YOKOGAWA DPharp EJA120E Installation guide

Type
Installation guide

This manual is also suitable for

Users
Manual
Contents
1. Introduction
1.1 For Safe Use of Product ..............................................2
1.2 Warranty ......................................................................4
1.3 ATEX Documentation ..................................................5
2. Handling Cautions
2.1 ModelandSpecicationsCheck .................................7
2.2 SelectingtheInstallationLocation ..............................7
2.3 PressureConnection ..................................................7
2.4 InstallationofanExplosion-ProtectedInstrument ......7
2.5 EMCConformityStandards ..................................... 27
2.6 Pressure Equipment Directive (PED) ...................... 28
2.7 Safety Requirement Standards ................................ 29
3. Installation
3.1 Mounting................................................................... 30
3.2
MountingtheDiaphragmSeals ......................................30
3.3 DiaphragmSealsInstallationConsideration ............ 31
3.4 MountingtheFlushingConnectionRing .................. 32
3.5 AfxingtheTeonFilm ............................................. 33
3.6 Rotating Transmitter Section .................................... 34
3.7 ChangingtheDirectionofIntegralIndicator............. 34
4. Installing Impulse Piping
4.1 ImpulsePipingInstallationPrecautions ................... 35
4.2 ImpulsePipingConnectionExamples ..................... 37
4.3 ProcessPipingInstallationPrecautions(EJ115) 38
5. Wiring
5.1 Wiring Precautions ................................................... 40
5.2 ConnectionsofExternalWiringtoTerminalBox ...... 40
5.3 Wiring ....................................................................... 43
5.4 RTDCableConnection(EJX910A/EJX930A) ......... 45
5.5 Grounding ................................................................ 47
5.6 PowerSupplyVoltageandLoadResistance ........... 47
6. Operation
6.1 Preparation for Starting Operation ........................... 48
6.2 Zero Point Adjustment .............................................. 48
6.3 LocalParameterSetting .......................................... 49
7. Errors and Countermeasures
EJX and EJA-E Series
Differential Pressure and
Pressure Transmitters
Installation Manual
IM01C25A01-01E
IM01C25A01-01E
12thEdition
<1. Introduction> 1
IM01C25A01-01E
12thEdition:Feb.2017(YK)
AllRightsReserved,Copyright©2009,YokogawaElectricCorporation
1. Introduction
Thisinstallationmanualprovidesthebasicguidelines
forinstallationandwiringproceduresoftheDPharpEJX
seriesandEJA-EseriestransmitterswithBRAINand
HARTprotocolsandiscomposedoftheinformation
extractedfromtheproductusersmanualsaslistedin
Table1.1.Itdoesnotprovidetheinformationincluding
wiringproceduresofthetransmitterswithFOUNDATION
Fieldbus,ProbusandModbusprotocols,product
specicfunctionalspecicationsandexplanations,
operation,maintenanceandtrouble-shooting.
ForEJXC40ADigitalRemoteSensor,asthisInstallation
Manualdoesnotcovertheproduct,pleaserefertothe
dedicatedmanualforEJXC40A.
WARNING
Toensurecorrectandsafeuseoftheinstrument,
obtainthemanualsapplicabletodesignatedmodels
andspecicationsaslistedTable1.1,readthem
thoroughlyandfullyunderstandhowtooperatethe
instrumentbeforeoperatingit.
Users’manualforeachproductconsistsofahardware
manualdescribinginstallation,wiring,operation,
maintenanceandspecicationincludingdetailedmodel
andsufxcodeinformation,andacommunication
manualdescribinginformationspecictoeach
communicationprotocoltype,includingsafetymanualfor
safety instrumented system.
Thesemanualscanbedownloadedfromthewebsite
ofYokogawaorpurchasedfromtheYokogawa
representatives.
Websiteaddress:http://www.yokogawa.com/d/
Table 1.1 PDF Manual List and Applicable Style Code
[EJX series Hardware Manual]
Models Document No. Style
EJX110A
IM01C25B01-01E
S3
EJX120A S1
EJX130A,EJX310A,EJX430A
andEJX440A S2
EJX210A IM01C25C01-01E S2
EJX510AandEJX530A IM01C25F01-01E S2
EJX610AandEJX630A S1
EJX118AandEJX438A IM01C25H01-01E S2
EJX115A IM01C25K01-01E S1
EJX910A IM01C25R01-01E S2
EJX930A S1
EJXC80AandEJXC50A IM01C25W01-01EN
EJXC40A IM01C25W05-01EN
[EJX series Communication Manual]
Models Document No. Style
DPharpHART5/HART7
CommunicationType IM01C25T01-06EN
DPharpFOUNDATIONFieldbus
CommunicationType IM01C25T02-01E
DPharpBRAINCommunication
Type IM01C25T03-01E
DPharpPROFIBUSPA
CommunicationType IM01C25T04-01EN
EJX910AandEJX930AHART
CommunicationType IM01C25R02-01E
EJX910AandEJX930A
FieldbusCommunicationType IM01C25R03-01E
EJX910AandEJX930AModbus
CommunicationType IM01C25R05-01E
[EJA-E series Hardware Manual]
Models Document No. Style
EJA110E,EJA120E
IM01C25B01-01E S1
EJA130E,EJA310E,EJA430E
andEJA440E
EJA210E IM01C25C01-01E S1
EJA510EandEJA530E IM01C25F01-01E S1
EJA118EandEJA438E IM01C25H01-01E S1
EJA115E IM01C25K01-01E S1
EJAC80EandEJAC50E IM01C25W01-01EN
[EJA-E series Communication Manual]
Models Document No. Style
DPharpHART5/HART7
CommunicationType IM01C25T01-06EN
DPharpFOUNDATIONFieldbus
CommunicationType IM01C25T02-01E
DPharpBRAINCommunication
Type IM01C25T03-01E
DPharpPROFIBUSPA
CommunicationType IM01C25T04-01EN
Note:AnexclusiveUser’sManualmightbeattachedforthe
productswhosesufxcodesoroptionalcodescontain
code“Z”.Pleasereaditalongwiththestandardmanuals.
<1. Introduction> 2
IM01C25A01-01E
Regarding This Manual
• Thismanualshouldbepassedontotheenduser.
• Thecontentsofthismanualaresubjecttochange
withoutpriornotice.
• Allrightsreserved.Nopartofthismanualmaybe
reproducedinanyformwithoutYokogawa’swritten
permission.
• Yokogawamakesnowarrantyofanykindwithregard
tothismanual,including,butnotlimitedto,implied
warrantyofmerchantabilityandtnessforaparticular
purpose.
• Ifanyquestionarisesorerrorsarefound,orifany
informationismissingfromthismanual,pleaseinform
thenearestYokogawasalesofce.
• Thespecicationscoveredbythismanualarelimited
tothoseforthestandardtypeunderthespecied
modelnumberbreak-downanddonotcovercustom-
made instruments.
• Pleasenotethatchangesinthespecications,
construction,orcomponentpartsoftheinstrument
maynotimmediatelybereectedinthismanualat
thetimeofchange,providedthatpostponementof
revisionswillnotcausedifcultytotheuserfroma
functional or performance standpoint.
• Yokogawaassumesnoresponsibilitiesforthis
productexceptasstatedinthewarranty.
• Ifthecustomeroranythirdpartyisharmedbytheuse
ofthisproduct,Yokogawaassumesnoresponsibility
foranysuchharmowingtoanydefectsintheproduct
whichwerenotpredictable,orforanyindirect
damages.
• WhendescribingthemodelnamelikeEJ110
inthismanual,itshowstheapplicabilityforboth
EJX110AandEJA110E.Thesamerepresentations
areusedfortheothermodels,too.
• Thefollowingsafetysymbolmarksareusedinthis
manual:
WARNING
Indicatesapotentiallyhazardoussituationwhich,ifnot
avoided,couldresultindeathorseriousinjury.
CAUTION
Indicatesapotentiallyhazardoussituationwhich,ifnot
avoided,mayresultinminorormoderateinjury.Itmay
alsobeusedtoalertagainstunsafepractices.
IMPORTANT
Indicatesthatoperatingthehardwareorsoftwarein
thismannermaydamageitorleadtosystemfailure.
NOTE
Draws attention to information essential for
understandingtheoperationandfeatures.
Direct current
Functional grounding terminal
 Caution
Thissymbolindicatesthattheoperatormust
refertoanexplanationintheuser’smanual
inordertoavoidtheriskofinjuryordeathof
personnelordamagetotheinstrument.
1.1 For Safe Use of Product
Fortheprotectionandsafetyoftheoperatorandthe
instrumentorthesystemincludingtheinstrument,please
besuretofollowtheinstructionsonsafetydescribed
inthismanualwhenhandlingthisinstrument.Incase
theinstrumentishandledincontradictiontothese
instructions,Yokogawadoesnotguaranteesafety.
Pleasegiveyourattentiontothefollowings.
(a) Installation
WARNING
• Theinstrumentmustbeinstalledbyanexpert
engineeroraskilledpersonnel.Theprocedures
describedaboutINSTALLATIONarenotpermitted
for operators.
• Incaseofhighprocesstemperature,careshould
betakennottoburnyourselfbecausethesurface
ofbodyandcasereachesahightemperature.
• Theinstrumentinstalledintheprocessisunder
pressure.Neverloosentheprocessconnector
boltstoavoidthedangerousspoutingofprocess
uid.
• Duringdrainingcondensatefromthepressure
detectorsection,takeappropriatecaretoavoid
contactwiththeskin,eyesorbody,orinhalation
ofvapors,iftheaccumulatedprocessuidmaybe
toxicorotherwiseharmful.
• Whenremovingtheinstrumentfromhazardous
processes,avoidcontactwiththeuidandthe
interiorofthemeter.
• Allinstallationshallcomplywithlocalinstallation
requirement and local electrical code.
<1. Introduction> 3
IM01C25A01-01E
(b) Wiring
WARNING
• Theinstrumentmustbeinstalledbyanexpert
engineeroraskilledpersonnel.Theprocedures
describedaboutWIRINGarenotpermittedfor
operators.
• Pleaseconrmthatvoltagesbetweenthepower
supplyandtheinstrumentbeforeconnectingthe
powercablesandthatthecablesarenotpowered
beforeconnecting.
(c) Operation
WARNING
• Wait5min.afterpoweristurnedoff,before
openingthecovers.
• Donotopenthecoverinwetweatherorhumid
environment.Ifthecoverisopened,stated
enclosureprotectionisnotapplicable.
(d) Maintenance
WARNING
• Pleasedonotcarryoutexceptbeingwritten
tomaintenancedescriptions.Whenthese
proceduresareneeded,pleasecontactnearest
YOKOGAWAofce.
• Careshouldbetakentopreventthebuildupof
drift,dustorothermaterialonthedisplayglass
andnameplate.Incaseofitsmaintenance,soft
anddryclothisused.
(e) Explosion Protected Type Instrument
WARNING
• Usersofexplosionproofinstrumentsshouldrefer
rsttosection2.4(InstallationofanExplosion
ProtectedInstrument)ofthismanual.
• ForTIISameprooftypeinstruments,besure
toread“INSTALLATIONANDOPERATING
PRECAUTIONSFORTIISFLAMEPROOF
EQUIPMENT”attheendofthismanual.
• Theuseofthisinstrumentisrestrictedtothose
whohavereceivedappropriatetraininginthe
device.
• Takecarenottocreatesparkswhenaccessingthe
instrumentorperipheraldevicesinahazardous
location.
(f) Modication
WARNING
• Yokogawawillnotbeliableformalfunctionsor
damageresultingfromanymodicationmadeto
thisinstrumentbythecustomer.
(g) Product Disposal
Theinstrumentshouldbedisposedofinaccordancewith
localandnationallegislation/regulations.
(h) Authorized Representative in EEA
InrelationtotheCEMarking,Theauthorized
representativeforthisproductintheEEA(European
EconomicArea)is:
YokogawaEuropeB.V.
Euroweg2,3825HDAmersfoort,TheNetherlands
<1. Introduction> 4
IM01C25A01-01E
(i) Control of Pollution Caused by the Product
Thisisanexplanationfortheproductbasedon“ControlofPollutioncausedbyElectronicInformation
Products”inthePeople’sRepublicofChina.TheinformationisvalidonlyinChina.
产品中有
EJX/
E
EJA/EJ
A
差压/压
FV
X
现场总线
○:表
×:表
环保使用
害物质或元
J
-E/
A
-A Series
力变送器
X
110
段指示器
示该部件的
示至少该部
期限:
该标识
注)该
的名称及
部件名
壳体
膜盒组
基板组
电源连接
线
壳体
基板组
电源连接
线
有均质材
的某些均
适用于 SJ /
T
年数为“环
(P
×
×
×
线
×
×
×
线
×
中的有害物
材料中的有
T
11364 中所
使用期限”
b
(H
g
×
×
×
×
×
×
×
质的含量均
害物质的含
在中华人
,并非产品
g
(Cd
GB/T26572
均在 GB/T2
6
民共和国销
的质量保证
害物质
六价
(Cr(VI
)
×
×
标准中所规
6
572 标准中
的电子电
)
多溴联
(PBB)
定的限量以
所规定的限
产品的环保
使
多溴二苯
(PBDE
以上。
使
用期限。
1.2 Warranty
• Thewarrantyshallcovertheperiodnotedonthe
quotationpresentedtothepurchaseratthetimeof
purchase.Problemsoccurredduringthewarranty
periodshallbasicallyberepairedfreeofcharge.
• Incaseofproblems,thecustomershouldcontactthe
Yokogawarepresentativefromwhichtheinstrument
waspurchased,orthenearestYokogawaofce.
• Ifaproblemariseswiththisinstrument,pleaseinform
usofthenatureoftheproblemandthecircumstances
underwhichitdeveloped,includingthemodel
specicationandserialnumber.Anydiagrams,
dataandotherinformationyoucanincludeinyour
communicationwillalsobehelpful.
• Responsiblepartyforrepaircostfortheproblems
shallbedeterminedbyYokogawabasedonour
investigation.
• ThePurchasershallbeartheresponsibilityfor
repaircosts,evenduringthewarrantyperiod,ifthe
malfunctionisdueto:
- Improperand/orinadequatemaintenancebythe
purchaser.
- Failureordamageduetoimproperhandling,use
orstoragewhichisoutofdesignconditions.
- Useoftheproductinquestioninalocation
notconformingtothestandardsspeciedby
Yokogawa,orduetoimpropermaintenanceofthe
installation location.
- Failureordamageduetomodicationorrepair
byanypartyexceptYokogawaoranapproved
representativeofYokogawa.
- Malfunctionordamagefromimproperrelocationof
theproductinquestionafterdelivery.
- Reasonofforcemajeuresuchasres,
earthquakes,storms/oods,thunder/lightening,
orothernaturaldisasters,ordisturbances,riots,
warfare,orradioactivecontamination.
Trademarks:
• ‘DPharp’,‘EJX’,‘EJA’,‘FieldMateand‘BRAIN
TERMINALareregisteredtrademarksofYokogawa
ElectricCorporation.Companynamesandproduct
namesusedinthismaterialareregisteredtrademarks
ortrademarksoftheirrespectiveowners.
• Inthismanual,trademarksorregisteredtrademarks
arenotmarkedwith™or®.
<1. Introduction> 5
IM01C25A01-01E
1.3 ATEX Documentation
ThisisonlyapplicabletothecountriesinEuropeanUnion.
GB
DK
I
E
NL
SF
P
F
D
S
LT
LV
PL
EST
SLO
H
BG
RO
M
CZ
SK
GR
<2. Handling Cautions> 6
IM01C25A01-01E
2. Handling Cautions
Whenthetransmitterisdelivered,visuallycheckthem
tomakesurethatnodamageoccurredduringshipment.
Alsocheckthatalltransmittermountinghardwareshown
inFigure2.1isincluded.Ifthetransmitterwasordered
withoutthemountingbracketorwithouttheprocess
connector,thetransmittermountinghardwareisnot
included.
Table 2.1 Applicable Model Code for Mounting
Hardware
Applicable
model Sufxcode Part name Qty
EJ110
EJ120
EJ130
EJX910A
EJX930A
Process
connections
1,2,3and4
Processconnectorbolt 4
Process connector 2
Process connector
gasket 2
EJ210
EJ310
EJ430
EJ440
Process
connections
1,2,3and4
Processconnectorbolt 2
Process connector 1
Process connector
gasket 1
EJ110
EJ120
EJ130
EJ310
EJ430
EJ440
EJ118
EJ438
EJ115
EJX910A
EJX930A
Mountingbracket
B,D,G,J,Kand
M *
U-bolt 1
U-boltnut 2
Mountingbracket
(Lorattype) 1
Transmitter mounting
bolt 4
EJ110
Mounting
bracketM(For
measurement
spancodeother
thanF)
U-bolt 1
U-boltnut 2
Mountingbracket 1
Transmitter mounting
bolt 2
EJ510
EJ530
EJX610A
EJX630A
Mountingbracket
FandL
U-bolt(LandS) 1 ea.
U-boltnut(LandS) 2 ea.
Mountingbracket 1
EJX910A
EJX930A
External
temperature input
B,CandD RTDcable 1
External
temperature input
1,2,3and4 Cablegland 2
EJ210
EJ438Optioncode/TF1 Teonlm 1
Fluorinated oil 1
EJ118Optioncode/TF1 Teonlm 2
Fluorinated oil 2
*: FormeasurementspancodeF.
EJX910A
EJX930A - 
1
2
3
4
1
2
3
4
B
C
D
- 
B
D
G
J
K
M
EJ110
EJ120
EJ130
EJ310
EJ430
EJ440
- 
1
2
3
4
- 
B
D
G
J
K
M
-  -  B
J
EJ210
1
2
3
4
-  - 
EJ510
EJ530
EJX610A
EJX630A
EJ118
EJ438
F
L
-  - 
F0201.ai
B
D
J
K
EJ115 -  - 
Mounting bracket
(Flat type)
F0202.ai
Teflon film
Fluorinated oil
Bolt
Process connector
Process connector
Gasket
U-bolt nut
U-bolt
Mounting bracket
(L type)
Transmitter mounting bolt
Cable gland and RTD cable
(EJX910A and EJX930A only)
U-bolt nut (L)
Mounting bracket
U-bolt (L)
U-bolt (S)
U-bolt nut (S)
Figure 2.1 Transmitter Mounting Hardware
<2. Handling Cautions> 7
IM01C25A01-01E
2.1 ModelandSpecications
Check
Themodelnameandspecicationsareindicatedonthe
nameplateattachedtothecase.
F0203.ai
Figure 2.2 Name Plate
2.2 Selecting the Installation
Location
Thetransmitterisdesignedtowithstandsevere
environmentalconditions.However,toensurethatitwill
provideyearsofstableandaccurateperformance,take
thefollowingprecautionswhenselectingtheinstallation
location.
(a)AmbientTemperature
Avoidlocationssubjecttowidetemperaturevariations
orasignicanttemperaturegradient.Ifthelocationis
exposedtoradiantheatfromplantequipment,provide
adequatethermalinsulationand/orventilation.
(b)AmbientAtmosphere
 Donotinstallthetransmitterinacorrosive
atmosphere.Ifthiscannotbeavoided,theremustbe
adequate ventilation as well as measures to prevent
theleakingofrainwaterandthepresenceofstanding
waterintheconduits.
(c)ShockandVibration
 Althoughthetransmitterisdesignedtoberelatively
resistanttoshockandvibration,aninstallationsite
shouldbeselectedwherethisiskepttoaminimum.
(d)InstallationofExplosion-protectedTransmitters
 Anexplosion-protectedtransmittersiscertiedfor
installationinahazardousareacontainingspecic
gastypes.Seesubsection2.4“Installationofan
Explosion-ProtectedInstrument.
2.3 Pressure Connection
WARNING
• Neverloosentheprocessconnectorboltswhenan
instrumentisinstalledinaprocess.Thedeviceis
underpressure,andalossofsealcanresultina
suddenanduncontrolledreleaseofprocessuid.
• Whendrainingtoxicprocessuidsthathave
condensedinsidethepressuredetector,take
appropriatestepstopreventthecontactofsuch
uidswiththeskinoreyesandtheinhalationof
vaporsfromtheseuids.
Thefollowingprecautionsmustbeobservedinorderto
safelyoperatethetransmitterunderpressure.
(a)Makesurethattheprocessconnectorboltsare
tightenedrmly.
(b)Makesurethattherearenoleaksintheimpulse
piping.
(c) Neverapplyapressurehigherthanthespecied
maximumworkingpressure.
2.4 Installation of an Explosion-
Protected Instrument
Ifacustomermakesarepairormodicationtoan
intrinsicallysafeorexplosionproofinstrumentandthe
instrumentisnotrestoredtoitsoriginalcondition,its
intrinsicallysafeorexplosionproofconstructionmaybe
compromisedandtheinstrumentmaybehazardousto
operate.PleasecontactYokogawabeforemakingany
repairormodicationtoaninstrument.
CAUTION
Thisinstrumenthasbeentestedandcertiedas
beingintrinsicallysafeorexplosionproof.Please
notethatsevererestrictionsapplytothisinstruments
construction,installation,externalwiring,maintenance
andrepair.Afailuretoabidebytheserestrictionscould
maketheinstrumentahazardtooperate.
WARNING
Maintainingthesafetyofexplosionproofequipment
requiresgreatcareduringmounting,wiring,and
piping. Safety requirements also place restrictions on
maintenanceandrepair.Pleasereadthefollowing
sections very carefully.
<2. Handling Cautions> 8
IM01C25A01-01E
WARNING
Therangesettingswitchmustnotbeusedina
hazardousarea.
IMPORTANT
Forcombinedapprovaltypes
Onceadeviceofmultipleapprovaltypeisinstalled,
itshouldnotbere-installedusinganyotherapproval
types.Applyapermanentmarkinthecheckboxof
theselectedapprovaltypeonthecerticationlabelon
thetransmittertodistinguishitfromunusedapproval
types.
2.4.1 FM Approval
a. FM Intrinsically Safe/Nonincendive for
HART/BRAIN Protocol Type (Except for
EJX90A)
Note1. EJX/EJA-ESeriespressuretransmitterswith
optionalcode/FS1areapplicableforusein
hazardouslocations.
• ApplicableStandard:
Class3600:2011,Class3610:2010,
Class3611:2004,Class3810:2005
ANSI/ISA-60079-0:2009,ANSI/ISA-60079-11:2009
NEMA250:1991
• Rating
IntrinsicallySafefor
ClassI,II,IIIDivision1,
GroupsA,B,C,D,E,F,GT4
ClassIZone0AExiaIICT4
 Nonincendivefor
ClassI,II,IIIDivision2
GroupsA,B,C,D,F,GT4
 ClassI,Zone2GroupIICT4
• Ambienttemperature:–60to60°C
• Enclosure:Type4X
Note2. Installation
InstallationshouldbeinaccordancewithControl
DrawingIFM022-A12.
Note3. MaintenanceandRepair
• Theinstrumentmodicationorpartsreplacement
byotherthanauthorizedrepresentativeof
YokogawaElectricCorporationisprohibitedand
willvoidFactoryMutualIntrinsicallysafeand
NonincendiveApproval.
<2. Handling Cautions> 9
IM01C25A01-01E
b. FM Intrinsically Safe/Nonincendive for
Fieldbus Type (Except for EJX90A)
EJX/EJA-ESeriespressuretransmitterswithoptional
code/FS15areapplicableforuseinhazardous
locations.
Note1.
• ApplicableStandard:
Class3600:2011,Class3610:2010,
Class3611:2004,Class3810:2005
ANSI/ISA-60079-0:2009,ANSI/ISA-60079-11:2009
 NEMA250:1991
• Rating
 IntrinsicallySafewithEntity/FISCOfor
ClassI,II,IIIDivision1,
GroupsA,B,C,D,E,F,GT4
 ClassIZone0AExiaIICT4
 Nonincendiveeldwiring/FNICOfor
ClassI,IIDivision2
GroupsA,B,C,D,F,GT4
 ClassIIIDivision1T4
 ClassI,Zone2GroupIICT4
• Ambienttemperature:–40to60°C
• Enclosure:Type4X
• ElectricalConnection:
1/2NPTfemale,M20female
Note2. Installation
InstallationshouldbeinaccordancewithControl
DrawingIFM024-A12.
<2. Handling Cautions> 10
IM01C25A01-01E
c. FM Intrinsically Safe/Nonincendive for
Fieldbus Type for EJX90A
EJXmultivariabletransmitterwithoptionalcode
/FS15areapplicableforuseinhazardouslocations.
Note1.
• ApplicableStandard:
Class3600:2011,Class3610:2010,
Class3611:2004,Class3810:2005
ANSI/ISA-60079-0:2009,ANSI/ISA-60079-11:2009,
ANSI/ISA-60079-27:2006
 NEMA250:1991
• Rating
 IntrinsicallySafewithEntity/FISCOforClassI,II,III
Division1GroupsA,B,C,D,E,F,GT4
 ClassIZone0AExiaIICT4
 Nonincendiveeldwiring/FNICOforClassI,II
Division2GroupsA,B,C,D,F,GT4
 ClassIIIDivision1T4
 ClassI,Zone2GroupIICT4
• Ambienttemperature:–40to60°C
• Enclosure:Type4X
• ElectricalConnection:1/2NPTfemale,M20
female
Note2. Installation
InstallationshouldbeinaccordancewithControl
DrawingIFM026-A12.
<2. Handling Cautions> 11
IM01C25A01-01E
<2. Handling Cautions> 12
IM01C25A01-01E
d. FM Explosionproof
CautionforFMexplosionprooftype.
Note1. EJX/EJA-ESeriespressuretransmitterswith
optionalcode/FF1or/V1Fareapplicablefor
useinhazardouslocations.
• ApplicableStandard:FM3600,FM3615,FM3810,
ANSI/NEMA250
• ExplosionproofforClassI,Division1,GroupsB,C
and D.
• Dust-ignitionproofforClassII/III,Division1,
GroupsE,FandG.
• Enclosure:Type4X
• TemperatureClass:T6
• AmbientTemperature:–40to60°C
• SupplyVoltage:42Vdcmax.
32Vdcmax.(FOUNDATIONFieldbusand
PROFIBUSPAtype)
9to28Vdc,27mW(LowPowertype)
9to30Vdc,250mW(RS485Modbus
CommunicationType)
• Outputsignal:4to20mA
15 mA (FOUNDATIONFieldbusandPROFIBUSPA
type)
1to5V(LowPowertype)
RS485Modbus(RS485ModbusCommunication
Type)
Note2. Wiring
• AllwiringshallcomplywithNationalElectrical
CodeANSI/NFPA70andLocalElectricalCodes.
• WheninstalledinDivision1,“FACTORYSEALED,
CONDUITSEALNOTREQUIRED.
• WiringconnectionforoutputsignalcodeQ(Low
Powertype)shallfollowthediagrambelow.
F0218.ai
Three-Wire Connection
Pressure Transmitters
Power Supply
Voltmeter
SUPPLY
+
SUPPLY
A
+
+
Four-Wire Connection
Pressure Transmitters
Power Supply
Voltmeter
SUPPLY
+
SUPPLY
A
+
+
<2. Handling Cautions> 13
IM01C25A01-01E
Note3. Operation
• Keepthe“WARNING”nameplateattachedtothe
transmitter.
 WARNING:OPENCIRCUITBEFORE
REMOVINGCOVER.FACTORYSEALED,
CONDUITSEALNOTREQUIRED.INSTALLIN
ACCORDANCEWITHTHEUSERSMANUALIM
01C25.
• Takecarenottogeneratemechanicalsparking
whenaccessingtotheinstrumentandperipheral
devicesinahazardouslocation.
Note4. MaintenanceandRepair
• Theinstrumentmodicationorpartsreplacement
byotherthanauthorizedrepresentativeof
YokogawaElectricCorporationisprohibitedand
willvoidFactoryMutualExplosionproofApproval.
e. FM Intrinsically Safe and Explosion Proof
Combination for HART/BRAIN Protocol
Type
EJX/EJA-ESeriespressuretransmitterswith
optionalcode/FU1or/V1U1canbeselectedthe
typeofprotection(FMIntrinsicallySafeorFM
Explosionproof)foruseinhazardouslocations.
Note1. Fortheinstallationofthistransmitter,oncea
particulartypeofprotectionisselected,any
othertypeofprotectioncannotbeused.The
installationmustbeinaccordancewiththe
descriptionaboutthetypeofprotectioninthis
instruction manual.
Note2. Inordertoavoidconfusion,unnecessary
markingiscrossedoutonthelabelother
thantheselectedtypeofprotectionwhenthe
transmitter is installed.
2.4.2 CSACertication
a. CSA Intrinsically Safe for HART/BRAIN
Protocol Type (Except for EJX90A)
CautionforCSAIntrinsicallysafeandnonincendive
type.(Followingcontentsreferto“DOCNo.ICS013-
A13”)
Note1. EJX/EJA-ESeriespressuretransmitterswith
optionalcode/CS1areapplicableforusein
hazardouslocations.
Certicate:1606623
[ForCSAC22.2]
• ApplicableStandard:C22.2No.0,C22.2No.0.4,
C22.2No.25,C22.2No.94,C22.2No.157,
C22.2No.213,C22.2No.60079-0,
C22.2No.61010-1,C22.2No.61010-2-030
• IntrinsicallySafeforClassI,Division1,Groups
A,B,C&D,ClassII,Division1,GroupsE,F&G,
ClassIII,Division1
• NonincendiveforClassI,Division2,GroupsA,B,
C&D,ClassII,Division2,GroupsF&G,ClassIII,
Division 1
• Enclosure:Type4X
• Temp.Code:T4
• Amb.Temp.:–50*to60°C
 *–15°Cwhen/HEisspecied.
• ProcessTemperature:120°Cmax.
[ForCSAE60079]
• ApplicableStandard:CAN/CSAE60079-11,
CAN/CSAE60079-15,IEC60529:2001
• ExiaIICT4,ExnLIICT4
• AmbientTemperature:–50to60°C
• Max.ProcessTemp.:120°C
• Enclosure:IP66/IP67
Note2. EntityParameters
• Intrinsicallysaferatingsareasfollows:
 MaximumInputVoltage(Vmax/Ui)=30V
 MaximumInputCurrent(Imax/Ii)=200mA
 MaximumInputPower(Pmax/Pi)=0.9W
 MaximumInternalCapacitance(Ci)=10nF
 MaximumInternalInductance(Li)=0µH
• Type"n"orNonincendiveratingsareasfollows:
 MaximumInputVoltage(Vmax/Ui)=30V
 MaximumInternalCapacitance(Ci)=10nF
 MaximumInternalInductance(Li)=0µH
• InstallationRequirements
 Uo≤Ui,Io≤Ii,Po≤Pi,
 Co≥Ci+Ccable,Lo≥Li+Lcable
 Voc≤Vmax,Isc≤Imax,
 Ca≥Ci+Ccable,La≥Li+Lcable
 Uo,Io,Po,Co,Lo,Voc,Isc,CaandLaare
parametersofbarrier.
Note3. Installation
• Inanysafetybarreirusedoutputcurrentmust
belimitedbyaresistor'R'suchthatIo=Uo/Ror
Isc=Voc/R.
• ThesafetybarriermustbeCSAcertied.
• Inputvoltageofthesafetybarriermustbeless
than250Vrms/Vdc.
• InstallationshouldbeinaccordancewithCanadian
ElectricalCodePartIandLocalElectricalCode.
• Dust-tightconduitsealmustbeusedwhen
installedinClassIIandIIIenvironments.
• Theinstrumentmodicationorpartsreplacement
byotherthanauthorizedrepresentativeof
YokogawaElectricCorporationandYokogawa
CorporationofAmericaisprohibitedandwill
voidCanadianStandardsIntrinsicallysafeand
nonincendiveCertication.
<2. Handling Cautions> 14
IM01C25A01-01E
F0206.ai
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
Pressure Transmitters Safety Barrier
Supply
Hazardous Location Nonhazardous Location
General
Purpose
Equipment
+
+
+
+
[Intrinsically Safe]
Group IIC, Zone 0
F0207.ai
Pressure Transmitters
Supply
Hazardous Location Nonhazardous Location
+
+
Class I, II, Division 2,
Groups A, B, C, D, F, G
Class III, Division 1.
Not Use
Safety Barrier
[Nonincendive]
CSA Certified
Equipment
([nL] or
nonincendive)
Group IIC, Zone 2
b. CSA Intrinsically Safe for Fieldbus Type
(Except for EJX90A)
EJX/EJA-ESeriespressuretransmitterswithoptional
code/CS15areapplicableforuseinhazardous
locations.
• Certicate:1689689
• Applicablestandard:C22.2No.0,C22.2No.0.4,
C22.2No.25,C22.2No.94,C22.2No.157,
C22.2No.213,C22.2No.61010-1,
C22.2No.61010-2-030,C22.2No.60079-0,
 CAN/CSAE60079-0,CAN/CSAE60079-11,
CAN/CSAE60079-15,IEC60529
• CSAIntrinsicallySafeApproval
 ClassI,Division1,GroupsA,B,C,&D;ClassII,
Division1,GroupsE,F&G;ClassIII;ExiaIICT4
 AmbientTemperature:–40*to60°C(–40*to
14F)Encl.Type4X,IP66/IP67
 *–15°Cwhen/HEisspecied.
• CSANonincendiveApproval
 ClassI,Division2,GroupsA,B,C,&D;ClassII,
Division2,GroupsF&G;ClassIII;ExnLIICT4
 AmbientTemperature:–40*to60°C(–40*to
14F)Encl.Type4X,IP66/IP67
 *–15°Cwhen/HEisspecied.
Caution for CSA Intrinsically Safe Type.
(Following Contents Refer to “DOC. No.
ICS018)
Installation Diagram for Intrinsically Safe
(Division 1 Installation)
Non-Hazardous Location
Hazardous Location
F0229.ai
Terminator
Safety Barrier
Field Instruments
Pressure
Transmitter
Field Instruments
+
+
+
Terminator
+
+
Note1. ThesafetybarriermustbeCSAcertied.
Note2. Inputvoltageofthesafetybarriermustbeless
than250Vrms/Vdc.
Note3. Installationshouldbeinaccordancewith
CanadianElectricalCodePartIandlocal
ElectricalCode.
Note4. Donotalterdrawingwithoutauthorizationfrom
CSA.
Electrical Data:
•Rating1(Entity)
 ForGroupsA,B,C,D,E,F,andGorGroupIIC
 Ui(vmax)=24Vdc
 Ii(Imax)=250mA
 Pi(Pmax)=1.2W
 Ci=3.52nF
 Li=0μH
or
•Rating2(FISCO)
 ForGroupsA,B,C,D,E,F,andGorGroupIIC
 Ui(vmax)=17.5Vdc
 Ii(Imax)=380mA
 Pi(Pmax)=5.32W
 Ci=3.52nF
Li=0μH
or
<2. Handling Cautions> 15
IM01C25A01-01E
• Rating3(FISCO)
 ForGroupsC,D,E,F,andGorGroupIIB
 Ui(vmax)=17.5Vdc
 Ii(Imax)=460mA
 Pi(Pmax)=5.32W
 Ci=3.52nF
 Li=0μH
Installationrequirements;
 Po≤PiUo≤UiIo≤Ii,
 Co≥Ci+CcableLo≥Li+Lcable
 Vmax≥VocImax≥Isc
 Ca≥Ci+CcableLa≥Li+Lcable
 Uo,Io,Po,Co,Lo,Voc,Isc,CaandLaareparameters
ofbarrier.
Caution for CSA Non-incendive Type.
(Following contents refer to “DOC. No.
ICS018)
Installation Diagram for Non-incendive or Type of
protection “n” (Division 2 Installation)
Non-Hazardous location
Hazardous location
F0230.ai
Terminator
CSA Certified
Equipment [nL]
Pressure
Transmitter
SUPPLY
Terminator
+
Transmitter
+
Transmitter
+
+ –
+ –
Note1. Installationshouldbeinaccordancewith
CanadianElectricalCodePartIandlocal
ElectricalCode.
Note2. Dust-tightconduitsealmustbeusedwhen
installedinclassIIandIIIenvironments.
Note3. Donotalterdrawingwithoutauthorizationfrom
CSA.
Electrical Data:
•Rating(includingFNICO)
 UiorVmax=32V
 Ci=3.52nF
 Li=0μH
c. CSA Explosionproof Type
CautionforCSAexplosionprooftype.
Note1. EJX/EJA-ESeriespressuretransmitterswith
optionalcode/CF1or/V1Fareapplicablefor
useinhazardouslocations.
• Certicate:2014354
• ApplicableStandard:C22.2No.0,
C22.2No.0.4,C22.2No.0.5,C22.2No.25,
C22.2No.30,C22.2No.94,C22.2No.61010-1,
C22.2No.61010-2-030,C22.2No.60079-0,
C22.2No.60079-1
• Explosion-proofforClassI,GroupsB,CandD.
• Dustignition-proofforClassII/III,GroupsE,Fand
G.
• Enclosure:Type4X
• TemperatureCode:T6...T4
• ExdIICT6...T4
• Enclosure:IP66/IP67
• MaximumProcessTemperature:120°C(T4),
10C(T5),85°C(T6)
• AmbientTemperature:–50*to75°C(T4),
–50*to80°C(T5),–50*to75°C(T6)
 *–15°Cwhen/HEisspecied.
• SupplyVoltage:42Vdcmax.
32Vdcmax.(FOUNDATIONFieldbusand
PROFIBUSPAtype)
9to28Vdc,27mW(LowPowertype)
9to30Vdc,250mW(RS485Modbus
CommunicationType)
• OutputSignal:4to20mAdc
15 mA (FOUNDATIONFieldbusandPROFIBUSPA
type)
1to5V(LowPowertype)
RS485Modbus(RS485ModbusCommunication
Type)
Note2. Wiring
• AllwiringshallcomplywithCanadianElectrical
CodePartIandLocalElectricalCodes.
• Inhazardouslocation,wiringshallbeinconduitas
showninthegure.
• WARNING:
 ASEALSHALLBEINSTALLEDWITHIN50cmOF
THEENCLOSURE.
 UNSCELLEMENTDOITÊTREINSTALLÉÀ
MOINSDE50cmDUBOÎTIER.
• WARNING:
 WHENINSTALLEDINCL.I,DIV2,SEALNOT
REQUIRED.
 UNEFOISINSTALLÉDANSCLI,DIV2,AUCUN
JOINTN'ESTREQUIS.
<2. Handling Cautions> 16
IM01C25A01-01E
Non-hazardous
Location Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Non-Hazardous
Locations
Hazardous Locations Division 1
50 cm Max.
Sealing Fitting Conduit
Transmitter
F0208.ai
Non-Hazardous
Locations
Hazardous Locations Division 2
Non-hazardous
Location Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Sealing Fitting
Transmitter
F0209.ai
• Allwiringshallcomplywithlocalinstallation
requirements and local electrical code.
• Inhazardouslocations,thecableentrydevices
shallbeofacertiedameprooftype,suitablefor
theconditionsofuseandcorrectlyinstalled.
• Unusedaperturesshallbeclosedwithsuitable
ameproofcertiedblankingelements.(Theplug
attachedisameproofcertied.)
• WiringconnectionforoutputsignalcodeQ(Low
Powertype)shallfollowthediagrambelow.
F0219.ai
Three-Wire Connection
Pressure Transmitters
Power Supply
Voltmeter
SUPPLY
+
SUPPLY
A
+
+
Four-Wire Connection
Pressure Transmitters
Power Supply
Voltmeter
SUPPLY
+
SUPPLY
A
+
+
Note3. Operation
• WARNING:
 AFTERDE-ENERGIZING,DELAY5MINUTES
BEFOREOPENING.
 APSPOWER-OFF,ATTENDRE5MINUTES
AVANTD'OUVRIR.
• WARNING:
 WHENAMBIENTTEMPERATURE≥65°C,USE
THEHEAT-RESISTINGCABLES≥90°C.
 QUANDLATEMPÉRATUREAMBIANTE≥65°C,
UTILISEZDESCÂBLESRÉSISTANTESÁLA
CHALEUR≥90°C.
• Takecarenottogeneratemechanicalsparking
whenaccessingtotheinstrumentandperipheral
devicesinahazardouslocation.
Note4. MaintenanceandRepair
• Theinstrumentmodicationorpartsreplacement
byotherthanauthorizedrepresentativeof
YokogawaElectricCorporationandYokogawa
CorporationofAmericaisprohibitedandwillvoid
CanadianStandardsExplosionproofCertication.
d. CSA Intrinsically Safe and Explosion-proof
Combination for HART/BRAIN Protocol
Type (Except for EJX90A)
EJX/EJA-ESeriespressuretransmitterswith
optionalcode/CU1or/V1U1canbeselectedthe
typeofprotection(CSAIntrinsicallySafeorCSA
Explosionproof)foruseinhazardouslocations.
Note1. Fortheinstallationofthistransmitter,oncea
particulartypeofprotectionisselected,any
othertypeofprotectioncannotbeused.The
installationmustbeinaccordancewiththe
descriptionaboutthetypeofprotectioninthis
instruction manual.
Note2. Inordertoavoidconfusion,unnecessary
markingiscrossedoutonthelabelother
thantheselectedtypeofprotectionwhenthe
transmitter is installed.
2.4.3 ATEXCertication
(1) Technical Data
a. ATEX Intrinsically Safe for HART/BRAIN
Protocol Type (Except for EJX90A)
CautionforATEXIntrinsicallysafetype.
Note1. EJX/EJA-ESeriespressuretransmitterswith
optionalcode/KS21forpotentiallyexplosive
atmospheres.
• No.DEKRA11ATEX0228X
• ApplicableStandard:
EN60079-0:2012+A11:2013
EN60079-11:2012
<2. Handling Cautions> 17
IM01C25A01-01E
• TypeofProtectionandMarkingcode:
ExiaIICT4Ga
 ExiaIIICT85ºCT100ºCT120ºCDb
• Group:II
• Category:1G,2D
• AmbientTemperatureforEPLGa:
–50to60°C
• AmbientTemperatureforEPLDb:
–30*to60°C
*–15°Cwhen/HEisspecied.
• ProcessTemperature(Tp.):120°Cmax.
• MaximumSurfaceTemperatureforEPLDb:
T8C(Tp.:80°C)
T100°C(Tp.:100°C)
T120°C(Tp.:120°C)
• Enclosure:IP66/IP67
TosatisfyIP66orIP67,applywaterproofglandsto
theelectricalconnectionport.
Note2 ElectricalData
• IntypeofexplosionprotectionintrinsicsafetyExia
IICorExiaIIIC,onlyforconnectiontoacertied
intrinsicallysafecircuitwithfollowingmaximum
values:
 Ui=30V
 Ii=200mA
 Pi=0.9W
 (LinearSource)
 Maximuminternalcapacitance;Ci=27.6nF
 Maximuminternalinductance;Li=0µH
 Whenthelightningprotectoroptionisspecied,
theapparatusisnotcapableofwithstandingthe
500VinsulationtestrequiredbyEN60079-11.This
mustbetakenintoaccountwheninstallingthe
apparatus.
Note3. Installation
• Refertothecontroldrawing.Allwiringshallcomply
withlocalinstallationrequirements.
Pressure Transmitters
Supply Safety Barrier *1
Nonhazardous Location
[Control Drawing]
Hazardous Location
+
+
F0210.ai
 *1:Anysafetybarriersmustbealinearpowersource
whoseoutputcurrentisresistivelylimited.
Note4. MaintenanceandRepair
• Theinstrumentmodicationorpartsreplacement
byotherthanauthorizedrepresentativeof
YokogawaElectricCorporationisprohibitedand
willvoidDEKRAIntrinsicallysafeCertication.
Note5. SpecialConditionsforSafeUse
WARNING
• WhentheenclosureofthePressureTransmitter
ismadeofaluminum,ifitismountedinanarea
wheretheuseofcategory1Gequipmentis
required,itmustbeinstalledsuch,that,evenin
theeventofrareincidents,ignitionsourcesdueto
impactandfrictionsparksareexcluded.
• Electrostaticchargesonthecoatedpartsof
PressureTransmittershallbeavoided.
• Electrostaticchargemaycauseanexlosion
hazard.Avoidanyactionsthatcausethe
generationofelectrostaticcharge,suchasrubbing
withadryclothoncoatingfaceoftheproduct.
• IncaseoftheenclosureofthePressure
Transmitterwithpaintlayers,ifitismountedinan
areawheretheuseofcategory2Dequipmentis
required,itshallbeinstalledinsuchawaythatthe
riskfromelectrostaticdischargesandpropagating
brushdischargescausedbyrapidowofdustis
avoided.
b. ATEX Intrinsically Safe for Fieldbus Type
(Except for EJX90A)
CautionforATEXIntrinsicallysafetype.
Note1. EJX/EJA-Eseriespressuretransmitterswith
optionalcode/KS26areapplicableforusein
hazardouslocations.
• No.KEMA04ATEX1116X
• ApplicableStandard:
 EN60079-0:2012+A11:2013
EN60079-11:2012
Note2. Ratings
TypeofProtectionandMarkingCode:
ExiaIIC/IIBT4Ga
ExiaIIICT8CT100°CT120°CDb
Group:II
Category:1G,2D
AmbientTemperatureforEPLGa:–40to60°C
AmbientTemperatureforEPLDb:–30*to60°C
 *–15°Cwhen/HEisspecied.
MaximumProcessTemperature(Tp.):120°C
MaximumSurfaceTemperatureforEPLDb.
T8C(Tp.:80°C)
T100°C(Tp.:100°C)
T120°C(Tp.:120°C)
AmbientHumidity:
0to100%(Nocondensation)
DegreeofProtectionoftheEnclosure:
IP66/IP67
<2. Handling Cautions> 18
IM01C25A01-01E
Electrical Data
• WhencombinedwithTrapezoidalandRectangular
outputcharacteristicFISCOmodelIICbarrier
 Ui=17.5V,Ii=380mA,Pi=5.32W,
 Ci=3.52nF,Li=0μH
• WhencombinedwithLinearcharacteristicbarrier
 Ui=24V,Ii=250mA,Pi=1.2W,
 Ci=3.52nF,Li=0μH
• WhencombinedwithTrapezoidalorRectangular
outputcharacteristicFISCOmodelIIBbarrier
 Ui=17.5V,Ii=460mA,Pi=5.32W,
 Ci=3.52nF,Li=0μH
Note3. Installation
• Allwiringshallcomplywithlocalinstallation
requirements.(Refertotheinstallationdiagram)
Note4. MaintenanceandRepair
• Theinstrumentmodicationorpartsreplacement
byotherthanauthorizedrepresentativeof
YokogawaElectricCorporationisprohibitedand
willvoidDEKRAIntrinsicallysafeCertication.
Note5. SpecialConditionsforSafeUse
WARNING
• InthecasewheretheenclosureofthePressure
Transmitterismadeofaluminium,ifitismounted
inanareawheretheuseofcategory1G
apparatusisrequired,itmustbeinstalledsuch,
thatevenintheeventofrareincidents,ignition
sourcesduetoimpactandfrictionsparksare
excluded.
• Electrostaticchargemaycauseanexplosion
hazard.Avoidanyactionsthatcausethe
generationofelectrostaticcharge,suchasrubbing
withadryclothoncoatingfaceoftheproduct.
• InthecasewheretheenclosureofthePressure
Transmitterismadeofaluminum,ifitismountedin
anareawheretheuseofcategory2Dapparatusis
required,itshallbeinstalledinsuchawaythatthe
riskfromelectrostaticdischargesandpropagating
brushdischargescausedbyrapidowofdustis
avoided.
• TosatisfyIP66orIP67,applywaterproofglandsto
theelectricalconnectionport.
• Whenthelightningprotectoroptionisspecied,
theapparatusisnotcapableofwithstandingthe
500VinsulationtestrequiredbyEN60079-11.
 Thismustbetakenintoaccountwheninstalling
theapparatus.
Note6. InstallationInstructions
Non-Hazardous Location
Hazardous Location
F0231.ai
Terminator
Safety Barrier
Transmitter
Pressure
Transmitter
Transmitter
+
+
+
Terminator
+
+
[Installation Diagram]
SUPPLY
• Intherating1(*1),theoutputcurrentofthebarrier
mustbelimitedbyaresistor‘Ra’suchthatIo=Uo/
Ra.
• Intherating2(*2),theoutputofthebarriermustbe
thecharacteristicsofthetrapezoidortherectangle
andthistransmittercanbeconnectedtoFieldbus
equipmentwhichareinaccordingtotheFISCO
model.
• Theterminatorsmaybebuiltinbyabarrier.
• Morethanonetransmittermaybeconnectedto
thepowersupplyline.
• Theterminatorandthesafetybarriershallbe
certied.
Electricaldata:
MaximumInputVoltageUi:24V
*1:
Rating 1
MaximumInputCurrentIi:250mA
MaximumInputPowerPi:1.2W
MaximumInternalCapacitanceCi:3.52nF
MaximumInternalInductanceLi:0μH
or
MaximumInputVoltageUi:17.5V
*2:
Rating 2
MaximumInputCurrentIi:380mA
MaximumInputPowerPi:5.32W
MaximumInternalCapacitanceCi:3.52nF
MaximumInternalInductanceLi:0μH
or
MaximumInputVoltageUi:17.5V
MaximumInputCurrentIi:460mA
MaximumInputPowerPi:5.32W
MaximumInternalCapacitanceCi:3.52nF
MaximumInternalInductanceLi:0μH
<2. Handling Cautions> 19
IM01C25A01-01E
c. ATEX Intrinsically Safe for Fieldbus Type
for EJX90A
CautionforATEXIntrinsicallysafetype.
Note1. EJXmultivariabletransmitterwithoptional
code/KS26areapplicableforuseinhazardous
locations:
• No.KEMA06ATEX0278X
• ApplicableStandard:
EN60079-0:2012+A11:2013
EN60079-11:2012
Note2. Ratings
TypeofProtectionandMarkingCode:
ExiaIIC/IIBT4Ga
ExiaIIICT8CT100°CT120°CDb
Group:II
Category:1G,2D
AmbientTemperatureforEPLGa:
–40to60°C
AmbientTemperatureforEPLDb:
–30*to60°C
 *–15°Cwhen/HEisspecied.
MaximumProcessTemperature(Tp.):120°C
MaximumSurfaceTemperatureforEPLDb.
T8C(Tp.:80°C)
T100°C(Tp.:100°C)
T120°C(Tp.:120°C)
AmbientHumidity:
 0to100%(Nocondensation)
DegreeofProtectionoftheEnclosure:
IP66/IP67
Electrical Data
• WhencombinedwithTrapezoidalorRectanglar
outputcharacteristicFISCOmodelIICbarrier
[Supplycircuit(terminals+and-)]
Ui=17.5V,Ii=380mA,Pi=5.32W,
Ci=3.52nF,Li=0µH
[Sensorcircuit]
Uo=7.63V,Io=3.85mA,Po=0.008W,
Co=4.8µF,Lo=100mH
• WhencombinedwithLinearcharacteristicbarrier
[Supplycircuit(terminals+and-)]
Ui=24V,Ii=250mA,Pi=1.2W,
Ci=3.52nF,Li=0µH
[Sensorcircuit]
Uo=7.63V,Io=3.85mA,Po=0.008W,
Co=4.8µF,Lo=100mH
• WhencombinedwithTrapezoidalorRectanglar
outputcharacteristicFISCOmodelIIBbarrier
[Supplycircuit(terminals+and-)]
Ui=17.5V,Ii=460mA,Pi=5.32W,
Ci=3.52nF,Li=0µH
[Sensorcircuit]
Uo=7.63V,Io=3.85mA,Po=0.008W,
Co=4.8µF,Lo=100mH
Note3. Installation
• Allwiringshallcomplywithlocalinstallation
requirements.(Refertotheinstallationdiagram)
Note4. MaintenanceandRepair
• Theinstrumentmodicationorpartsreplacement
byotherthanauthorizedrepresentativeof
YokogawaElectricCorporationisprohibitedand
willvoidDEKRAIntrinsicallysafeCertication.
Note5. SpecialConditionsforSafeUse
WARNING
• InthecasewheretheenclosureofthePressure
Transmitterismadeofaluminium,ifitismounted
inanareawheretheuseofcategory1Gapparatus
isrequired,itmustbeinstalledsuch,thatevenin
theeventofrareincidents,ignitionsourcesdueto
impactandfrictionsparksareexcluded.
• Electrostaticchargemaycauseanexplosion
hazard.Avoidanyactionsthatcausethe
generationofelectrostaticcharge,suchasrubbing
withadryclothoncoatingfaceoftheproduct.
• InthecasewheretheenclosureofthePressure
Transmitterismadeofaluminum,ifitismountedin
anareawheretheuseofcategory2Dapparatusis
required,itshallbeinstalledinsuchawaythatthe
riskfromelectrostaticdischargesandpropagating
brushdischargescausedbyrapidowofdustis
avoided.
• TosatisfyIP66orIP67,applywaterproofglandsto
theelectricalconnectionport.
• Whenthelightningprotectoroptionisspecied,
theapparatusisnotcapableofwithstandingthe
500VinsulationtestrequiredbyEN60079-11.
 Thismustbetakenintoaccountwheninstalling
theapparatus.
Note6. Installationinstructions
Non-Hazardous Location
Hazardous Location
F0232.ai
Terminator
Safety Barrier
Transmitter
Pressure
Transmitter
Transmitter
+
+
+
Terminator
+
+
SUPPLY
RTD
Pt100.3wire
[Installation Diagram]
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57

YOKOGAWA DPharp EJA120E Installation guide

Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI