgetmedicalattention.
Thefiguresinthismanualservesanillustrativepurpose. Becauseofthemany
variables associated with any particular installation, the supplier cannot
assume responsibility for actual use based on the figures.
The supplier neither guarantees that the operator panel is suitable for your
particular application, nor assumes responsibility for your product design,
installation or operation.
It is recommended to turn on and shut down the operator panel at least once
before installing any components/cards or bef ore connecting the operator
panel to external devices, like for example serial devices.
1.2 ULandcULInstallation
This equipment is suitable for use in Class 2 non-hazardous locations only.
[Combinations of equipment in your system are subject to investigation by
the local authority having jurisdiction at the time of installation].
All devices have to be supplied by a Class 2 power supply.
Warning:
Donotdisconnectequipmentunlesspowerhasbeenremovedortheareais
knowntobenon-hazardous
BeijerElectronics, MAEN095C
4
Safety Precautions
For Canada also AVERTISSEME NT AVANT DE DECONNECTER
L’EQUIPEMENT, COUPER LE COURANT OUS’ASSURER QUE
L‘EMPLACEMENT EST DESIGNE NON DANGEREUX.
Warning:
OnlyULandcULapprovedexpansionunitsareallowedt obeconnectedto
theportdesignated“EXPANSION”. Atthemomenttherearenosuchunits
evaluatedorallowed.
Warning:
Donotreplaceexpansionunitunlesspowerhasbeenswitchedofforthearea
isknowntobenon-hazardous.
This product contains a battery; this must only be changed in an area known
to be non-hazardous.
Replace the battery with a BR 2032 battery. Use of another type of battery
may present a risk of fire or explosion.
Warning:
Batterymayexplodeifmistreated. Donotrecharge,d
isassembleordispose
ofinre.
For use on a flat surface of a type 4X enclosure indoor use only.
Use 75 degree conductors only
Use copper conductors only
To make wiring connections to the power supply connector, follow the table
with cable and torque specifications below:
TerminalBlockNo. WireSizeAWG TQLb.In.
X1/X100Phoenixconnectors AWG30–12 5–7
X1/X100Anytekconnectors AWG24–12 3.5
ThesedevicesareClass2suppliedprogrammablecontrollers(industrialPCs)
for the use in indus trial control equipment and are intended to be ( front)
panel mounted (Type 1 and 4x for indoor use only).
1.3 DuringInstallation
The operator panel is designed for stationary installation on a plane surface,
where the following conditions are fulfilled:
no high explosive risks
no strong magnetic fields
no direct sunlight
no large, sudden temperature changes
Install the product according to the accompanying instal lation instructions.
Ground the product according to the accompanying installation instru ctions.
Only qualified personnel may install the operator panel.
BeijerElectronics, MAEN095C
5
Safety Precautions
Separate the high voltage, signal and supply cables.
Make sure that the voltage and polarity of the power source i s correct before
connecting the product to the power outlet.
Peripheral equipment must be appropriate for the application and location.
1.4 DuringUse
Keep the operator panel clean.
Emergency stop and other safety functions may not be controlled from the
operator panel.
Do not use too much force or sharp objects when touching the keys,
touchscreen etc.
1.5 ServiceandMaintenance
Only qualified personne l should carry out repairs.
The agreed warranty applies.
Before carrying out any cleaning or maintenance operations, disconnect the
equipment from the electrical supply.
Clean the display and surrounding front cover with a soft cloth and mild
detergent.
Replacing the battery incorrectly may result in explosion. Only use batteries
recommended by the supplier. During the warranty period, the battery needs
to be replaced by an authorized Beijer Electronics service center.
1.6 DismantlingandScrapping
The operator panel or parts thereof shall b
e recycled according to local
regulations.
The following components contain s
ubstances that might be hazardous
to health and the environment: lit
hium battery, electrolytic capacitor and
display.
1.7 AppearanceofAirinTouchScreen
Thelayerstructureofthetouchscreencontainsairandinrarecases
appearance of bubbles can arise. This is purely cosmetic and does no t affect
any functionality of the panel. The appearance can occur under certain
environmental conditions such as temperature, humidity, and atmospheric
pressure.
BeijerElectronics, MAEN095C
6
Installation
2Installation
2.1 SpaceRequirements
Maximum installation plate thickness: 11 mm
Space requirements in millimeters when installing the operator panel:
143
204
50 mm
100 mm
100 mm
50 mm
100 mm
Note:
Thedimensionsonthedrawin
ga renotproportional.
BeijerElectronics, MAEN095C
7
Installation
2.2 InstallationProcess
The following is needed:
A Phillips/slot screwdriver
1.
Unpack and check the delivery. If damage is found, notify the supplier.
Note:
Placetheoperatorpanelonastablesurfaceduringinstallation.
Droppingthepanelorlettingitfallmaycausedamage.
2.
Usethecutoutdimensionsthatareincludedontheoutlinedrawing,found
in section Operator Panel Drawings and in the Technical Data table, to cut
a correct opening in the cabinet. A separate cut out drawing is available for
download from the Beijer Electronics web site.
3.
Secure the operator panel in position using all the fastening holes and the
provided brackets and screws:
x 4 0.5 - 1.0 Nm
BeijerElectronics, MAEN095C
8
Installation
4.
Connect the cables in the specified order, according to the drawing and steps
below.
Caution:
Ensurethattheoperatorpanelandthecontrollersystemhavethesameelectrical
grounding(referencevoltagelevel),otherwiseerrorsincom municationmay
occur.
Theoperatorpanelmustbebroughttoambienttemperaturebeforeitisstarted
up. Ifcondensationforms,ensurethattheoperatorpanelisdrybeforeconnecting
ittothepoweroutlet.
Ensurethatthevoltageandpolarityofthepowersourceiscorrect.
Useonlyshieldedcommunicationcables.
Separatehighvoltagecablesfromsignalandsupplycables.
24V DC
RS232/
RS422/
RS485
24V DC
A
D
Controller
Power
B
Ethernet
C
Connect cable A.
Connect cable B, using an M5 screw and a grounding conductor (as short
as possible) with a cross-section of minimum 2.5 mm
2
.
Connect cable C.
Connect cable D. The recommended cross-section of the cable is
1.5 mm
2
.
5.
Carefully remove the laminated film over the operator panel display, to avoid
static electricity that could damage the panel.
2.2.1 Connectionstot
heController
For information about the cables to be used when connecting the operator panel to
the controller, please refer to the help file for the driver in question.
BeijerElectronics, MAEN095C
9
Installation
2.2.2 OtherConnectionsandPeripherals
Cables, peripheral equipment and accessories must be suitable for the application
and its environment. For further details or recommendations, please refer to the
supplier.
BeijerElectronics, MAEN095C
10
Technical Data
3TechnicalData
Parameter iX T7B
Frontpanel,W×H×D 204×143×7mm
Cutoutdimensions,
W×H
187×126mm
Mountingdepth 43mm(143mmincludingclearance)
Standalonemounting VESA75×75
Note: MaximumscrewlengthforVESAmountingis4mm.
Usageoflongerscrewsmayleadtodamage.
Frontpanelseal IP65
Rearpanelseal IP20
Touchscreen
material
Polyesteronglass,resistive.
Overlay: AutoexEBA180L
(1)
.
Touchscreen
operations
1millionngertouchoperations
Reverseside
material
Powder-coated aluminum
Framematerial Powder-coatedaluminum
Weight 1.010kg
Serialportfor
COM1RS232and
COM2RS422/RS485
9-pinD-subcontactwithRS232RTS/CTS,chassis-mounted
femalewithstanda rdlockingscrews4-40UNC
Serialportfor
COM3RS232and
COM4RS422/RS485
9-pinD-subcontactwithRS232RTS/CTS,chassis-mounted
femalewithstanda rdlockingscrews4-40UNC
Ethernet 1×10/100/1000Mbit/sand1×10/100Mbit/s. Shielded
RJ45
USB 3×USBHost2.0,maxoutputc urre nt500mA
Processor Intel®Atom
Externalstorage
media
1×SDcard(optional). OnlycompatiblewiththestandardSD
formatwithupto2GBstoragecapacity.
MemoryRAM 1GB
LED 1×multi-color
Realtimeclock Yes(onchip)
Battery LithiumbatterytypeBR2032(orCR2032),exchangeable
Powerconsumption
atratedvoltage
14W
Fuse 3.15ASlow
Powersupply +24VDC(18-32VDC)
CE:Thepowersupplymustconformwiththerequirements
accordingtoIEC60950andIEC61558-2-4.
ULandcUL:Thepowersupplymustconformwiththe
requirementsforclassIIpowersupplies.
Display TFT-LCDwithLEDbacklight. 800×480pixels,262kcolors
Activeareaof
display,W×H
152.4×91.4mm
BeijerElectronics, MAEN095C
11
Technical Data
Parameter iX T7B
Operating
temperature
-10°C+50°C
Storagetemperature -20°C+70°C
Relativehumidity 5%85%non-condensed
Approvalsand
certications
Informationisavailableonthewebsite
www.beijerelectronics.com
(1)
SeesectionChemicalResistanceformoreinformation.
BeijerElectronics, MAEN095C
12
Chemical Resistance
4 ChemicalResistance
4.1 MetalCasing
The frame and casing material is powder-coated aluminum. This powder paint
withstands exposure to the following chemicals without visible change:
Aceticacid10% Phosphoricacid4%
Citricacid10% Phosphoricacid10%
Diesel Seawater
Distilledw ater Sodiumchloride2%
Edibleoil Sodiumchloride20%
Fueloil Sulphuricacid20%
Hydrogenperoxide3% Tapwater
The powder paint shows limited resistance to the f
ollowing chemicals at room
temperature:
Butanol Nitricacid3%
Hydrochloricacid5% Nitricacid10%
Isopropylalcohol Phosp horicacid43%
Na-hypochlorite10% Turpentine
Note:
Ifexposuretoanyoftheabovechemicalsisdemanded,itisrecommendedtorsttest
thechemicalinahiddenspotofthemetalcasing.
Thepowderpaintshowslittleornoresistancetothefollowingchemicalsatroom
temperature:
Aceticacid,conc. Methyl-ethylketone Toluene
Acetone Nitricacid30% Trichlorethylene
Ammonia5% Phenol Xylene
Ammonia,conc. Sodiumhydroxide5% 97octaneunleadedpetrol
Ethylacetate Sodiumhydroxide30% 98octanele a dedpetrol
BeijerElectronics, MAEN095C
13
Chemical Resistance
4.2 TouchScreenandOverlay
4.2.1 AutoexEBA180L
Autoflex EBA 180L covers the overlay surrounding the touch screen.
SolventResistance
Autoflex EBA 180L withstands exposure of more than 24 hours duration under
DIN42115Part2tothefollowingchemicalswithoutvisiblechange:
Acetonitrile DieselDowney/Lenor
(1)
Phosphoricacid(<30%)
Ajax/Viminsolution Ethanol Potassiumferricyanide
Alkalicarbonate
solution
(1)
Glycerine Potassiumhydroxide(<30%)
Ammonia(<40%)
(1)
Glycol PureTurpentine
Aceticacid(<50%) Gumption
(1)
SBP60/95
(1)
Arielpowderin
solution
(1)
Hydrochloricacid(<36%) Sulfuricacid(<10%)
Bleach
(1)
Linseedoil Tomatoketchup
Castoroil Methanol Trichloroaceticacid(<50%)
Causticsoda(<40%)
(1)
Nitricacid(<10%) WhiteSpirit
Cuttingoil Parafnoil Windex
(1)
Cyclohexanol Persilpowderin
solution
(1)
Wisk
Diacetonealcohol Petroleumspirit
(1)
-
(1)
Extremelyf
aintglossingofthetexturewasnoted.
Autoflex EBA 180L withstands DIN 42 115 Part 2 exposure of up to 1 hour
duration to glacial acetic acid without visible change.
Autoflex EBA 180L is not resistant to high pressure steam at over 100 °C or the
following chemicals:
Concent
ratedmineralacids
Benzyla
lcohol
Conce
ntratedcausticsolution
Methy
lenechloride
BeijerElectronics, MAEN095C
14
Chemical Resistance
4.2.2 TouchScreenSurface
The touch screen surface on the operator panel withstands exposure to the
following solvents without visible chan ge:
Solvents Time
Acetone 10minutes
Isopropanol 10minutes
Toluene 5 hours
4.2.3 AutoexEBA180L
It is recommended to use the Autoflex EBA 180Ltouch display protection film,
that can be ordered from Beijer Electronics.
SolventResistance
Autoflex EBA 180L withstands exposure tothesamechemicalsasAutotexF157or
F207 according to section Autoflex EBA 180L.
OutdoorUse
In common with all polyester based fi lms, Autoflex EBA 180L is not suitable for
use in conditions of long-term exposure to direct sunlight.
BeijerElectronics, MAEN095C
15
Operator Panel Drawings
5 Opera torPanelDrawings
5.1 Connectors
1234567
Pos. Connector Description
1 Powersupply +24VDC(18-32VDC)
2 COM1/2 CommunicationPorts
3 LAN(Port2) 1×10/100Base-T(shieldedRJ-45)
4 USB 2×USBHost2.0,maxoutputcurrent500mA
5 Headphone HeadphoneConnector
6 LAN(Port1) 1×10/100/1000Base-T(shieldedRJ-45)
7 COM3/4 CommunicationPorts
5.2 CommunicationPorts
Serialport,9-pinfemale Serialport,9-pinfemale
Pin
COM1 COM2 COM3 COM4
1-
RS422Tx +
RS485Tx+/Rx+
-
RS422Tx+
RS485Tx+/Rx+
2 RS232RxD - RS232RxD -
3 RS232TxD - RS232TxD -
4 - RS422Rx+ - RS422Rx+
5 GND GND GND GND
6-
RS422Tx-
RS485Tx-/Rx-
-
RS422Tx-
RS485Tx-/Rx-
7 RS232RTS - - RS422RTS+
8 RS232CTS - - RS422RTS-
9 - RS422Rx- - RS422Rx-
Note:
Inordertoutilizetwocommunicationportsonthesamephysicalport,theY-splitcable
CAB109mustbeused.
DrawingforexternalcableC AB109(drawing#Z7100-029E)isavailableonthewebsite:
www.beijerelectronics.com
BeijerElectronics, MAEN095C
16
Operator Panel Drawings
5.3 iXT7BOutline
126 99
43
max. 11 mm
7
143
187
204
99
Note:
AStepCADleisavailableonthewebsitewww.beijerelectronics.com
BeijerElectronics, MAEN095C
17
Additional Installation Tips
6 AdditionalInstallationTips
When experiencing communication problems in for example noisy environments
or when operating close to temperature limits, the following recommendations
are to be noticed.
6.1 GroundingtheOperatorPanel
1
2
3
4
5
6
5350
Door
Operator panel
Ferrite core
Mounting plate in the cabinet
Power supply
24 V DC
The operator panel’s mounting clamps do not provide a secure grounding
connection between the panel and the device cabinet, see 1 in drawing above.
1.
Connect a 2.5 mm
2
wire between the operator panel’s quick-connect plinth
and the panel’s chassis, see 2 in drawing above.
2.
Connect a 6 mm
2
or 4 mm
2
wire or grounding braid between the operator
panel’s chassis and the closest grounding point on the door, see 3 in drawing
above.
3.
Connect a strong but short grounding braid between the door and the device
cabinet,see 4 in drawing above.
4.
Twist th e cables onto the 24 V
DC feed, see 5 in drawing above. Minimum
cross-section of the cable
is 2.5 mm
2
.
2 turns around the ferrite core provide 4 times the suppression of 1 turn.
3 turns around the ferrite
core provide 9 times the suppression of 1 turn.
A ferrite core suppresses disturbances to the 24 V feed, see 6 in drawing above.
BeijerElectronics, MAEN095C
18
Additional Installation Tips
Note:
Thegroundingwiresshouldbeshortandtheconductorshouldhavealargearea.
Along,thingroundingwirehasaveryhighimpedance(resistance)athighfrequencies
andwillnotguidedisturbancestotheground.
Multi-wireconductorsarebetterthansinglewireconductorswiththesamearea.
Abraidedconductorwirewiththesameareaisevenbetter. Thebestisashort,thick
groundingbraid.
6.2 EthernetConnectioninthe
OperatorPanel
1
2
3
4
5
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
Industrial Ethernet
Operator panel
Operator panel
Operator panel
Operator panel
Shielded
Short and
unshielded
0.1 μF
250 V
1-1
3-3
8-8
2-2
In some industri al units for Ethernet, the RJ45 contact’s shield is connected to the
chassis via a capacitor, s ee 1 in drawing above.
The operator panel’s Ethernet shield is directly connected to the chassis, see 2 in
drawing above.
1.
Check whether the other Ethernet unit has its shi eld directly grounded or
grounded via a capacitor.
Note:
Inmanycases,connectingtheshieldedEthernetcablingtothechassisatbothendsis
inappropriate. Humo rgroundingloopscanoccur. Unshield edcablingmayevenresult
infewercommunicationerrors.
BeijerElectronics, MAEN095C
19
Additional Installation Tips
A good solution may be to use a shielded Ethernet cable, but to co nnect the shield
at one end only.
One option is to break the shield, see 3 in drawing above.
A more elegant method is to expand the shielded Ethernet cabling with a piece of
unshielded Ethernet cable, see 4 in drawing above.
The shield can be grounded via an external 0.1 μF/250 V plastic capacitor, see 5 in
drawing above. This will c onnect the HF transients to ground.
BeijerElectronics, MAEN095C
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26

Eurotherm iX T7 Installation guide

Category
Touch screen monitors
Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI