Kit No.
Cable Insulation
O. D. Range
15 kV
5681
5682
5683
0.84 – 1.38 in.
(21 – 35
mm)
1.08 – 1.80 in.
(27 – 46
mm)
1.31 – 2.10 in.
(33 – 53
mm)
15 to 34.5 kV Kit Selection Chart
NOTE: Final determining factor is cable insulation diameter.
Conductor Size Range (AWG & kcmil)
5684
25/28 kV
0.637 – 1.12 in.
(16 – 28
mm)
34.5 kV
Table 1
#1 – 4/0
(50 – 100)
4/0 – 500
(100 – 250)
500 – 1250
(250 – 625)
#4 – 2/0
(22 – 60)
1/0 – 350
(50 – 185)
350 – 750
(185 – 400)
750 – 1500
(400 – 800)
#4 – 4/0
(22 – 100)
250 – 500
(120 – 250)
500 – 1250
(250 – 625)
1000 – 1750
(500 – 850)
Instructions
ISSUE DATE:
7/1/91
I
SSUE:
SCALE:
Not to scale
5681
5682
Silicone Rubber Termination Kits
for use on Concentric Neutral (CN) Cable
3M Quick Term II
2047MT–56
Concentric Neutral Cable
5683
5684
Quick Term II
Silicone Rubber Termination
(with High-K Stress Relief)
IEEE Std. No. 48–1990
Class 1 Termination
25 kV Class
150 kV BIL
Kit Contents
1 Hi–K Silicone Rubber Termination
2 Scotch 70 Silicone Rubber Tape Strip(s)
1 Neutral Wire Ground Clip
1 Pack of Silicone Grease
1 Instruction Sheet
2
Ridge at End of Cable Insulation Shield (Semi-Con)
Ridge at End of High-K Tube
Binding Wire
or Vinyl Tape
Semi-Con Insulation Shield
Cable Insulation
Conductor
High-K Stress Relief
Correct Installation of Termination
A. Prepare Cable
1. Check to be sure cable size fits within kit range as shown in
Table 1 (cover page).
2. Train cable into position and cut to length required for installation.
Allow sufficient neutral wire length for neutral connection.
3. Bind neutral wires with a piece of wire or vinyl tape at dimension
[A] + [B] Table 2.
1
(See * below)
4. Bend the neutral wires over the binding wire or vinyl tape.
2
5. Remove cable semi-conductive insulation shield (semi-con) for a
distance of [C] plus [B] Table 2.
3
(See * below)
6. Remove cable insulation
4
from end of conductor for
distance [B] Table 2.
5
7. Place a marker tape 2 back from semi-con cut edge as shown.
6
* add 1 to [A] and [C] for short lug barrels (1 or less).
Depth of
Terminal
Lug Barrel
Kit No.
5681
11
3
/
4
(298 mm)
[B]
Table 2
[A] *
8
1
/
4
(216 mm)
[C] *
5682
11
3
/
4
(298 mm)
8
1
/
4
(216 mm)
5683
12
1
/
4
(311 mm)
9
(229 mm)
5684
12
1
/
4
(311 mm)
9
(229 mm)
Dimension
[C]
[A] [B]
Semi-Con Insulation Shield
2
DO NOT LOOP NEUTRAL WIRES BEYOND MARKER TAPE
Marker Tape
Cable Insulation
Conductor
Binding Wire
or Vinyl Tape
Neutral Wire
1
5
4
6
3
2
3
B. Install Lug or Connector
1. These units were designed to fit over Scotchlok and 3M copper and aluminum lugs. If other lugs
1
will not fit
through the core of the termination, slide termination on cable before installing lug. Do not remove core at this time.
1
2. When using 3M type lugs or connectors, refer to the tooling index (Pages 5 and 6) for crimping information.
3. Position lug or connector and crimp according to manufacturers directions. Remove excess contact aid and sharp
crimp flash.
C. Clean Cable Insulation and Lug Barrel Using Standard Practice
1. Wipe the cable insulation with an approved solvent. Do not allow solvent to touch semi-con insulation shield!
2. If abrasive must be used:
a. Use on insulation only. Do not use abrasive on semi-con insulation shield!
b. Use only aluminum oxide abrasive; grit 120 or finer or Scotch A–3 Electrician’s Abrasive Roll.
c. Be careful not to reduce the cable insulation diameter below that allowed by the kit.
D. Install Termination
1. Important: A track resistant seal must be made between the silicone termination insulator and connector using one of
two gray Scotch 70 Silicone Rubber Electrical Tape Strips (contained in kit).
1
If the lug barrel is smaller than the cable insulation, wrap the bottom end of the lug with gray silicone tape to the
approximate diameter of the cable insulation.
1
2. Cover the edge of the semi-con insulation shield with a liberal coating of silicone grease.
2
On this product the
silicone grease does not serve as a lubricant. It must be used to fill the step at the semi-con cutoff.
IMPORTANT
Do Not Forget
Silicone Grease
2
Silicone Grease Gray Silicone Tape
1
4
Install Termination (continued)
3. Slide the termination body onto the cable and remove core by unwinding, counter-clockwise,
3
starting with the loose
end. Make sure the termination body is butted up to the edge of the marker tape.
4
Tip: An occasional tug of the
strand while unwinding will aid in core removal.
3
4
Marker Tape
Gray Silicone Tape
4. Complete the lug seal using the second gray silicone tape strip. Overlap
insulator by one inch and extend tape wrapping onto lug barrel as shown.
5
E. Grounding
1. Snap stainless steel grounding clip onto base of termination.
1
Clip must be applied to the base of the termination,
between the bottom two rings
2. Loop one neutral strand around ground clip ends, pulling clip tight onto the termination.
2
3. Bundle all neutral wires together and connect to ground.
3
1
Stainless Steel Grounding Clip
2
3
5
Gray Silicone Tape
5
76(2)
76(2)
Thomas & Betts
Corporation
Square D Co.
Anderson Div.
Cable
Size
AWG/
kcmil
Stud
Size
(in.)
Scotchlok
Lug Number
CRIMPING TOOL-DIE SETS (NO. OF CRIMPS)
MD6 MY29 Y34A
Y35, 39,
45*, 46*
TBM 5 TBM 8 TBM 15
VC6–3**
VC6–FT**
Burndy Corporation
40016
40028
40029
40037
40137
40041
40141
40045
40046
40145
40049
40050
40149
40053
40153
40056
40057
40156
40160
40067
40166
6
1
2/0
3/0
4/0
250
300
350
400
500
5
/
16
3
/
8
1
/
2
1
/
2
5
/
8
1
/
2
1
/
2
5
/
8
1
/
2
1
/
2
5
/
8
1
/
2
1
/
2
1
/
2
1
/
2
5
/
8
1
/
2
W161(1)
W163(3)
W163(3)
BG(4)
BG(4)
W166(4)
W166(4)
W249(3)
W249(3)
W249(3)
6 AWG(1)
1 AWG(1)
1 AWG(1)
3/0(1)
3/0(1)
4/0(2)
4/0(2)
4/0(2)
A6CAB(1)
A1CAR(1)
A1CAR(1)
A30AR(2)
A30AR(2)
U32ART(4)
U6CABT(1)
U1CART(1)
U1CART(1)
U30ART(2)
U30ART(2)
Grey(1)
Gold(2)
Gold(2)
Olive(2)
Olive(2)
Ruby(2)
Ruby(2)
White(4)
White(4)
White(4)
66(4)
66(4)
66(4)
60(2)
60(2)
54H(2)
54H(2)
45(1)
45(1)
Lug and Crimping Information for
Scotchlok Copper/Aluminum Lugs
40016 thru 40079
One hole
40132 thru 40178
Two hole
40170600
1
/
2
U36ART(4) 115H(3)
750
1000
**
Y1000
(1)
Grey(1)
TBM 12
29(1)
VC8C**
ITT Black-
burn Co.
OD58
Kearne
Nat’l Div.
TYPE 0
J(3)BY19(3)(1)
400204
5
/
16
W162(3) 4 AWG(1) A4CAB(1) U4CABT(1) Green(2)(1) 37(1) P(3)BY53(3)(1)Green(2)
40024
40025
2
3
/
8
1
/
2
W163(3)
W163(3)
A2CAB(1)
A2CAB(1)
U2CABT(1)
U2CABT(1)
Pink(2)
Pink(2)
42H(2)
42H(2)
2 AWG(1)
2 AWG(1)
(1)
(1)
Pink(2)
Pink(2)
(1)
(1)
1
/
2
(3)
1
/
2
(3)
BY23(3)
BY23(3)
(1)
(1)
Gold(2)
Gold(2)
(1)
(1)
BY23(3)
BY23(3)
1
/
2
(3)
1
/
2
(3)
40032
40033
40132
1/0
3
/
8
1
/
2
3
/
8
W241(3)
W241(3)
W241(3)
1/0 (1)
1/0 (1)
1/0 (1)
A25AR(1)
A25AR(1)
A25AR(1)
U25ART(1)
U25ART(1)
U25ART(1)
Tan(2)
Tan(2)
Tan(2)
50(1)
50(1)
50(1)
(1)
(1)
(1)
(1)
(1)
(1)
BY25(3)
BY25(3)
BY25(3)
5
/
8
–1(3)
5
/
8
–1(3)
5
/
8
–1(3)
Tan(2)
Tan(2)
Tan(2)
1
/
2
1
/
2
2/0(1)
2/0(1)
A26AR(2)
A26AR(2)
U26ART(2)
U26ART(2)
(1)
(1)
Olive(2)
Olive(2)
(2)
(2)
5
/
8
–1(3)
5
/
8
–1(3)
BY31C(3)
BY31C(3)
1
/
2
1
/
2
A27AR(2)
A27AR(2)
U27ART(2)
U27ART(2)
(1)
(1)
Ruby(2)
Ruby(2)
(2)
(2)
737(3)
737(3)
W660(4)
W660(4)
W660(4)
A28AR(2)
A28AR(2)
A28AR(2)
U28ART(2)
U28ART(2)
U28ART(2)
(1)
(1)
(1)
(2)
(2)
(2)
BY35C(4)
BY35C(4)
BY35C(4)
840(4)
840(4)
840(4)
A29AR(2)
A29AR(2)
A29AR(2)
U29ART(2)
U29ART(2)
U29ART(2)
(1)
(1)
(1)
71H(4)
71H(4)
71H(4)
71H(2)
71H(2)
71H(2)
(3)
(3)
(3)
(1)
(1)
76H(4)
76H(4)
(3)
(3)
U31ART(2)
U31ART(2)
U31ART(2)
(1)
(1)
(1)
87H(4)
87H(4)
87H(4)
87H(3)
87H(3)
87H(3)
(3)
(3)
(3)
(1) 94H(4) 94H(4) (2)
U34ART(4)
U34ART(4)
(1)
(1)
106H(4)
106H(4)
106H(3)
106H(3)
(2)
(2)
(1) (3)
5
/
8
1
/
2
40073
40172
U39ART(4)
U39ART(4)
125H(5)
125H(5)
(3)
(3)
5
/
8
1
/
2
40079
40178
S44ART(4)
S44ART(4)
(1)
(1)
(1)
(1)
140H(4)
140H(4)
(3)
(3)
* Y45 and Y46 accept all Y35 dies (“U” series). For Y45 use PT6515 adapter. For Y46 use PUADP adapter.
** Anderson VC6–3, VC6–FT, VC8C and Burndy Y1000 require no die set.
Crimping Information for
3M Stem Connectors
Copper/Aluminum
CRIMPING TABLE FOR 3M STEM TYPE CONNECTOR
Recommended Crimping Tools
Conductor
Size
3M
Connector No.
Manufacturer Mech. Tool Die (No. Crimps) Hydraulic Tool Die (No. Crimps)
Burndy
Kearny
T & B
Anderson
Burndy
Kearny
T & B
Anderson
TBM 8
TBM 8
0–51, 0–52
0–51, 0–52
MD6
MD6 BG(4), W243(4)
5/8–1(4)
Olive(2)
W669(0) 840(5)*
840(5)*
White(4)
VC 6
TBM 15
WH–1, WH–2
Y35, Y39, Y45**
VC 6
TBM 15
12, 20, 40, Ton
Y35, Y39, Y45** U25ART(2), U243(2)
5/8–1(4)
50*(2)
Universal(2)
U28ART(2)
840(2)
66(3)
Universal(2)
#2 Sol.
#1, #2
1/0
SC0002
SC0001
SC0010
SC0020
SC0030
SC0040
2/0
3/0
4/0
Tooling Index
IMPORTANT NOTICE TO PURCHASER:
All statements, technical information and
recommendations related to the Seller’s
products are based on information believed to
be reliable, but the accuracy or completeness
thereof is is not guaranteed. Before utilizing the
product, the user should determine the
suitability of the product for its intended use.
The user assumes all risks and liability
whatsoever in connection with such use.
All statements or recommendations of the seller
which are not contained in the Seller’s current
publications shall have no force or effect unless
contained in an agreement signed by an
authorized officer of the Seller. The statements
contained herein are made in lieu of all
warranties express or implied, including but not
limited to the implied warranties of
merchantability and fitness for a particular
purpose which warranties are hereby expressly
disclaimed.
SELLER SHALL NOT BE LIABLE TO THE
USER OR ANY OTHER PERSON UNDER ANY
LEGAL THEORY, INCLUDING BUT NOT
LIMITED TO NEGLIGENCE OR STRICT
LIABILITY, FOR ANY INJURY OR FOR ANY
DIRECT OR CONSEQUENTIAL DAMAGES
SUSTAINED OR INCURRED BY REASON OF
THE USE OF ANY OF THE SELLER’S
PRODUCTS.
3M Electrical Products Division
34–7030–6658–8
6801 River Place Blvd.
Austin, Texas 78726–9000
3M 1991
Thomas & Betts
Corporation
Square D Co.
Anderson Div.
Cable
Size
AWG/
kcmil
Stud
Size
(in.)
Scotchlok
Copper Lug
Number
CRIMPING TOOL-DIE SETS (NO. OF CRIMPS)
MD6 MY29 Y34A
Y35, Y39 Y45*,
Y46*
TBM 5 TBM 8 TBM 15
VC6–3,
VC6–FT**
Burndy Corporation
30014
30015
30016
30018
30019
30021
30022
30023
30024
30027
30028
30031
30032
30036
31036
30041
31041
30045
31045
31145
31049
31149
31053
31153
31056
31156
31060
31160
31066
31067
31166
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
10
1
/
4
5
/
16
10
1
/
4
3
/
8
1
/
4
5
/
16
3
/
8
5
/
16
3
/
8
5
/
16
3
/
8
3
/
8
3
/
8
1
/
2
1
/
2
1
/
2
1
/
2
1
/
2
1
/
2
1
/
2
1
/
2
1
/
2
1
/
2
1
/
2
1
/
2
5
/
8
1
/
2
W161(1)
W162(2)
W163(2)
W241(2)
W241(3)
W243(2)
W243(3)
BG(3)
BG(4)
BG(4)
W166(4)
6 AWG(1)
4 AWG(1)
2 AWG(1)
1 AWG(1)
1/0(1)
2/0(1)
2/0(2)
3/0(1)
3/0(2)
4/0(1)
4/0(2)
4/0(2)
250(2)
——
A4CR(1)
A2CR(1)
A1CR(1)
A25R(1)
A26R(1)
A26R(2)
A27R(1)
A27R(2)
A29R(2)
A30R(2)
A31R(2)
A32R(2)
A34R(2)
U5CRT(1)
U4CRT(1)
U2CRT(2)
U1CRT(2)
U25RT(1)
U26RT(2)
U26RT(3)
U27RT(2)
U27RT(3)
U28RT(2)
U28RT(3)
U28RT(3)
U29RT(3)
U30RT(3)
U31RT(3)
U32RT(3)
U34RT(3)
Blue(1)
Grey(1)
Brown(1)
Green(1)
Pink(2)
Black(2)
Black(3)
Orange(2)
Orange(3)
Purple(2)
Purple(3)
Purple(3)
Yellow(2)
Blue(1)
Grey(1)
Brown(1)
Green(1)
Pink(2)
Purple(2)
Purple(3)
Purple(3)
Yellow(2)
White(3)
Red(4)
Blue(4)
Brown(4) 87H(4)
76H(4)
71H(4)
66(3)
62(2)
54H(2)
54H(3)
54H(3)
50(1)
50(2)
45(1)
45(2)
42H(2)
37(1)
33(1)
Universal(1)
Universal(1)
Universal(2)
Universal(2)
Universal(1)
Universal(1)
Universal(2)
Universal(2)
Universal(3)
Universal(2)
Universal(3)
Universal(3)
Universal(2)
Universal(3)
Lug and Crimping Information for
Scotchlok Copper Lugs
30014 thru 30045
One hole
31036 thru 31068
One hole —
long barrel
Tooling Index
31145 thru 31178
Two hole
Black(2)
Black(3)
1
/
2
1
/
2
Orange(2)
Orange(3)
A28R(2)
31068
31168
600
1
/
2
1
/
2
U36RT(3) Green(4) 94H(4)
31172750
1
/
2
106H(4)
Y39, Y45, Y46:
U39RT(5)
311781000
1
/
2
125H(4)
Y45: S44RT(6)
Y46: P44RT(6)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6